Brand:

Danfoss 032L1045 EVR 40 Solenoid Valve 2 1/8 in Solder NO

Description

EVR 40 NO: a normally open 2 1/8 in refrigeration valve for large lines

The 032L1045 is an EVR 40 in the less common normally open version. When the coil has no power, the piston stays open and refrigerant flows; applying current closes the valve. That is the inverse of the NC types, and it is used where a failure of supply should keep the line open, for instance on hot-gas bypass and pump-down logic designed that way.

The solder connections are 2 1/8 in with extended ends, the body is cast iron, the orifice 25.4 mm and the Kv 24.2 m3/h. The data sheet lists NC and NO versions with de-energised coil and a media temperature of up to 105 C, with a defrost peak of 130 C per the store entry.

Technical specifications

Parameter Specification
Danfoss code number 032L1045
Type EVR 40
Function Normally open (NO)
Operation Servo-operated (piston)
Connection 2 1/8 in solder (ODF), cast iron body
Orifice 25.4 mm
Kv / Cv 24.2 m3/h / 28 gal/min
Max. working pressure 45.2 bar
Medium temperature -40 C to 105 C
Min. opening differential pressure 0.2 bar
Max. opening pressure differential (MOPD) 21 bar for 10 W AC, 14 W AC, 20 W DC and BJ/BX coils
Manual operation No
Defrost temperature (max.) 130 C
Coil Not included (ordered separately)
Lubricants compatibility AB; MO; PAG; PAO; POE; PVE
Approvals as listed EAC; UL
Net weight 4.42 kg
EAN 5702428950602

NO function and pressure limits

The store gives the same MOPD figure of 21 bar for all coils, 10 W AC, 14 W AC, 20 W DC and BJ/BX, and the minimum opening differential is 0.2 bar for this piston servo design. Design the system so that the closing function, which needs voltage, works at the highest differential pressure that can occur.

No manual operation is provided on this code. Working pressure is 45.2 bar, and the compatible refrigerants include R22, R134a, R404A, R407A, R407C and R1234ze(E), with lubricant compatibility for mineral, AB, PAG, PAO, POE and PVE oils.

Weight, brazing and ordering

At 4.42 kg this is a heavy valve for a refrigerant line, so support the pipe and do not hang the weight on the solder joints. Remove or protect the piston parts if the data sheet requires it before brazing, and keep the body from overheating.

Confirm the function (NO), coil, voltage, refrigerant and line size before ordering. Seven Star LLC is an independent supplier in Muscat; send 032L1045 and the quantity for a quotation.

The NO function is chosen deliberately, so verify the control logic with the plant designer before ordering. A valve ordered by mistake as NO instead of NC can leave a circuit open after a power failure. Compare the function letter in the type description with the existing valve and keep the nameplate code in the maintenance record.

Large piston valves close with force, so check for noise and hammer when the first cycle is run.

Projects that use 032L1045 often need related parts from the same manufacturer, such as connectors, mounting parts or spare kits. Mention them in the same enquiry so that compatibility can be checked together rather than discovered on site, when a missing part stops the work.

Documents and quotation

The attached Danfoss EVR 2 to EVR 40 data sheet AI249086497583 gives dimensions and coil tables. See also solenoid valves.

Datasheets & Documents
  • PDF Datasheet Danfoss EVR 2 - EVR 40 solenoid valve data sheet AI249086497583 (manufacturer, unaltered) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Danfoss is the Danish engineering group that makes refrigeration and air-conditioning controls, heating components, variable speed drives and mobile hydraulics. Mads Clausen founded it on 1 September 1933 at his parents' farm in Nordborg on the island of Als, after making his first refrigeration expansion valve in 1932. Nordborg is still the group's headquarters, and Danfoss remains controlled by the Clausen family through the Bitten & Mads Clausen Foundation.

Danfoss company profile

Founded 1 September 1933, Nordborg, Denmark, by Mads Clausen (1905–1966)
First product Thermostatic expansion valve for refrigeration
Headquarters Nordborg, Denmark
Ownership Private; majority controlled by the Bitten & Mads Clausen Foundation and the Clausen family
Size About 42,000 employees (2023)
Business segments Danfoss Climate Solutions (refrigeration, air conditioning and heating), Danfoss Drives (VLT and VACON frequency converters, soft starters), Danfoss Power Solutions (mobile and industrial hydraulics)
Brands in the group VLT, VACON, Eaton Hydraulics (bought 2021), Ikusi radio remote controls

Milestones

  • 1932–1933: First expansion valve; the company is founded in Nordborg.
  • 1939: 26 employees. By the 10th anniversary in 1943 the company has 179.
  • 1950s: Rapid growth turns Nordborg into a Danfoss town with housing and schools for its workforce.
  • 1968: Danfoss launches its VLT frequency converter, one of the first mass-produced AC drives.
  • 2014: Acquisition of the Finnish drives maker Vacon, now the VACON brand.
  • 2021: Acquisition of Eaton's hydraulics business.

Choosing Danfoss products

For solenoid valves, check the operating principle. A direct-operated valve such as EV210B opens even at 0 bar differential pressure. A servo-operated valve such as EV220B needs a minimum differential (typically about 0.3 bar) to open, while an assisted-lift valve such as EV250B works from 0 bar. Coils are ordered separately, so the voltage on the coil (for example 230 V AC or 24 V DC) must match the control circuit. For drives, the VLT family is split by application: FC 51 Micro Drive for small machines, FC 102 HVAC Drive for fans and pumps in buildings, FC 202 AQUA Drive for water, and FC 302 AutomationDrive for demanding industrial duty.

Where Danfoss products are used

In Oman and the GCC, Danfoss drives run pumps, fans and compressors in district cooling plants, water and wastewater stations, desalination and building HVAC. Danfoss pressure switches, transmitters and solenoid valves are built into chillers, refrigeration plants, boilers and hydraulic systems, and AB-QM valves balance chilled-water circuits in large buildings.

Danfoss products we list

Family Examples
Variable speed drives and soft starters VLT Micro Drive FC 51, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, FC 280, iC2-Micro, VACON NXP, MCD 600 soft starter
Solenoid valves and coils EV220B, EV210B, EV250B, EV225B steam, EVR 25, AM230C coil
Pressure switches and thermostats KP 37, KP 44, RT 200, CS, MBC 5000, KPS 77, RT 101
Pressure transmitters MBS 3000, MBS 5100, MBS 3250, MBS 4251 Ex, AKS 33, DST P92S SIL 2
HVAC and refrigeration valves AB-QM PICV, NovoCon S, AB-PM, AVTA, ICV, TE 5 element

Ordering Danfoss products: what we need

Send the Danfoss code number from the label (for example 032U7115 or 131B0149) or the full drive type code (FC-302P3K0T5...). For drives, add the motor power, supply voltage and any fieldbus option. For valves, add the size, connection, medium and coil voltage. For pressure switches and transmitters, add the range, output and pressure connection.

Facts checked against Danfoss's company history pages and published company data, October 2026.

Frequently Asked Questions

What is Danfoss 032L1045?
An EVR 40 solenoid valve: normally open, 2 1/8 in solder ODF, cast iron, Kv 24.2 m3/h, servo-piston.
What does normally open mean here?
The valve is open with no coil voltage and closes when the coil is energised.
Is manual operation available?
No, the store lists no manual operation for this code.
Is a coil included?
No. The valve and coil are ordered separately.
Which document is attached?
The Danfoss EVR 2 - EVR 40 data sheet AI249086497583.