Brand: GESTRA
GESTRA NRS 1-50 Water Level Limiter Level Switch SIL 3
Description
GESTRA NRS 1-50 Water Level Limiter Level Switch SIL 3: overview
The GESTRA NRS 1-50 is a rail-mounted level switch that evaluates one or two NRG level electrodes and acts as the water level limiter of a steam boiler or pressurised hot-water plant. When the electrodes are exposed by falling water, and after the de-energising delay, its two output contacts open the safety circuit of the heating.
The shut-off is interlocked in the safety circuit and can only be released once the electrode is immersed again. Two additional signal outputs close instantly for external alarms, and an automatic self-test routine continuously checks the switch, the electrode and the wiring. The datasheet is published in versions for one electrode and for two electrodes.
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. We list the NRS 1-50 for buyers who need an exact GESTRA type for a repair, a replacement or a new project and want a clear technical summary before asking for a quotation. The facts below are condensed from the manufacturer datasheet, and where a value is not stated there, we leave it out rather than guess.
Control and evaluation units for boiler water level, conductivity and safety circuits are normally replaced as a matched set with their sensors. Because the electrical interface, supply voltage and sensor type must agree, buyers usually need the exact type designation rather than a generic equivalent. Quote the full designation NRS 1-50 together with the nameplate data of the old unit, and we can check the details before a quotation is prepared.
Key features of the NRS 1-50
- Equipment combination with NRG 16-50, NRG 17-50, NRG 19-50 and NRG 111-50 corresponds to a type B subsystem, SIL 3, architecture 1oo2
- Approved with further electrodes for VdTUV Bulletin 100 and, with selected types, for marine use under DNV and Lloyd’s Register directives
- Two volt-free make contacts in the safety circuit and two signal outputs
- Sensitivity ranges selectable to suit the boiler water conductivity
- Stand-by input for monitoring rinsing and bypass time with the SRL 6-50 logic unit
- Test button and LED indication for alarms and errors
GESTRA NRS 1-50 technical specifications
| Parameter | Value |
|---|---|
| Type | NRS 1-50 (versions for one or two electrodes) |
| Supply voltage | 24 VDC +/-20 %, 0.3 A; 100-240 VAC +10/-15 %, 47-63 Hz, 0.2 A optional |
| External fuse | M 0.5 A (semi-delay) |
| Power consumption | 7 VA |
| Response sensitivity (water at 25 °C) | Above 0.5 and below 1000 µS/cm, or above 10 and below 10000 µS/cm |
| Stand-by input | 2 volt-free inputs, 24 VDC, max. bypass time 5 minutes |
| Safety circuit | 2 volt-free make contacts |
| Signal outputs | 2, closing without delay on alarm |
| Functional safety | SIL 3, type B subsystem, architecture 1oo2 (with listed NRG 1…-50 electrodes) |
| Hazardous areas | Not to be used in potentially explosive atmospheres |
All values above come from the manufacturer datasheet for the NRS 1-50 and its family. Related types named in the datasheet, such as NRS 1-50 for one electrode and for two electrodes, have their own ratings, so check the type designation before ordering.
Typical applications in Oman and the GCC
Process steam and hot water are everywhere in the region. Food and beverage plants, hospitals, hotels and laundries run package boilers; refineries, petrochemical sites and utility stations in Oman and the wider Gulf operate larger steam generators and thermal desalination units. In hot and dusty climates, cabinet temperature, cable routing and the condition of connectors deserve extra attention, and a spare unit on the shelf can shorten an outage considerably.
- Burner and heating cut-out on low water in industrial and utility steam boilers
- Boiler rooms at power and desalination plants that follow EN 12952 and EN 12953 practice
- Marine and offshore support vessels using the listed marine-approved electrode types
- Upgrades of existing GESTRA water level limiter loops where the switch must be replaced
Selection and compatibility notes for the NRS 1-50
- Decide whether you need the version for one electrode or for two electrodes.
- Pick the electrode type from the list in the datasheet. The SIL 3 combination applies to NRG 16-50, NRG 17-50, NRG 19-50 and NRG 111-50.
- Choose the supply voltage version, 24 VDC as standard or 100-240 VAC as an option.
- Set the response sensitivity switch to match the conductivity of the boiler water and the cable type you installed.
If you are unsure which variant of the NRS 1-50 you have, photograph the nameplate and send the full text. The type, the pressure class or supply voltage and any suffix letters are what we need to match the right part.
Planning a spare is straightforward if you note a few details when the cabinet is open. Record the type designation, the supply voltage, the sensor type connected and the way the outputs are wired. A controller that is replaced with the same type can usually be set up quickly from the old parameters, so photograph the settings before you remove the old unit. For a critical boiler, many operators keep one spare evaluation unit on the shelf, which turns a failed test during an inspection into a short job instead of a long wait.
Installation and commissioning
- Clip the unit onto a TH 35 support rail in the control cabinet and protect it with an external M 0.5 A fuse.
- Use a screened multi-core cable such as LiYCY 4 x 0.5 mm2, up to 100 m, for the 10 microsiemens setting, or a double-screened low-capacitance cable up to 30 m for 0.5 microsiemens.
- If the electrode sits in an external level pot, connect the stand-by input to the SRL 6-50 logic unit so that rinsing is supervised.
- The actuator in the safety circuit, such as an auxiliary contactor, must be considered separately in the overall safety assessment.
Always follow the manufacturer manual and the safety rules of your site and boiler inspection body during installation and commissioning. Isolate and depressurise the plant before any work on pressure-bearing parts and lock off the electrical supply before opening a terminal box or cabinet.
Maintenance and service
- Press the test button to simulate a low-water alarm and confirm that both safety contacts open.
- Review the LED indications after any alarm and trace error messages to the electrode, cable or switch.
- Keep records of proof tests in line with the proof-test interval stated by the manufacturer.
Record each test of the NRS 1-50 in the plant log. A written history of tests and replacements helps the inspector, shortens fault finding and gives you a clear basis for deciding when a spare should be ordered.
Related products and ordering notes
Matching parts are the NRG 16-50 family of electrodes, the SRL 6-50 logic unit and the NRG 16-36 for selected approvals. Quote the electrode type you intend to connect.
When you order a NRS 1-50, state the quantity, the full type designation and any option or length that applies, and tell us the plant tag or project if you have it. Lead times depend on stock and on the manufacturer, so please ask early for planned shutdowns.
Frequently asked questions
What does the NRS 1-50 do? It evaluates one or two level electrodes and opens the safety circuit of the heating when the water level falls below the set minimum.
Which SIL level is stated? The combination of NRG 1…-50 electrodes and the NRS 1-50 corresponds to a type B subsystem with SIL 3 under IEC 61508, with a 1oo2 architecture.
What supply voltages are possible? 24 VDC plus or minus 20 percent as standard, and 100 to 240 VAC as an option.
Which sensitivity ranges are available? Above 0.5 and below 1000 microsiemens per cm, or above 10 and below 10000 microsiemens per cm.
Can it be used in hazardous areas? No. The datasheet says it must not be used in potentially explosive atmospheres.
Documents and quotation
The manufacturer datasheet for the NRS 1-50 is available from us on request and is attached to this listing where file size allows. To receive a quotation, send an RFQ with the part number NRS 1-50, the quantity and your delivery location in Oman or the GCC, and our team will reply with availability and lead time.
Datasheets & Documents
- Datasheet GESTRA NRS 1-50 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
GESTRA is the German steam and condensate specialist behind the UNA ball float steam traps, the MPA blowdown valves and a long line of boiler level and conductivity controls. It was founded in Bremen in 1902 by Gustav F. Gerdts, and has been part of Spirax Sarco since 2017.
Seven Star LLC is an independent supplier in Muscat. We list GESTRA steam traps, blowdown valves and boiler control equipment, and supply GESTRA parts and spares to boiler houses and process plants in Oman and the GCC.
GESTRA company profile
| Established | 29 October 1902, Bremen, Germany, by Gustav Friedrich Gerdts; renamed Gustav F. Gerdts KG in 1907 |
|---|---|
| Ownership history | Became a stock corporation (GESTRA AG) in 1987, was taken over by Flowserve in 2002, and has been part of the Spirax Sarco group since 2017 |
| Product families | Steam traps, non-return and check valves, boiler blowdown valves, control valves, and boiler control electronics for level, conductivity and temperature |
| Applications | Steam boilers, steam distribution and condensate return in process plants, power stations, hospitals, food and textile plants |
Milestones
- 1902: Gustav Friedrich Gerdts founds the company in Bremen on 29 October.
- 1907: The company is renamed Gustav F. Gerdts KG.
- 1987: It becomes a stock corporation, GESTRA AG.
- 2002: Flowserve takes over GESTRA.
- 2017: GESTRA becomes part of the Spirax Sarco group.
GESTRA products we list
| Series | Type | What it does |
|---|---|---|
| UNA 45, UNA 16, UNA 38 | Ball float steam traps | Continuous condensate discharge from heat exchangers and process equipment; the UNA 38 is the high-pressure version (PN 100) |
| BK 45 | Bimetallic steam trap | Robust trap for steam main drainage and tracing, resistant to water hammer |
| MK 45, TK 23, SMK 22-81 | Thermostatic steam traps | Air venting and condensate discharge; the SMK 22-81 is the sanitary version for clean steam |
| MPA 46 | Rapid-action blowdown valve | Short, intermittent bottom blowdown that removes sludge from the boiler |
| NRS 1-54, NRR 2-50, NRR 2-60, NRGT 26-2 | Boiler level controls | Water level limiting, feedwater control and continuous level measurement |
| LRGT 16-1, LRR 1-50 | Conductivity measurement and control | Keeps boiler water conductivity in range through continuous blowdown |
| TRS 5-50 | Safety temperature limiter | SIL 3 temperature limiting for boilers and hot water systems |
The type of steam trap follows the duty. Ball float traps discharge condensate as soon as it forms, which suits heat exchangers with changing loads. Thermostatic and bimetallic traps hold condensate back slightly and suit steam mains, tracing and air venting. On the boiler itself, GESTRA level and conductivity electronics work as a system: electrodes or transmitters in the boiler, controllers in the panel, and the feedwater and blowdown valves they drive.
Where GESTRA products are used
In Oman and the GCC, GESTRA equipment is used in boiler houses of refineries, petrochemical and fertiliser plants, power and desalination stations, food and beverage plants, laundries, hotels and hospitals.
Ordering GESTRA parts: what we need
Send the type designation, pressure rating (PN) and connection size (DN), the end connection (flanged, screwed or socket weld), the operating pressure and condensate load for steam traps, and the supply voltage and bus type (CAN bus, 4-20 mA) for control equipment. For electrodes, add the insertion length.
Facts checked against GESTRA company history and Bremen city records, October 2026.
Browse GESTRA products by category: Liquid Analysis Sensors.
FAQ
Questions about the GESTRA NRS 1-50 Water Level Limiter Level Switch
Answers from our engineering team on installation, compatibility and integration.
01What does the NRS 1-50 do?
It evaluates one or two level electrodes and opens the safety circuit of the heating when the water level falls below the set minimum.
02Which SIL level is stated?
The combination of NRG 1...-50 electrodes and the NRS 1-50 corresponds to a type B subsystem with SIL 3 under IEC 61508, with a 1oo2 architecture.
03What supply voltages are possible?
24 VDC plus or minus 20 percent as standard, and 100 to 240 VAC as an option.
04Which sensitivity ranges are available?
Above 0.5 and below 1000 microsiemens per cm, or above 10 and below 10000 microsiemens per cm.
05Can it be used in hazardous areas?
No. The datasheet says it must not be used in potentially explosive atmospheres.