Schneider Electric GVAD1010 TeSys GV2/GV3 2 NO Contact Block

Description

GVAD1010: two normally open contacts for breaker status and trip signals

The GVAD1010 is a Schneider Electric TeSys Deca side contact block for GV2 and GV3 motor circuit-breakers with two normally open contacts, one of which acts as the fault signal. It is the right accessory when the control system only needs closing signals and no normally closed loop. Seven Star LLC supplies the GVAD1010 in Oman and the GCC as an independent supplier based in Muscat.

Within the family, the GVAD1010 is the only active reference with two NO contacts. The other three trade one of them for a normally closed contact. So the choice is mostly about the input card that will read them.

Technical specifications of the GVAD1010

Parameter Specification
Manufacturer / part number Schneider Electric / GVAD1010
Description Product datasheet TeSys GV2 & GV3 – auxiliary contact – 1 NO + 1 NO (fault)
Range TeSys; TeSys Deca
Device short name GVAD
Product or component type Auxiliary contact block
Product compatibility GV2L; GV2P; GV2RT; GV3L; GV2LE; GV3P; GV2ME
Mounting location Left side
Auxiliary contacts operation Fault signal 1 NO
Pole contact composition 2 NO
[Ui] rated insulation voltage 690 V conforming to IEC 60947-1; 300 V conforming to UL 508; 300 V conforming to CSA C22.2 No 14
[Ue] rated operational voltage 48 to 690 V AC; 24 to 240 V DC
[Ith] conventional free air thermal 6A
Mechanical durability 100000 cycles
Minimum switching current 5 mA
Minimum switching voltage 17 V
Protection type GB2CB– circuit breaker; GG fuse 10 A
Rated operational power in VA 300 VA at 48 V AC-15 – electrical durability: 100000 cycles; 414 VA at 690 V AC-15 – electrical durability: 100000 cycles
Rated operational power in W 120 W at 240 V DC-13 – electrical durability: 100000 cycles; 140 W at 110 V DC-13 – electrical durability: 100000 cycles
Height 89 mm
Width 9.3 mm
Depth 66 mm
Net weight 0.055 kg
Environmental characteristic Normal environment
Product certifications UKCA

Ordering checklist for the GVAD1010

  • Both contacts normally open; the fault signal is one of them.
  • Match the PLC input type to closing signals.
  • Check compatibility of the breaker with the listed GV2 and GV3 types.
  • Check that the signal voltage is within 24 to 240 V DC or 48 to 690 V AC.
  • Keep the contact function written on the wiring schedule.

GVAD family: the GVAD1010 against its siblings

The four references below share the same left-side mounting and ratings and differ only in contact pattern and lifecycle status.

Reference Contacts Fault signal contact Status in datasheet
GVAD0101 2 NC Fault signal 1 NC Discontinued (17 Jul 2023)
GVAD0110 1 NO + 1 NC Fault signal 1 NC Listed
GVAD1001 1 NO + 1 NC Fault signal 1 NO Listed
GVAD1010 2 NO Fault signal 1 NO Listed

What the GVAD1010 fits and how it is rated

The block mounts at the left of GV2ME, GV2P, GV2L, GV2LE, GV2RT, GV3L and GV3P breakers, as the datasheet states. With 9.3 mm width it keeps a row of breakers compact.

Electrical limits are the same as in the other family members: 6 A conventional thermal current, 2.5 A on the fault contact, 48 to 690 V AC, 24 to 240 V DC, and 5 mA and 17 V as minimum switching level.

The block mounts on the left side of the breaker and is 9.3 mm wide, 89 mm high and 66 mm deep, with a net weight of 0.055 kg. The datasheet lists a rated operational voltage of 48 to 690 V AC and 24 to 240 V DC, a conventional thermal current of 6 A, and 2.5 A for the fault-signalling contact. Rated operational power at AC-15 is 720 VA at 230 to 240 V and 850 VA at 380 to 415 V, each with an electrical durability of 100000 cycles; the DC-13 figures include 120 W at 240 V DC.

Commissioning notes for the GVAD1010

Fit with the feeder isolated, check continuity at each terminal pair in both breaker positions, and record which terminal is the fault contact and which is the status contact. The datasheet gives mechanical durability as 100000 cycles, so no extra maintenance is needed in ordinary use.

When replacing a block on a running plant, plan the shutdown of the feeder; the block cannot be changed live.

GVAD1010 in Oman and GCC installations

Packaged plant such as chiller skids, fire-water pump panels and compressor starters report their breaker status with closing contacts to the site DCS. Two NO contacts on one block save an extra accessory.

Where panels are built to a standard of closing signals, the GVAD1010 is the usual spare to hold in stock.

Reading the two contacts of the GVAD1010

With both contacts normally open, each one gives a closing signal. One reports the fault condition, the other reports the status of the breaker. Neither carries a supervised loop, so a broken cable shows up as a missing signal and not as an alarm.

If your design relies on loop supervision, specify a block with a normally closed fault contact. If it uses simple lamp or counter inputs, the GVAD1010 keeps the logic uniform: all signals are closing signals.

Information to send with an RFQ for the GVAD1010

  • Full reference and quantity required
  • Breaker model (GV2 or GV3 type) the block must fit
  • Contact logic needed (NO or NC fault signal)
  • Signal voltage and the input card that reads it
  • Delivery location and timing

Storage, handling and spares for the GVAD1010

Keep the GVAD1010 in its original packaging in a dry, dust-free store until installation, and check the label against the order before fitting. For plants that run continuously, holding one spare unit on site shortens downtime if a replacement is needed during a shutdown or after a fault. Record the reference and installation date in the maintenance log so the next order can be placed quickly.

Documents and quotation

A datasheet for the GVAD1010 is attached on this page. It carries the electrical, mechanical and environmental data summarised above, so the figures can be checked against your drawings.

Send the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Tesys Gvad Range

Seven Star LLC supplies models from the Se Tesys Gvad range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric GVAD0101 TeSys GV2/GV3 2 NC Contact BlockContactors & Overload RelaysView details
Schneider Electric GVAD0110 TeSys GV2/GV3 1 NO + 1 NC ContactContactors & Overload RelaysView details
Schneider Electric GVAD1001 TeSys GV2/GV3 1 NC + 1 NO ContactContactors & Overload RelaysView details
Schneider Electric GVAD1010 TeSys GV2/GV3 2 NO Contact BlockContactors & Overload RelaysYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric GVAD1010 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric GVAD1010 TeSys GV2/GV3 2 NO

Answers from our engineering team on installation, compatibility and integration.

01What contacts does the GVAD1010 have?
Two normally open contacts, one of which is the fault signal.
02Does the GVAD1010 have a normally closed contact?
No. Its pole composition in the datasheet is 2 NO.
03Which breakers fit the GVAD1010?
GV2ME, GV2P, GV2L, GV2LE, GV2RT, GV3L and GV3P.
04Which AC-15 power is listed for the GVAD1010?
720 VA at 230 to 240 V and 850 VA at 380 to 415 V, with 100000 cycles of electrical durability.
05How heavy is the GVAD1010?
0.055 kg. See the datasheet linked on this page for the full figures.