Schneider Electric RSL1PVBU Slim Interface Relay 24 V

Description

RSL1PVBU slim interface relay with socket: overview

RSL1PVBU is a Harmony RSL slim interface relay delivered pre-assembled on its own socket. The unit is only 6.2 mm wide, carries one changeover contact rated 6 A, and runs from a 24 V AC/DC control signal with an LED and a protection module already fitted.

Pre-assembly saves wiring time on panels with many digital outputs: the relay, coil protection and socket come as one component, with screw connectors for the conductors. The datasheet we hold is dated 8 Nov 2026, and Seven Star LLC supplies RSL1PVBU in Oman and the GCC as an independent supplier in Muscat.

Control circuit and contact limits of RSL1PVBU

The control input is 24 V AC/DC with limits of 21.6–28.8 V, so it accepts either a PLC output rail or a small AC control supply. The datasheet gives an average coil resistance of 3390 Ω (DC), average consumption of 0.17 W DC and a drop-out threshold of ≥ 0.05 Uc, meaning the coil must fall to a low voltage before the relay releases.

That low drop-out matters on PLC outputs that leak: check that the off-state leakage of the output plus any parallel LED or surge element cannot hold the coil above 5 % of 24 V. Contact data for RSL1PVBU: 6 A at 250 V AC in AC-1, maximum 1500 VA, minimum 100 mA at 12 V, which means it is a power-level contact and not intended for dry-circuit signals.

Operate time is 12 ms and reset 5 ms. Contact life is 60000 cycles at 6 A, 250 V AC-1, against 10000000 mechanical cycles; operating rate under load is limited to 360 cycles per hour.

Installation and maintenance

Snap the assembly onto a 35 mm rail, wire the coil and contact terminals within the 0.5 N·m limit, and test with a known load before closing the panel. Since the relay is pre-assembled, replacement means replacing the module; label each channel so that a swap is quick.

The datasheet gives IP40 and an ambient range of −40 to 55 °C, so keep it in an enclosure with adequate ventilation, and do not stack heat-generating devices directly beside a row of these relays.

Selection and ordering checklist for RSL1PVBU

Before ordering RSL1PVBU, confirm:

  • The control signal is 24 V AC or DC within 21.6–28.8 V, and the output driver leaks little when off.
  • One changeover contact of 6 A is sufficient; otherwise a multi-contact relay is needed.
  • The load is not below 100 mA at 12 V, which is the stated minimum.
  • Screw connector sizes up to 2.5 mm² suit your wiring.
  • Rail space and clearance for a 6.2 mm wide, 78.6 mm tall module.

Related relay and socket parts

Within the Harmony Electromechanical Relays range, the RSB series interface relays (for example RSB2A080BD, 8 A, 2 C/O) are wider but offer two contacts and plug into separate sockets such as RSZE1S48M. RSL1PVBU is the choice when width and a pre-assembled build matter more than contact count or relay replacement without rewiring.

Information to send with an RFQ

To quote RSL1PVBU, please send:

  • Part number RSL1PVBU and the quantity.
  • Control voltage and the output device driving it.
  • Load type and current.
  • Delivery location in Oman or the GCC.

RSL1PVBU technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / RSL1PVBU
Range / series Harmony Electromechanical Relays, RSL series, slim interface relay
Type Pre-assembled plug-in relay with socket
Contacts 1 C/O, standard operation
Control voltage 24 V AC/DC (input limit 21.6–28.8 V)
Status LED / protection LED fitted; protection module included
Thermal current 6 A at -40–55 °C
Rated operational current 6 A 1 C/O (AC-1/DC-1), IEC/UL
Max switching capacity 1500 VA / 150 W; maximum switching voltage 277 V
Minimum switching 100 mA, 12 V, 120 mW
Contact material Silver alloy (AgSnO2)
Coil data Average resistance 3390 Ω (DC, 23 °C); consumption 0.17 W DC; drop-out ≥ 0.05 Uc
Operate / reset time 12 ms operate; 5 ms reset
Durability Mechanical 10000000 cycles; electrical 60000 cycles at 6 A, 250 V, AC-1
Connections Screw connectors, 1 × 0.2–2.5 mm² (24–14 AWG), torque < 0.5 N·m
Mounting 35 mm DIN rail; plastic compression spring fixing
Insulation / impulse Ui 250 V IEC, 277 V cUL; Uimp 6 kV; 4000 V AC coil to contact
Size / weight 6.2 × 78.6 × 95 mm (W × H × D); 0.029 kg
Operating / storage temperature -40–55 °C / -40–85 °C
Protection IP40
Certifications UL, GOST, CSA; CE marking

Where RSL1PVBU is used in Oman and the GCC

Slim interface relays like this fill terminal strips between PLC and field in water treatment, power distribution, oil and gas skids and building management panels. This unit is a fit where a single changeover contact per channel is enough and cabinet space is the constraint.

Heat is the main environmental factor in Gulf installations; the 55 °C operating ceiling in the datasheet is a real design limit for sun-loaded cabinets, so verify enclosure temperature rise in summer.

Why the 6.2 mm width matters

Interface relays are mounted in rows. At 6.2 mm per channel, a 16-channel marshalling strip needs about 100 mm of rail for the relays themselves, which is a large saving over a 15.5 mm wide socket such as the RSZE1S48M. For this unit, the 78.6 mm height and 95 mm depth should still be checked against duct clearance and door depth.

The compression-spring fixing described in the datasheet and the screw connectors keep terminations accessible from the front, which helps when a loop has to be traced under time pressure.

Documents and quotation

The datasheet for this unit is attached to this page (document dated 8 Nov 2026). Please treat it as the reference for every figure above, and tell us if your project specification asks for anything the datasheet does not state.

Send the part number, quantity, required delivery point and any project reference through the quotation form or by email. Seven Star LLC is an independent industrial supplier based in Muscat, serving customers across Oman and the GCC, and we reply with availability and lead time for this exact part number.

Datasheets & Documents
  • PDF Datasheet Schneider Electric RSL1PVBU Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric RSL1PVBU Slim Interface Relay 24

Answers from our engineering team on installation, compatibility and integration.

01What control voltage does RSL1PVBU use?
24 V AC/DC, with an input voltage limit of 21.6–28.8 V.
02How many contacts does RSL1PVBU have?
One changeover (1 C/O) contact rated 6 A at 250 V AC in AC-1, with a maximum switching capacity of 1500 VA.
03How wide is RSL1PVBU?
The datasheet gives 6.2 mm wide, 78.6 mm high and 95 mm deep; the net weight is 0.029 kg.
04Does RSL1PVBU include a socket and LED?
Yes, it is a pre-assembled relay with socket, and it has a status LED and a protection module.
05What temperature limits apply to RSL1PVBU?
Operating ambient is −40 to 55 °C and storage −40 to 85 °C; protection is IP40.