Schneider Electric RXM3AB1B7 Harmony RXM Relay 24 V AC

Description

RXM3AB1B7: RXM3 miniature relay, 24 V AC coil

The RXM3AB1B7 is an RXM-series miniature plug-in relay with 3 changeover contacts rated 10 A, a 24 V AC coil, no status LED and a lockable test button. It belongs to the Schneider Electric Harmony electromechanical relay range and is built for panel and marshalling-cabinet duty, where it plugs into a socket instead of being wired directly. Seven Star LLC supplies the RXM3AB1B7 in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference as our own pattern across the RXM3A group, and not as a published ordering table: RXM3 gives the contact count, AB the high-rating body, the digit 1 (without an LED) and the closing code B7 the coil, here 24 V AC.

RXM3AB1B7 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / RXM3AB1B7
Range / series Harmony Electromechanical Relays / RXM series
Relay type Miniature plug-in relay
Contacts 3 C/O
Control circuit voltage [Uc] 24 V AC 50/60 Hz
Operating voltage limits 19.2–26.4 V AC
Drop-out threshold ≥ 0.15 Uc
Average coil resistance 180 Ohm at 20 °C ± 15 %
Average coil consumption 1.2 VA at 60 Hz
Status LED Without
Control / test Lockable test button
Load current 10 A at 250 V AC; 10 A at 28 V DC
Maximum switching capacity 2500 VA/280 W
Contact material AgNi
Mechanical durability 10000000 cycles
Electrical durability 100000 cycles for resistive load
Operating temperature -40–55
Storage temperature -40–85
Protection class IP40 conforming to IEC 60529
Net weight 0.037 kg
Standards IEC 61810-1, UL 508, CSA C22.2 No 14
Certifications listed UL, Lloyd’s, CE, CSA, GOST, IECEE CB Scheme

All figures above come from the Schneider Electric product datasheet for the RXM3AB1B7, which carries the print date 8 Nov 2026. The sheet shows no discontinuation notice for this reference.

Typical applications in Oman and the GCC

Three changeover contacts allow one coil to switch a load, repeat its status and feed an interlock, which reduces the relay count in compact marshalling and control panels. Panels in Oman and the wider Gulf see high ambient temperatures, dust and humidity, so relays should be installed in ventilated, sealed cabinets and the temperature limits (operation -40–55 °C) kept in mind when panels sit in the sun. Seven Star LLC supplies the RXM3AB1B7 for panel builders, maintenance teams and projects in oil and gas, power, desalination and general industry.

Coil data and operating range of the RXM3AB1B7

A 24 V AC coil is fed from a small control transformer inside the panel, a practice that persists in older HVAC and machine-control cabinets and in panels built around transformer-fed pilot circuits.

The datasheet gives operating voltage limits of 19.2–26.4 V AC, with a drop-out threshold of ≥ 0.15 Uc. The average coil resistance is 180 Ohm at 20 °C ± 15 % and the average consumption is 1.2 VA at 60 Hz. Those numbers matter more than the nominal voltage: a supply that sags under load, or that sits at the top of its tolerance, should still fall inside the stated window for RXM3AB1B7 to pick up and release cleanly.

Because this is an AC coil, the contacts follow the supply frequency of 50/60 Hz; the relay is not meant for a rectified or unsmoothed DC feed, and an AC coil must not be fitted where a DC coil was specified.

Contact capability of the RXM3AB1B7 relay

The 3 changeover contacts carry a load current of 10 A at 250 V AC; 10 A at 28 V DC, with a maximum switching capacity of 2500 VA/280 W and a continuous output current of 6.7 A. The contact material is AgNi. The normally closed side is rated lower than the normally open side, at 5 A on IEC duty, so check which contact your load uses.

Rated operational currents on the datasheet include 10 A at 28 V (DC) NO conforming to IEC ; 10 A at 250 V (AC) NO conforming to IEC ; 5 A at 28 V (DC) NC conforming to IEC ; 5 A at 250 V (AC) NC conforming to IEC. Mechanical durability is 10000000 cycles cycles and electrical durability for a resistive load is 100000 cycles for resistive load. Operating rate is up to 1200 cycles per hour under load.

The dielectric strength is 1300 V AC between contacts with micro disconnection; 2000 V AC between coil and contact; 2000 V AC between poles.

Selection checklist for this relay

  • Coil voltage and type: 24 V AC. Match both the voltage and AC or DC to the supply that actually feeds the coil.
  • Contact count and load: 3 changeover contacts, 10 A at 250 V AC; 10 A at 28 V DC; confirm the NC contact rating if the load is on the NC side.
  • Indication: no LED, so status must be read from the controller or by a lamp elsewhere in the circuit.
  • Test facility: lockable test button fitted.
  • Socket: the relay has Flat (faston type) pins, so choose a matching socket from the same Harmony range and confirm its reference with your supplier.
  • Environment: operating temperature -40–55 °C and IP40 conforming to IEC 60529; as a plug-in relay it belongs inside a panel, not on an open plant floor.

Installation, commissioning and maintenance

Seat the relay squarely so that all pins engage, fit the retaining clip, and keep the three contact sets segregated in the wiring so that one failed circuit does not feed another. The permitted ambient is -40–55 °C, and the net weight is 0.037 kg.

Use the lockable test button during commissioning to prove the downstream circuit, then release it and note that in the commissioning record. A relay is a wear item: keep spare relays of the same coil voltage and replace them on a schedule defined by the duty, not only after a failure.

Comparing this relay with related references

The table below lists the RXM3AB1B7 next to the closest references from the same group, ordered by coil voltage, so that you can check that you are specifying the right coil and indicator combination.

Part number Coil voltage Indicator LED Test button Coil resistance
RXM3AB1B7 (this page) 24 V AC Without Lockable 180 Ω
RXM3AB1E7 48 V AC Without Lockable 710 Ω
RXM3AB1F7 120 V AC Without Lockable 4430 Ω
RXM3AB2F7 120 V AC With Lockable 4430 Ω
RXM3AB1P7 230 V AC Without Lockable 15000 Ω
RXM3AB2P7 230 V AC With Lockable 15000 Ω
RXM3AB1BD 24 V DC Without Lockable 650 Ω

Information to send with an RFQ

  • The exact part number RXM3AB1B7 and the quantity, remembering the pack quantity of the reference.
  • The coil voltage on site, 24 V AC here, and the supply tolerance.
  • The socket reference or the existing relay being replaced.
  • The load type and current on each contact.
  • The delivery location and whether the relays are for a project or maintenance stock.

Documents and quotation

The Schneider Electric datasheet for the RXM3AB1B7 is attached on this page, and the figures above come from it. Always check the latest revision before final design.

To obtain a quotation, send us the part number RXM3AB1B7 with the quantity and delivery location, and we will respond with availability and lead time. Seven Star LLC is an independent supplier and does not claim any official status with the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric RXM3AB1B7 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric RXM3AB1B7 Harmony RXM Relay 24 V

Answers from our engineering team on installation, compatibility and integration.

01What coil voltage does the RXM3AB1B7 use?
The RXM3AB1B7 has a 24 V AC control coil. The datasheet gives operating limits of 19.2–26.4 V AC and a drop-out threshold of ≥ 0.15 Uc, and an average coil resistance of 180 Ohm at 20 °C ± 15 %.
02How many contacts and what current does the RXM3AB1B7 switch?
It has 3 changeover contacts with a load current of 10 A at 250 V AC; 10 A at 28 V DC and a maximum switching capacity of 2500 VA/280 W. The contact material is AgNi.
03Does the RXM3AB1B7 have an LED or a test button?
It has no status LED and a lockable test button, according to the datasheet.
04What temperature range applies to the RXM3AB1B7?
The datasheet lists operation at -40–55 °C and storage at -40–85 °C. The relay is rated IP40 conforming to IEC 60529, so it is intended for installation inside a panel.
05Can I request a quotation for the RXM3AB1B7 in Oman?
Yes. Send the part number RXM3AB1B7, the quantity and the delivery location, and Seven Star LLC will confirm availability and lead time as an independent supplier in Muscat.