Brand:

Danfoss NovoCon S Digital Actuator for AB-QM DN 10-32

Description

Overview

The Danfoss NovoCon S is a high-accuracy, multi-functional field bus actuator designed specifically for the Danfoss AB-QM pressure independent control valve in sizes DN 10 to 32. Combined with the valve, it controls water flow to fan coil units, chilled beams, induction units, small re-heaters and re-coolers, air handling units and other terminal units. Unlike a conventional 0-10 V actuator, it communicates directly with the building management system over BACnet MS/TP or Modbus RTU, which allows remote commissioning, flow indication, alarm reporting and, with optional sensors, energy measurement at every terminal unit.

Seven Star LLC supplies the Danfoss NovoCon S with its cables and accessories to MEP contractors, system integrators and facility managers across Oman and the GCC, with engineering support in Muscat. For buildings that run hundreds of chilled water fan coils, the actuator turns each valve into a data point, so operators can see which zones are drawing too much flow, which valves are blocked and where delta-T is falling.

Operating Principle

The Danfoss NovoCon S drives the AB-QM stem through a 7 mm stroke with a force of 90 N and a position accuracy of ±0.05 mm. Because the AB-QM holds a constant differential pressure across its control part and has a linear characteristic, the stem position corresponds directly to a flow value. That relationship lets the Danfoss NovoCon S act as a flow indicator without a separate flow meter, and lets the BMS set a design flow per unit through the bus instead of a technician adjusting each valve by hand.

Control can come from the field bus or from analog signals of 0-10 V, 0-5 V, 2-10 V, 5-10 V, 2-6 V, 6-10 V, 0-20 mA or 4-20 mA. Speed is selectable at 3, 6, 12 or 24 s/mm, or as constant time. With the Energy cable and two PT1000 sensors on the supply and return pipes, the actuator calculates power emission, logs heating and cooling energy separately, and can apply energy management functions such as minimum delta-T control.

Engineering Design of the Danfoss NovoCon S

The Danfoss NovoCon S is supplied at 24 V AC/DC and consumes 2.7 VA at 24 VAC or 1.2 W at 24 VDC when operating, falling to 1.8 VA or 0.7 W in standby. It operates with supply deviations of up to ±25 %, has mis-wiring protection on any wire up to 30 V and is rated IP 54 (IP 40 when mounted upside down). It mounts on the valve without tools, runs a self-positioning process, and an LED bar shows status and alarms. Ambient temperature range is -10 to 50 °C and the maximum medium temperature is 120 °C, with a weight of 0.4 kg.

All connections use plug-in, halogen-free cables, ordered separately: digital bus and power cables, daisy chain cables between actuators, analog cables, Energy cables with PT1000 sensors, and an I/O cable. The I/O option provides one analog output, one analog input and two resistance inputs, so a room thermostat, window contact, CO2 or humidity sensor can appear on the field bus through the Danfoss NovoCon S. The BACnet device profile is B-ASC, and both protocols support baud rates from 9600 to 115200 bps with automatic detection.

Key Features

The Danfoss NovoCon S adds diagnostics and data to every AB-QM valve it drives:

  • BACnet MS/TP and Modbus RTU in one product, with auto MAC addressing for BACnet and auto baud rate detection.
  • Position accuracy of ±0.05 mm and flow indication based on the linear AB-QM characteristic.
  • Remote commissioning, flow presetting and flushing functions over the field bus.
  • Valve blockage alarm and broken wire detection on analog control and ground signals.
  • Power emission indication and separate heating and cooling energy logging with PT1000 sensors.
  • I/O connections for room devices such as thermostats, window contacts, CO2 and humidity sensors.
  • ChangeOver6 support for four-pipe single-coil systems, with separate design flows for heating and cooling.
  • Low-noise, maintenance-free operation and tool-free mounting.

Industrial Applications

The Danfoss NovoCon S is used in commercial offices, hotels, hospitals, airports, universities and high-rise residential buildings where chilled water fan coils or chilled beams are controlled by a BMS. In Oman and the wider GCC, where cooling runs most of the year, the ability to check each unit’s flow and delta-T remotely helps facility teams catch problems that would otherwise show up only as complaints or as a low delta-T penalty from a district cooling provider. Remote presetting also shortens commissioning on large projects, because design flows can be written to every valve from the BMS workstation.

Facility managers also use the energy logging feature for fair allocation of cooling cost between tenants or departments, and integrators use the I/O inputs to reduce field wiring in each room. Seven Star LLC supplies the Danfoss NovoCon S, the matching AB-QM valves, cables and PT1000 sensors for projects in Muscat, Sohar, Duqm and Salalah, along with the Danfoss data sheet for approval.

The matching valve is the Danfoss AB-QM pressure independent control valve.

Technical Specifications

The data for the Danfoss NovoCon S below is taken from the Danfoss data sheet AI262437193437en-010801:

Parameter Specification
Model Danfoss NovoCon S, code 003Z8504
Compatible valves Danfoss AB-QM DN 10 to 32
Power supply 24 V AC/DC, 50/60 Hz; 2.7 VA / 1.2 W operating, 1.8 VA / 0.7 W standby
Field bus BACnet MS/TP (B-ASC) and Modbus RTU, 9600 to 115200 bps, auto baud
Analog control 0-10, 0-5, 2-10, 5-10, 2-6, 6-10 VDC; 0-20, 4-20 mA
Speed 3, 6, 12 or 24 s/mm, or constant time
Stroke and force 7 mm; 90 N
Position accuracy ±0.05 mm
Ambient temperature -10 to 50 °C, 98 % r.h. non-condensing
Max. medium temperature 120 °C
Enclosure IP 54 (IP 40 upside down); protection class III
Weight 0.4 kg
Approvals EMC Directive 2014/30/EU, EN 60730-2-14, RoHS 2011/65/EU

How to Order

To request a quotation for the Danfoss NovoCon S, send Seven Star LLC the number of terminal units, AB-QM sizes, BMS protocol, cable lengths and whether energy or I/O functions are required. Our Muscat team will confirm the actuator and cable list, advise on stock and lead time for Oman and the GCC, and provide the official data sheet. Other actuators and instruments on our site include the ABB Contrac LME620 linear actuator, the ABB Contrac RSD10 linear actuator and the Danfoss MBS 3000 pressure transmitter.

Datasheets & Documents
  • PDF Datasheet Danfoss NovoCon S High Accuracy Actuator Data Sheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

From its headquarters in Nordborg, Denmark, where it was founded in 1933, Danfoss makes the drives, valves and sensors found in pump rooms, chiller plants and cold stores. Its blue VLT frequency converters are probably the most familiar of them.

Seven Star LLC lists Danfoss VLT drives, pressure transmitters, refrigeration valves and HVAC control valves, and supplies them to contractors and plant owners in Oman against the exact code number on the label.

Danfoss product families on this page

Among the VLT drives listed, three are each aimed at a different duty: the VLT HVAC Drive FC 102 for fans and building services, the VLT AQUA Drive FC 202 for water and wastewater pumping, and the VLT AutomationDrive FC 302 for general industrial machinery. The LCP 12 control panel with potentiometer (code number 132B0101) is also listed; Danfoss specifies it for the VLT Micro Drive FC 51. In pressure measurement there are the MBS 3000 general purpose transmitter and the MBS 5100. Valves include the AB-QM pressure independent control valve in DN 15 to DN 250, the EVR 25 servo-operated solenoid valve and the ICV pilot-operated valve for industrial refrigeration.

Where Danfoss equipment is used

District cooling and chilled water plants, air handling units, booster and irrigation pump stations, desalination and wastewater works, ammonia and CO2 refrigeration plants, food storage and marine engine rooms are the usual places. Demand in the GCC is driven largely by cooling and water.

Ordering Danfoss parts: what we need

Every Danfoss product has a code number, and drives also carry a long type code string on the label. Send both. For a drive we need the motor power and current, the mains voltage, enclosure rating, any fieldbus or option card and the filter class. For an MBS transmitter give the pressure span, output signal, pressure connection and electrical connection. For valves give the size, connection type, coil voltage where relevant and the refrigerant or medium.

Frequently Asked Questions

How does the Danfoss NovoCon S show flow without a flow meter?
The actuator positions the AB-QM stem with an accuracy of plus or minus 0.05 mm. Because the AB-QM is pressure independent and has a linear characteristic, the stem position corresponds to a known flow, so the actuator can report flow over the field bus. Adding PT1000 supply and return sensors through the Energy cable lets it also indicate power and log heating and cooling energy.
Which building management protocols does the Danfoss NovoCon S support?
BACnet MS/TP and Modbus RTU are both built into the same product, with automatic baud rate detection and automatic MAC addressing for BACnet. The actuator can also be controlled through analog signals such as 0-10 V or 4-20 mA while its data is still read over the bus.
Can the Danfoss NovoCon S be fitted to existing AB-QM valves?
NovoCon S is designed for AB-QM valves in sizes DN 10 to 32 and mounts without tools. For older AB-QM valves, Danfoss offers a NovoCon adapter kit for DN 10 to 32 (code 003Z0239), which allows the actuator to be added during a retrofit.
What is the NovoCon ChangeOver6 option used for?
In four-pipe systems with a single coil, such as radiant ceilings or some fan coils, NovoCon S can control both the AB-QM and a ChangeOver6 six-port ball valve that switches the unit between heating and cooling water. Only one bus connection is needed, the pair never drives at the same time, and separate design flows can be set for heating and cooling.
Does Seven Star LLC supply the Danfoss NovoCon S and its cables in Oman?
Seven Star LLC supplies the Danfoss NovoCon S actuator together with the required bus, daisy chain, analog, energy and I/O cables for projects in Oman and the GCC. Cables are ordered separately, and our Muscat team can help define the cable list and BMS integration requirements.