Schneider Electric ATS01N109FT Altistart 01 Soft Starter 9 A

Description

ATS01N109FT: Altistart 01 soft starter, 9 A starter rating, 110–480 V

The ATS01N109FT is a soft starter from the Schneider Electric Altistart 01 range for asynchronous motors on simple machines. It limits the stress of direct-on-line starting by raising the motor voltage along a ramp, and it carries an integrated bypass that takes over at the end of the start. The datasheet gives a starter rating (IcL) of 9 A and a rated supply voltage of 110–480 V −10/+10 %. This is the larger 45 mm wide member of the pair, sized for motors up to 4 kW at 400 V. Seven Star LLC supplies the ATS01N109FT in Oman and the GCC as an independent supplier based in Muscat.

In the reference, ATS01 is the range and device short name, N1 appears in the compatibility code ATS01N1, and the number 103 or 109 follows the starter rating of 3 A or 9 A in our reading; FT is part of the manufacturer’s code. The datasheet remains the authority for ordering.

How the ATS01N109FT starts a motor

The type of start is a voltage ramp. Two rotary adjusters on the front set the start time and the initial voltage, and the datasheet states that the start time is adjustable from 1 to 5 s and that starting torque lies between 30 and 80 % of the torque the motor would develop connected directly to the line. Raising the initial voltage gives more torque on a stiff load; lowering it gives a softer pull-away for belts, fans and small pumps. Two LEDs indicate the status: green for power on and yellow for full voltage.

The power dissipation is quoted as 1 W at full load and at end of starting and 46 W in transient state, a reminder that the heat is produced mainly during the ramp and is small once the bypass is closed. ATS01N109FT also lists a discrete output rated 2 A DC-13 and 3 A AC-15, and a control circuit voltage that depends on the version of the control supply: 110 V AC ± 10 % at 35 mA; 24 V AC/DC ± 10 % at 30 mA; 240 V AC ± 10 % at 80 mA.

Selection checklist for the ATS01N109FT

  • Confirm the motor power and voltage against the table: 4 kW, 3 phases at 400 V; 1.5 kW, 3 phases at 230 V; 1.1 kW, 1 phase at 230 V.
  • Check the control supply: 24 V AC/DC, 110 V AC or 240 V AC versions are listed in the control circuit data.
  • Plan the surrounding devices: motor circuit-breaker, line contactor and control fuses as in the datasheet example.
  • Check the ambient temperature and altitude against the derating rules.
  • Confirm the duty is a simple machine start, not a frequent or heavy-duty application.

ATS01N109FT technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / ATS01N109FT
Range / short name Altistart 01 / ATS01
Product destination Asynchronous motors
Application Simple machine
Starter rating IcL 9 A
Utilisation category AC-53B to EN/IEC 60947-4-2
Motor power 4 kW, 3 phases at 400 V; 1.5 kW, 3 phases at 230 V; 1.1 kW, 1 phase at 230 V
Motor power (hp) 1 hp, 3 phases at 210 V; 2 hp, 3 phases at 230 V; 5 hp, 3 phases at 460 V
Rated supply voltage 110–480 V – 10–10 %
Supply voltage limits 99–528 V
Supply frequency 50–60 Hz – 5–5 %
Control circuit voltage 110 V AC ± 10 % at 35 mA; 24 V AC/DC ± 10 % at 30 mA; 240 V AC ± 10 % at 80 mA
Type of start Voltage ramp
Starting time 1 s / 100 / 5 s / 20 / Adjustable from 1 to 5 s
Starting torque 30–80 % of starting torque of motor connected directly on the line supply
Relay output rating 2 A DC-13 / 3 A AC-15
Bypass Integrated
Assembly With heat sink
Dimensions (W × H × D) 45 × 124 × 131 mm
Net weight 0.28 kg
Protection degree IP20
Operating temperature −10–40 °C (without derating) ; 40–50 °C (with current derating of 2 % per °C)

Typical uses of the ATS01N109FT in Oman and the GCC

This unit suits pumps, fans, compressors and conveyors up to the 4 kW class where a gentle start reduces mechanical shock and inrush on a weak feeder. In Oman and the GCC that includes building services, small water-treatment skids, irrigation pumps and workshop machines. The ambient limit of 40 °C without derating is the key figure for the region: a starter in a closed cabinet in the sun will need the 2 % per °C derating above 40 °C, so size accordingly or ventilate. Frequent start-stop cycles generate heat in the ramp phase, which the simple machine category does not cover.

Motors the ATS01N109FT is rated for

The datasheet lists these motor powers: 4 kW, 3 phases at 400 V; 1.5 kW, 3 phases at 230 V; 1.1 kW, 1 phase at 230 V. In horsepower terms they are 1 hp, 3 phases at 210 V; 2 hp, 3 phases at 230 V; 5 hp, 3 phases at 460 V. The corresponding power ranges are 1.1–2 kW at 200–240 V 1 phase; 2.2–3 kW at 200–240 V 3 phases; 4–6 kW at 380–440 V 3 phases. The line current figure given is 45 A at nominal load, the supply frequency 50–60 Hz – 5–5 % (network range 47.5–63 Hz) and the output voltage is at most the supply voltage. For a lighter duty the smaller sibling ATS01N103FT (3 A) is available; for loads above 4 kW a different soft starter or a drive is required.

Altistart 01 ATS01N1 pair: ATS01N109FT and ATS01N103FT

Reference Starter rating Motor power (3 phase, 400 V) W × H × D Weight
ATS01N103FT 3 A 1.1 kW 23 × 100 × 100 mm 0.16 kg
ATS01N109FT 9 A 4 kW 45 × 124 × 131 mm 0.28 kg

Both references share the 110–480 V supply range, the voltage-ramp start and the integrated bypass. They differ in current rating, motor size, housing and terminal type.

Installation and environment of the ATS01N109FT

The housing measures 45 × 124 × 131 mm and weighs 0.28 kg. It is mounted on a symmetrical 35 mm rail or fixed by screws using the retractable fixings, in a vertical position within ±10 degrees. The datasheet’s example for a three-phase supply shows a motor circuit-breaker (Q1), a line contactor in the sequence (KM1), control protection fuses (F1, F2) and start and stop pushbuttons (S1, S2) around the starter. Tightening torque is listed as 0.5 N.m / 1.9–2.5 N.m.

The ambient temperature is −10–40 °C (without derating) without derating and 40–50 °C (with current derating of 2 % per °C); storage is −25–70 °C conforming to EN/IEC 60947-4-2. Altitude up to 1000 m needs no derating, and above it the current is derated by 2.2 % per additional 100 m. Relative humidity is 5–95 % without condensation, protection is IP20, pollution degree 2, and vibration and shock are 1 gn (13–150 Hz) and 15 gn for 11 ms. Certifications listed are CSA, GOST, C-Tick, UL and CCC with the CE marking, and the product standard is EN/IEC 60947-4-2.

Information to send with an RFQ for the ATS01N109FT

  • Reference ATS01N109FT and quantity.
  • Motor power, voltage and frequency.
  • Control supply voltage available (24 V, 110 V or 240 V).
  • Ambient temperature and altitude of the installation.
  • Delivery location and required date.

Documents and quotation

The manufacturer datasheet for the ATS01N109FT is attached on this page and carries the complete specification set, including the dimension drawings and the derating information. Compare the datasheet revision with your project documents before you freeze a bill of materials.

Send us the reference ATS01N109FT, the quantity and the delivery location, and Seven Star LLC will reply to your request for quotation. We work as an independent supplier based in Muscat and serve customers across Oman and the GCC.

Other Models in the Se Ats01 Range

Seven Star LLC supplies models from the Se Ats01 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric ATS01N103FT Altistart 01 Soft Starter 3 AMotor Soft StartersView details
Schneider Electric ATS01N109FT Altistart 01 Soft Starter 9 AMotor Soft StartersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric ATS01N109FT Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric ATS01N109FT Altistart 01 Soft

Answers from our engineering team on installation, compatibility and integration.

01What motors is the ATS01N109FT rated for?
The datasheet lists 4 kW, 3 phases at 400 V; 1.5 kW, 3 phases at 230 V; 1.1 kW, 1 phase at 230 V. The starter rating (IcL) is 9 A.
02How is the start adjusted on the ATS01N109FT?
The start time is adjustable from 1 to 5 s and the starting torque is 30–80 % of the direct-on-line value, set with the front adjusters.
03What control voltage does the ATS01N109FT use?
The datasheet lists 110 V AC ± 10 % at 35 mA; 24 V AC/DC ± 10 % at 30 mA; 240 V AC ± 10 % at 80 mA, depending on the control supply.
04Does the ATS01N109FT have a bypass?
Yes, an integrated bypass is listed. A yellow LED shows full voltage and a green LED shows power on.
05What temperature range does the ATS01N109FT accept?
Operation is −10–40 °C (without derating) without derating and 40–50 °C (with current derating of 2 % per °C); storage is −25–70 °C conforming to EN/IEC 60947-4-2.