Schneider Electric GV3L40 TeSys GV3 40 A Motor Breaker

Description

GV3L40: rotary handle, magnetic only motor circuit breaker

The GV3L40 is a Schneider Electric TeSys Deca GV3 motor circuit breaker of the magnetic-only type: three poles, 40 A rating, rotary handle. A magnetic-only breaker contains short-circuit protection but no thermal element, so it protects the cable and the starter against faults and leaves overload protection to a separate relay in the contactor circuit.

Reading the reference against the datasheet: the device short name is GV3L, which the datasheet pairs with a rotary handle and magnetic trip technology; the digits after the family letters follow the current band, here 40 A.

The datasheet gives the range as TeSys Deca and the product name as TeSys GV3, with the application stated as motor protection. Rated operational voltage is 690 V AC 50/60 Hz, rated insulation voltage 690 V AC 50/60 Hz and the rated impulse withstand 6 kV.

GV3L40 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / GV3L40
Range / product name TeSys Deca / TeSys GV3
Device short name GV3L
Product type Motor circuit breaker
Trip unit technology Magnetic
Poles 3P
Control Rotary handle
Rated current [In] 40 A
Magnetic tripping current 560 A
Conventional thermal current [Ith] 40 A
Rated operational voltage [Ue] 690 V AC 50/60 Hz
Utilisation categories Category A; AC-3
Suitability for isolation Yes
Power dissipation per pole 8 W
Mechanical durability 50000 operating cycles
Electrical durability 50000 cycles for AC-3 at 415 V In
Fixing 35 mm symmetrical DIN rail: clipped | Panel: screwed (with 3 x M4 screws)
Mounting position Horizontal or Vertical
Dimensions H × W × D 132 × 55 × 136 mm
Net weight 0.96 kg
Tightening torque 5 N.m – on screw clamp terminal
IP / IK protection IP20
Operating temperature -20 to 60 °C
Storage temperature -40 to 80 °C
Operating altitude 3000 m
Standards EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, IEC/EN 60335-1:Clause 30.2, IEC/EN 60335-2-40:Annex JJ
Certifications CB Scheme, CE, UKCA, CCC cULus, EAC, LROS (Lloyds register of shipping), BV, ABS, DNV-GL

How the GV3L40 protects the motor feeder

The only trip element in the GV3L40 is magnetic. At 560 A the breaker opens instantly, which for a 40 A rating is a fixed threshold of roughly 14.0 times the rated current. There is no thermal setting dial, so there is nothing to adjust on site, and the datasheet does not list phase-failure sensitivity for this version.

This makes the GV3L40 a good fit where the motor is already protected against overload by a relay, a soft starter or a drive. The breaker then provides isolation and short-circuit protection, while the thermal function stays with the equipment that knows the real motor load. Do not use it alone as motor overload protection.

GV3L40 compared with neighbouring TeSys GV3 ratings

The table lists the closest GV3 references by current. Moving one step up or down changes the thermal range, the magnetic trip and the motor power it is intended for, while the frame stays the same. Neighbouring references are GV3P18, GV3P25, GV3P40 and GV3L50.

Reference Type Setting / rating Magnetic trip Motor kW at 400/415 V
GV3P18 rotary handle, thermal-magnetic 12–18 A 252 A 7.5 kW
GV3P25 rotary handle, thermal-magnetic 17–25 A 350 A 11 kW
GV3L40 (this page) rotary handle, magnetic only 40 A 560 A 18.5 kW
GV3P40 rotary handle, thermal-magnetic 30–40 A 560 A 18.5 kW
GV3L50 rotary handle, magnetic only 50 A 700 A 22 kW
GV3P50 rotary handle, thermal-magnetic 37–50 A 700 A 22 kW

Among the GV3 references covered here, the rotary thermal-magnetic GV3P units run from 12 A to 65 A and the magnetic-only GV3L units from 40 A to 80 A; the L versions need a separate overload relay.

Dimensions, terminals and mounting of the GV3L40

The GV3L40 is a larger frame: 55 mm wide, 132 mm high and 136 mm deep, weighing 0.96 kg. It clips to a 35 mm DIN rail or is screwed to a plate with three M4 screws, and it is mounted horizontally or vertically. Terminals are EverLink type with a tightening torque of 5 N.m – on screw clamp terminal.

Environmental limits from the datasheet are -20 to 60 °C in operation and -40 to 80 °C in storage, an altitude limit of 3000 m, and protection IP20. Power dissipation is 8 W per pole, so the heat released inside the enclosure at full load is about 24 W for the three poles; add this to the enclosure thermal budget in a Gulf plant room.

Selection checklist and RFQ details for the GV3L40

  • Motor nameplate current and voltage, checked against the 40 A range and the motor kW table
  • Required control style: rotary handle
  • An overload relay is needed behind the breaker because this version has no thermal element
  • Prospective short-circuit current at the board against the 50 kA rating at 400/415 V
  • Terminals: EverLink terminals; check the cable size and ferrule practice
  • Space for a 55 mm wide device, 136 mm deep, and ambient heat inside the enclosure
  • Accessories such as auxiliary contacts, trip indicators or busbar links if the design uses them

When requesting a quotation, include the following with the part number:

  • Part number GV3L40 and quantity
  • Motor power, voltage and full-load current
  • Replacement or new build, and the existing breaker marking
  • Delivery location and required date

Motor ratings listed for the GV3L40

The datasheet ties this breaker to specific motor sizes at each supply voltage. These figures are the rated motor powers for the AC-3 category and are what a motor schedule should be matched against, not only the current.

Supply voltage Motor power in datasheet
400/415 V AC 18.5 kW
500 V AC 22 kW
690 V AC 37 kW

Rated duty is uninterrupted, and the durability figures are given in the table of specifications.

Using the GV3L40 in Oman and the GCC

Motor starters are everywhere in Gulf plants, and this breaker suits mid-size process pumps, compressors, blowers and larger fans on utility and plant-services panels. The datasheet lists motor powers up to 37 kW across its voltages, which is what the GV3 frame is built for. Typical sites are desalination and water treatment, power auxiliaries, oil and gas utilities, petrochemical units and commercial HVAC.

Heat and dust drive the real life of a breaker. With an operating limit of -20 to 60 °C and protection of IP20, the device belongs inside a ventilated or air-conditioned enclosure rather than on an open wall in summer sun. For a retrofit, send the nameplate and the old breaker marking and we will match it.

Breaking capacity of the GV3L40 by voltage

Short-circuit breaking capacity falls as system voltage rises, which is the reason to read the whole table instead of a single headline value. The service breaking capacity Ics is shown as a percentage of Icu.

Voltage Icu Ics as % of Icu
230/240 V AC 100 kA 100 %
400/415 V AC 50 kA 100 %
440 V AC 50 kA 100 %
500 V AC 12 kA 50 %
690 V AC 6 kA 50 %

At 400/415 V AC the rating is 50 kA, which is the figure that matters on most Gulf 400 V distribution boards; compare it with the prospective fault level at the point of installation and with any upstream protection before relying on it.

Documents and quotation

The Schneider Electric manufacturer datasheet for the GV3L40 is attached on this page as a PDF. It is the reference for every rating quoted above, and it is worth checking the revision against your project documents before an order is placed. The utilisation categories, breaking capacity table and environmental limits are all in it.

Seven Star LLC is an independent supplier in Muscat that serves buyers in Oman and the GCC. Send the part number GV3L40, the quantity and the delivery site, and we will reply with a quotation and the availability we can confirm.

Datasheets & Documents
  • PDF Datasheet Schneider Electric GV3L40 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric GV3L40 TeSys GV3 40 A Motor

Answers from our engineering team on installation, compatibility and integration.

01What current range does the GV3L40 cover?
The GV3L40 is a magnetic-only breaker with a 40 A rating and a fixed magnetic trip of 560 A; it has no thermal adjustment.
02What is the breaking capacity of the GV3L40 at 400/415 V?
The datasheet gives 50 kA Icu at 400/415 V AC, with the service breaking capacity shown as a percentage of Icu in the table above.
03Does the GV3L40 provide overload protection?
No, it is a magnetic-only version. It trips on short-circuit and provides isolation, so a separate overload relay is needed.
04How is the GV3L40 operated and mounted?
It uses a rotary handle and mounts on a 35 mm DIN rail or on a panel. Size is 55 mm wide, 132 mm high and 136 mm deep.
05What motor powers is the GV3L40 listed for?
18.5 kW at 400/415 V; 22 kW at 500 V; 37 kW at 690 V.