Brand:

Danfoss 032U5254 EV250B 18 Solenoid Valve G 3/4 NC 0 bar

Description

EV250B 18: a 2/2-way valve that opens from zero pressure difference

Servo-operated valves such as the EV220B need a minimum differential pressure, but the Danfoss 032U5254 does not: it is an EV250B 18 with assisted-lift operation, which means the armature helps lift the diaphragm so that the valve opens even at 0 bar. That is the central reason to select it, for example in gravity-fed tanks, low-head circulation loops or applications where the pressure cannot be guaranteed.

The body is DZR brass with a G 3/4 connection, an 18 mm orifice and a Kv of 6 m3/h. The EPDM seals suit technical and soft water, with a medium range of -30 to 120 C and a maximum pressure of 10 bar. SINTEF and UA approvals are listed in the store entry.

Technical specifications

Parameter Specification
Danfoss code number 032U5254
Type EV250B 18
Function Normally closed (NC), 2/2-way
Operation Assisted lift operated
Connection G 3/4 internal (ISO 228-1), DZR brass body
Orifice 18 mm
Kv / Cv 6 m3/h / 6.95 gal/min
Differential pressure range 0 to 10 bar (works from zero)
Max. working / test pressure 10 bar / 15 bar
Medium temperature -30 to 120 C
Ambient temperature (max.) 80 C
Seal material EPDM
Media recommendation Technical and soft water
Opening / closing time, water (est.) 150 ms / 100 ms
Approvals as listed SINTEF; UA
Net weight 0.81 kg
EAN 5702423179176

Where zero-differential operation helps

Typical uses include water treatment dosing lines, tank drains, boiler make-up from a header tank and rinse circuits in washing equipment. The application field on the store page is “closed and drain”, so the unit is chosen to close and drain off water as needed, with the coil sold separately.

The listed opening time of 150 ms and closing time of 100 ms are estimates on water. The valve is faster than the EV220B 32 or 50 sizes, which makes water hammer more likely on long pipes, so install a short run and fix the pipe near the valve.

Installation and ordering

Use a strainer and keep to the maximum medium temperature of 120 C. The installation guide for the EV250B gives maximum working pressure of 10 bar and a 15 bar test pressure for DN 10 to 22 sizes, which agrees with the store values. The coil must be ordered separately, with plug and connector.

Seven Star LLC is an independent supplier in Muscat and can quote 032U5254 if you send voltage and quantity. Check the thread, the medium and the minimum pressure of your application against the page.

For maintenance planning, treat the valve like any wetted component: flush the line before commissioning to remove weld slag and sand, avoid running it dry for long periods and replace the coil if the housing shows discolouration. A spare valve and a spare coil of the same voltage cost little compared with a stopped treatment plant.

Because the opening time is short, a quarter-turn isolation valve upstream helps with maintenance.

Before you order 032U5254, compare it with the nameplate of the unit you intend to replace. Photographs of the nameplate help us to confirm the exact code quickly, and we will tell you plainly if a different version of the same family looks like a better fit for your duty.

Documents and quotation

The attached file is the Danfoss EV250B installation guide AN22648643469500. See similar items under solenoid valves.

Datasheets & Documents
  • PDF Installation Guide Danfoss EV250B installation guide AN22648643469500 (manufacturer, unaltered) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Danfoss is the Danish engineering group that makes refrigeration and air-conditioning controls, heating components, variable speed drives and mobile hydraulics. Mads Clausen founded it on 1 September 1933 at his parents' farm in Nordborg on the island of Als, after making his first refrigeration expansion valve in 1932. Nordborg is still the group's headquarters, and Danfoss remains controlled by the Clausen family through the Bitten & Mads Clausen Foundation.

Danfoss company profile

Founded 1 September 1933, Nordborg, Denmark, by Mads Clausen (1905–1966)
First product Thermostatic expansion valve for refrigeration
Headquarters Nordborg, Denmark
Ownership Private; majority controlled by the Bitten & Mads Clausen Foundation and the Clausen family
Size About 42,000 employees (2023)
Business segments Danfoss Climate Solutions (refrigeration, air conditioning and heating), Danfoss Drives (VLT and VACON frequency converters, soft starters), Danfoss Power Solutions (mobile and industrial hydraulics)
Brands in the group VLT, VACON, Eaton Hydraulics (bought 2021), Ikusi radio remote controls

Milestones

  • 1932–1933: First expansion valve; the company is founded in Nordborg.
  • 1939: 26 employees. By the 10th anniversary in 1943 the company has 179.
  • 1950s: Rapid growth turns Nordborg into a Danfoss town with housing and schools for its workforce.
  • 1968: Danfoss launches its VLT frequency converter, one of the first mass-produced AC drives.
  • 2014: Acquisition of the Finnish drives maker Vacon, now the VACON brand.
  • 2021: Acquisition of Eaton's hydraulics business.

Choosing Danfoss products

For solenoid valves, check the operating principle. A direct-operated valve such as EV210B opens even at 0 bar differential pressure. A servo-operated valve such as EV220B needs a minimum differential (typically about 0.3 bar) to open, while an assisted-lift valve such as EV250B works from 0 bar. Coils are ordered separately, so the voltage on the coil (for example 230 V AC or 24 V DC) must match the control circuit. For drives, the VLT family is split by application: FC 51 Micro Drive for small machines, FC 102 HVAC Drive for fans and pumps in buildings, FC 202 AQUA Drive for water, and FC 302 AutomationDrive for demanding industrial duty.

Where Danfoss products are used

In Oman and the GCC, Danfoss drives run pumps, fans and compressors in district cooling plants, water and wastewater stations, desalination and building HVAC. Danfoss pressure switches, transmitters and solenoid valves are built into chillers, refrigeration plants, boilers and hydraulic systems, and AB-QM valves balance chilled-water circuits in large buildings.

Danfoss products we list

Family Examples
Variable speed drives and soft starters VLT Micro Drive FC 51, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, FC 280, iC2-Micro, VACON NXP, MCD 600 soft starter
Solenoid valves and coils EV220B, EV210B, EV250B, EV225B steam, EVR 25, AM230C coil
Pressure switches and thermostats KP 37, KP 44, RT 200, CS, MBC 5000, KPS 77, RT 101
Pressure transmitters MBS 3000, MBS 5100, MBS 3250, MBS 4251 Ex, AKS 33, DST P92S SIL 2
HVAC and refrigeration valves AB-QM PICV, NovoCon S, AB-PM, AVTA, ICV, TE 5 element

Ordering Danfoss products: what we need

Send the Danfoss code number from the label (for example 032U7115 or 131B0149) or the full drive type code (FC-302P3K0T5...). For drives, add the motor power, supply voltage and any fieldbus option. For valves, add the size, connection, medium and coil voltage. For pressure switches and transmitters, add the range, output and pressure connection.

Facts checked against Danfoss's company history pages and published company data, October 2026.

Frequently Asked Questions

What is Danfoss 032U5254?
An EV250B 18 solenoid valve: NC, G 3/4 DZR brass, 18 mm orifice, Kv 6 m3/h, EPDM, assisted-lift operation.
Does it need a minimum pressure difference?
No. The store lists a minimum differential of 0 bar.
What media are recommended?
Technical and soft water.
Is a coil included?
No, the coil is a separate order.
Which document is included?
The Danfoss EV250B installation guide AN22648643469500.