Brand: Schneider Electric
Schneider Electric ZA2EE101 XA2 Contact Block, 1 NO
Description
ZA2EE101: single 1 NO contact block for XA2 heads
The ZA2EE101 is a Schneider Electric Harmony XA2 contact block with one NO (1 NO) contact. It is the electrical half of a modular control station: the operator head sits in the panel door, and the block behind it carries the contact that the control circuit actually uses. Seven Star LLC supplies the ZA2EE101 in Oman and the GCC as an independent supplier in Muscat, mostly to panel builders and maintenance stores that rebuild or extend existing XA2 stations.
The datasheet lists the item as a single block with standard contacts, and the nameplate on the product photo repeats the reference together with the ratings AC15 240 V/3 A, Ith 10 A, Ui 600 V and Uimp 6 kV, plus the terminal numbers 3-4. On ZA2EE101, the ZA2E component name and the 1 NO composition are what separate this block from its opposite-action sibling ZA2EE102.
Wiring and mounting of the ZA2EE101
The block offers two connection styles on the same terminal: screw clamp or 6.3 mm Faston. In the screw version the datasheet allows up to two conductors of 1.5 mm², or up to one conductor of 2.5 mm² and down to 0.5 mm², tightened to 0.8 N.m. Fastons help on factory lines where harnesses are pre-crimped, and screws help on site where a cable needs to be changed in a hurry.
The packaged unit is a single block in a small carton, and the product is rated IP20 on its own. That rating applies to the finger-safe block, not to the station; the sealing of the finished control station depends on the head and the panel, not on this block. Fit the block behind the head following the head instructions and confirm that the contact action matches the schematic before closing the door.
Selection checklist and RFQ information for ZA2EE101
Send these details with the enquiry so that the part number can be confirmed against the datasheet in one reply.
- Part number ZA2EE101 and the quantity required.
- The contact action you need (NO or NC) and whether you also need the sibling block.
- The control voltage and current the contact will switch, compared with 2 A at 230 V AC-15 or 0.2 A at 110 V DC-13.
- The head or station type the block will be fitted behind, with a photo of any block being replaced.
- Terminal style needed in the field (screw or Faston) and wire size.
- Any project approval needed, compared with the CE and CCC listing.
- Delivery location in Oman or the GCC and the lead time you need.
Ratings of the ZA2EE101 and what they allow
The block is a control-circuit device. The rated operational current is 2 A at 230 V in utilisation category AC-15, which covers contactor and relay coils, and 0.2 A at 110 V in DC-13, which covers small solenoids and DC relays. Electrical durability is stated as 500000 cycles at those loads at under 60 operations per minute with a load factor of 0.5, against a mechanical durability of 1500000 cycles. In plain terms, the more current and the higher the duty rate, the sooner the contacts wear, so size the load to stay well within these figures.
The datasheet requires short-circuit protection with a 10 A type gL fuse. The thermal current is 10 A, but that is a heating limit and not a switching rating, and it should not be read as permission to switch a 10 A load. For heavier loads, use the ZA2EE101 to drive a contactor instead of switching the load directly.
Pairing the ZA2EE101 with ZA2EE102 and the XA2 range
A single block gives one contact. When a station needs both a make and a break, designers stack one ZA2EE101 with one ZA2EE102, giving a 1 NO plus NC pair on the same head. The order matters for wiring clarity: keep the NO and NC blocks in a consistent position from station to station so that maintenance staff can read the stack without opening the drawing.
The datasheet places the product in the Harmony XA2 range and does not list compatible heads on the page, so the choice of head should be confirmed from the head datasheet and the XA2 catalogue, not assumed from the name. If you are matching an existing station, a photo of the old block and its nameplate is the most reliable way to confirm the replacement.
Technical specifications of the ZA2EE101
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / ZA2EE101 |
| Range | Harmony XA2 |
| Product type | Contact block, single |
| Component name | ZA2E |
| Contacts | 1 NO (1 NO) |
| Contact operation | Slow-break |
| Contacts usage | Standard contacts |
| Positive opening | Without |
| Contact material | Silver alloy (Ag/Ni) |
| Thermal current [Ith] | 10 A, IEC 60947-5-1 |
| Rated insulation voltage [Ui] | 600 V, pollution degree 3 |
| Rated impulse withstand [Uimp] | 6 kV |
| Rated operational current [Ie] | 2 A at 230 V, AC-15 (A600); 0.2 A at 110 V, DC-13 (Q600) |
| Electrical durability | 500000 cycles at 2 A, 230 V AC-15 or 0.2 A, 110 V DC-13, below 60 cycles/min, load factor 0.5 |
| Mechanical durability | 1500000 cycles |
| Short-circuit protection | 10 A fuse, type gL (IEC 60269-1) |
| Terminals | Screw clamp: up to 2 × 1.5 mm², up to 1 × 2.5 mm², at least 1 × 0.5 mm²; Faston 6.3 mm |
| Tightening torque | 0.8 N.m |
| Degree of protection | IP20, IEC 60529 |
| Protective treatment | TC |
| Operating temperature | -25 to 55 °C |
| Storage temperature | -40 to 70 °C |
| Certifications | CE, CCC |
| Standards | IEC 60947-1, IEC 60947-5-1, IEC 60947-5-4, IEC 60529 |
| Packaged unit | 1.52 × 2.9 × 3.0 cm (H × W × L), 15 g |
| Warranty | 18 months |
Typical uses in Oman and the GCC
A block of this type, such as the ZA2EE101, serves as a start input to a relay coil or a PLC input, or the signal contact of a selector position. It appears on motor control centres, pump and fan control stations, local control boxes, packaged skids and machine panels across oil and gas, power, desalination and water treatment sites. The datasheet gives an operating range of -25 to 55 °C, which is narrower than the upper limit of many XB4 and XB5 parts, so a block fitted in a panel exposed to direct sun or to heat from nearby equipment should be checked against the real cabinet temperature, not the ambient figure.
Dust and humidity do not reach the contacts of a sealed station, but a block with open terminals inside a wet cabinet will corrode faster than one inside a dry enclosure. Keep the block clean, keep the terminals tight and keep spare blocks in the store, since the part is small, inexpensive in comparison with the equipment it controls, and a common cause of avoidable stoppages when it fails.
How the ZA2EE101 behaves in a circuit
With one normally open contact the block can only complete a circuit while the operator drives it. That fits a start command, a run request to a contactor coil or a digital input that must stay low until someone acts. The contact closes when the head is operated and opens again on release, and the datasheet describes the action as slow-break, meaning the contacts separate at the speed of the operator rather than snapping. Slow-break contacts are well suited to ordinary relay and PLC control circuits, and the contact material is silver alloy (Ag/Ni).
On the {ZA2EE101}, a broken wire or a missing block simply reads as no command, which is the safe default for a start signal but not for a stop or an interlock.
Documents and quotation
The Schneider Electric datasheet for the ZA2EE101 is attached on this page for your technical file. It holds the electrical, mechanical and environmental data summarised above, with the drawings and packaging data.
To request a quotation, send the part number and quantity through the enquiry form and we will reply with availability and delivery terms. Seven Star LLC is an independent supplier and does not act for the manufacturer, so please check the datasheet against your project requirements before ordering.
Datasheets & Documents
- Datasheet Schneider Electric ZA2EE101 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric ZA2EE101 XA2 Contact Block, 1 NO
Answers from our engineering team on installation, compatibility and integration.
01What contact does the ZA2EE101 provide?
One NO contact (1 NO) on terminals 3-4, with slow-break action and silver-alloy contact material, according to the datasheet.
02What load can the ZA2EE101 switch?
The datasheet lists 2 A at 230 V in AC-15 and 0.2 A at 110 V in DC-13. The 10 A figure is the thermal current, not a switching rating.
03How is the ZA2EE101 connected?
By screw clamp terminals (up to 2 × 1.5 mm² or 1 × 2.5 mm², torque 0.8 N.m) or by 6.3 mm Faston connectors.
04Is the ZA2EE101 a positive-opening safety contact?
No. The datasheet states positive opening as Without, so it should not be used where a positive-opening device is required.
05Does Seven Star LLC supply the ZA2EE101 in Oman?
Yes, as an independent supplier in Muscat for Oman and the GCC. Send the part number and quantity and we confirm availability and documents.