- Automation & ControlView all 2,221 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- Motor Soft Starters
- HMI Displays
- Pneumatic Cylinders
- Industrial Computers
- Servo Drives
- Machine Vision
- Automation Software
- Robotics
Brand: Schneider Electric
Schneider Electric EZC100H4100 Easypact 100 A 4P MCCB
Description
What the EZC100H4100 is
Start with the reference. The EZC100H4100 is an EasyPact EZC100H moulded-case circuit breaker, and the datasheet title reads: circuit breaker Easypact EZC100H – TMD – 100 A – 4 poles 3d. The letter H matches the breaking capacity code H printed in the document, the 4 after it gives the pole count and 100 is the rating in amperes at 40 °C. In plain terms it is a four-pole breaker with four poles of which three are protected and the fourth (neutral) has no protection. Seven Star LLC is an independent supplier in Muscat and can quote the EZC100H4100 for projects in Oman and the GCC.
Technical specifications of the EZC100H4100
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / EZC100H4100 |
| Range of product | EasyPact EZC |
| Product or component type | Circuit breaker |
| Device short name | Easypact EZC100H |
| Device application | Distribution |
| Poles description | 4P |
| Protected poles description | 3t |
| Network type | DC and AC |
| Network frequency | 50/60 Hz |
| [In] rated current | 100 A at 40 °C |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 550 V AC 50/60 Hz; 250 V DC |
| Breaking capacity code | H |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Utilisation category | Category A |
| Trip unit | TM-D, thermal-magnetic |
| Trip unit rating | 100 A at 50 °C |
| Protection type | overload protection and short-circuit protection |
| Control type | Toggle |
| Mounting mode / support | Fixed / backplate |
| Upstream / downstream connection | Front / Front |
| Connection pitch | 25 mm |
| Local signalling | Positive contact indication |
| Neutral protection setting | Without protection |
| Earth-leakage protection | Without |
| Mechanical durability | 13000 cycles |
| Height x width x depth | 130 mm x 100 mm x 60 mm |
| IP / IK degree | IP20 conforming to IEC 60529; IK07 conforming to EN 50102 |
| Operating temperature | -25–70 °C |
| Storage temperature | -35–85 °C |
| Unit weight (package 1) | 1.045 kg |
Information to send with an RFQ for the EZC100H4100
- Reference EZC100H4100 and the quantity required
- Supply voltage, AC or DC, and frequency at the point of installation
- Prospective short-circuit current at the installation point
- Load current and cable size so that the 100 A rating can be confirmed
- Delivery location and required date
- Whether the breaker is for a new panel or a like-for-like replacement
Selection and ordering checklist for the EZC100H4100
- Confirm that 100 A at 40 °C is the right continuous rating for the cable and the load; the trip unit rating in the datasheet is 100 A at 50 °C.
- Check that the voltage at site is covered by the Ue entries: 550 V AC 50/60 Hz; 250 V DC.
- Compare the prospective short-circuit current with the Icu table for the EZC100H4100; use the Ics column when service continuity after a fault matters.
- Decide whether the pole count is correct: four poles with a neutral pole that is not protected by the trip unit.
- Verify that the space at the panel is 100 mm wide, 130 mm high and 60 mm deep, plus the clearance required for connections.
- Check the supply of accessories separately; the datasheet for the EZC100H4100 covers the breaker only.
Breaking capacity of the EZC100H4100 at each voltage
The breaking capacity is the figure that decides whether a breaker may sit at a given point in a network, and the EZC100H4100 datasheet lists it per voltage and per pole condition. The ultimate breaking capacity (Icu) is listed first, followed by the rated service breaking capacity (Ics).
| Voltage and pole condition | Icu (kA) |
|---|---|
| 125 V DC 1P | 10 |
| 250 V DC 2P | 10 |
| 550 V AC 50/60 Hz | 10 |
| 110–130 V AC 50/60 Hz | 100 |
| 440 V AC 50/60 Hz | 20 |
| 220–240 V AC 50/60 Hz | 50 |
| 380–400 V AC 50/60 Hz | 30 |
| 415 V AC 50/60 Hz | 30 |
| Voltage | Ics (kA) |
|---|---|
| 125 V DC | 5 |
| 250 V DC | 5 |
| 440 V AC 50/60 Hz | 5 |
| 550 V AC 50/60 Hz | 2.5 |
| 380–400 V AC 50/60 Hz | 15 |
| 220–240 V AC 50/60 Hz | 25 |
| 110–130 V AC 50/60 Hz | 50 |
| 415 V AC 50/60 Hz | 7.5 |
Read the H class in this light: at 220–240 V AC the datasheet gives 50 kA Icu and at 400–415 V AC 30 kA Icu for the EZC100H4100. Compare these with the prospective short-circuit current calculated at the installation point, not with the nameplate of the transformer alone.
Typical applications of the EZC100H4100 in Oman and the GCC
A 100 A breaker of this type is normally found in sub-distribution boards and larger single feeders. In Oman and the GCC such devices appear in commercial buildings, workshops, site cabins, utility rooms and the auxiliary panels of industrial plants, including oil and gas, power and water installations. The datasheet marks the device application as distribution.
Heat is the main practical concern: a panel in direct sun can run well above the 40 °C reference of this breaker rating, so check the panel temperature, ventilation and derating rules with the panel builder. Dust and humidity favour a sealed enclosure with the IP rating checked for the whole panel, not only the breaker.
Where the EZC100H4100 fits in the EZC100 range
This breaker belongs to the EZC100 frame, which the catalogue offers in several pole counts and ratings. The four-pole body is 100 mm wide; three poles are protected and the fourth is the neutral pole, which is not protected by the trip unit. Other references in the same family seen in our catalogue include EZC100H4040, EZC100H4060; each has its own datasheet, and the breaking capacity depends on the frame letter, so a EZC100H4100 cannot be exchanged for an EZC100F or EZC100N breaker of the same rating without checking the figures above.
The datasheet lists the breaker as fixed on a backplate with front upstream and front downstream connections, so it goes into a panel designed for backplate mounting rather than a DIN-rail layout.
Installation, commissioning and maintenance of the EZC100H4100
Mount this breaker on a flat backplate and keep the front connections accessible. The datasheet gives a mechanical durability of 13000 cycles, so operating the handle for routine tests is within the stated life, but it should not be used as a daily switch. The control type is toggle and the local signalling is positive contact indication, which lets an operator see the contact state at the front.
Before energising, check terminal tightness against the cable manufacturer and panel instructions and compare the trip unit marking with the cable rating. During maintenance, look for discolouration at the terminals, which is a common sign of a loose connection, and keep a record of the breaker reference. The datasheet gives an operating temperature of -25–70 °C and a storage temperature of -35–85 °C, with IP and IK degrees of IP20 conforming to IEC 60529 and IK07 conforming to EN 50102, so the breaker needs a proper enclosure in dusty or damp sites.
How the EZC100H4100 protects the circuit
Inside this breaker the 100 A trip unit works with two mechanisms, as the datasheet naming (TM-D, thermal-magnetic) indicates: a heat-driven part for overloads and a magnetic part for short circuits. Rating and temperature belong together: the datasheet gives 100 A at 40 °C for the breaker and 100 A at 50 °C for the trip unit. A fixed trip unit means there is no dial to turn on site, which keeps this breaker simple to commission but means the rating must be right before the order.
Because this breaker is listed with the neutral setting “without protection” and protected poles 3t, plan the neutral conductor separately where the system needs it.
Documents and quotation
A datasheet for this breaker is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it should be read together with the manufacturer installation instructions before the final design.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Other Models in the Se Easypact Ezc100h Range
Seven Star LLC supplies models from the Se Easypact Ezc100h range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric EZC100H2100 Easypact 100 A 2P MCCB | Circuit Breakers | View details |
| Schneider Electric EZC100H3100 Easypact 100 A 3P MCCB | Circuit Breakers | View details |
| Schneider Electric EZC100H4100 Easypact 100 A 4P MCCB | Circuit Breakers | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric EZC100H4100 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric EZC100H4100 Easypact 100 A 4P
Answers from our engineering team on installation, compatibility and integration.
01What is the rated current of the EZC100H4100?
The datasheet gives 100 A at 40 °C for the breaker, with the trip unit rated at 100 A at 50 °C. The TM-D trip unit is thermal-magnetic.
02How many poles does the EZC100H4100 have?
The datasheet lists 4P with protected poles 3t, meaning four poles, three of them protected. The width is 100 mm.
03What is the breaking capacity of the EZC100H4100?
The datasheet lists 50 kA Icu at 220–240 V AC 50/60 Hz and 30 kA Icu at 415 V AC 50/60 Hz. The full voltage-by-voltage table is on this page; compare it with the prospective short-circuit current at site.
04What voltage can the EZC100H4100 be used on?
The rated operational voltage entries are: 550 V AC 50/60 Hz; 250 V DC. The rated insulation voltage is 690 V AC 50/60 Hz.
05How is the EZC100H4100 mounted and connected?
The datasheet gives fixed mounting on a backplate, with front upstream and front downstream connections and a 25 mm pitch.


















Reviews
There are no reviews yet.