Schneider Electric EZ9F51310 Easy9 3P 10 A C-curve MCB
Description
EZ9F51310: Easy9 3P 10 A C-curve miniature circuit breaker
The EZ9F51310 is a Schneider Electric Easy9 miniature circuit breaker with three-pole construction, a 10 A rated current and a C trip curve. It uses thermal-magnetic tripping, clips onto a DIN rail and is rated for AC networks. Seven Star LLC supplies the EZ9F51310 in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference from the product title: 3P is the pole count, 10 A is the rated current [In], C is the curve code, and the series title states the breaking capacity and voltage class. Three protected poles open all three phases at once, so a fault on one phase disconnects the whole three-phase load. This sits in the higher breaking-capacity group of the series, with 10000 A listed at both 230 V and 400 V.
What the C curve and 10 A rating mean for the EZ9F51310
The datasheet gives a magnetic tripping limit of 5 to 10 times In. For a 10 A device that works out to roughly 50 A to 100 A, the band in which the instantaneous magnetic element is expected to open the circuit on a short circuit. Below that, the thermal element handles ordinary overloads and trips more slowly the smaller the overload is. The C characteristic tolerates the inrush of lamps, small transformers and motors better than a B curve, yet reacts sooner than a D curve to a genuine fault.
Under IEC 60898-1, the standard named in the datasheet, a breaker of this kind carries its rated current without tripping and then opens within defined times at higher multiples; the exact time-current curve belongs to the manufacturer’s published characteristics. This unit is therefore best matched to lighting circuits, small control supplies and low-power equipment feeders, where the cable is sized for 10 A or slightly above and the downstream load has moderate starting current.
Technical specifications of the EZ9F51310
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / EZ9F51310 |
| Range / application | Easy9 / Distribution |
| Product type | Miniature circuit-breaker (Easy9 MCB) |
| Poles / protected poles | 3P / 3 |
| Rated current [In] | 10 A |
| Network type / frequency | AC / 50/60 Hz |
| Trip unit | Thermal-magnetic |
| Curve code | C |
| Magnetic tripping limit | 5–10 × In (calculated 50–100 A) |
| Rated operational voltage [Ue] | 400 V AC |
| Breaking capacity | 10000 A Icn at 230 V AC 50/60 Hz; 10000 A Icn at 400 V AC 50/60 Hz |
| Rated service breaking capacity [Ics] | 10 kA 100 % x Icn at 400 V AC 50/60 Hz |
| Limitation class | 3 |
| Rated insulation voltage [Ui] | 500 V AC 50/60 Hz |
| Rated impulse withstand [Uimp] | 4 kV |
| Suitability for isolation | Yes |
| Control / indication | Toggle; contact position indicator |
| Mounting | Clip-on, DIN rail |
| Width | 54 mm (6 × 9 mm pitches) |
| Height / depth | 81 mm / 66.5 mm |
| Colour | Grey (RAL 7035) |
| Terminals | Tunnel type terminal (top or bottom) 1–25 mm² rigid; Tunnel type terminal (top or bottom) 1–16 mm² flexible |
| Tightening torque | 2 N.m top or bottom |
| Mechanical durability | 20000 cycles |
| Electrical durability | 4000 cycles |
| Standard | IEC 60898-1 |
| Certification | CE |
| Degree of protection | IP20 conforming to IEC 60529 |
| Pollution degree / tropicalisation | 2 / 2 |
| Ambient temperature | Operation -5 to 60 °C; storage -40 to 85 °C |
| Relative humidity | 95 % at -5 to 60 °C |
| Packing | 1 piece, 310 g; carton of 4 |
| Warranty | 18 months |
Installation and maintenance of the EZ9F51310
Isolate the board before work, clip the EZ9F51310 onto the DIN rail and make sure the toggle moves freely. Strip conductors to the length the terminal needs, insert them fully and tighten to 2 N.m. This unit accepts the cross-sections listed above, so avoid forcing larger cable or using ferrules that do not fit. After energising, operate the toggle once to check the contact position indicator, then label the circuit.
Periodically re-torque terminals in boards that see vibration or large temperature swings, and look for discoloured plastic, which indicates heat at a termination. A breaker that has tripped on a short circuit should be investigated before it is reset, and one that trips repeatedly on a normal load points to an undersized rating, not a faulty device.
Size, terminals and mounting of the EZ9F51310
The EZ9F51310 is 54 mm wide, 81 mm high and 66.5 mm deep, which equals 6 modules of 9 mm. It clips on a DIN rail and its toggle shows the contact position. Terminals are tunnel type, top or bottom, with Tunnel type terminal (top or bottom) 1–25 mm² rigid; Tunnel type terminal (top or bottom) 1–16 mm² flexible. The tightening torque is 2 N.m, and a calibrated screwdriver avoids both loose and crushed conductors.
At 6 modules it takes three times the width of a single-pole breaker, so allow for the extra rail length and neutral busbar arrangement. Ambient limits are -5 to 60 °C in operation and IP20 applies to the front of the breaker, so the enclosure supplies the wider protection.
Breaking capacity and voltage data of the EZ9F51310
Breaking capacity is listed as 10000 A Icn at 230 V AC 50/60 Hz; 10000 A Icn at 400 V AC 50/60 Hz. The rated operational voltage is 400 V AC and the rated service breaking capacity [Ics] is 10 kA 100 % x Icn at 400 V AC 50/60 Hz. The Ics line is expressed as a percentage of Icn, so read both figures together when you compare with the prospective short-circuit current at the board.
The prospective fault current at the installation point must stay below the relevant rating, and the voltage on your network must match the voltages the datasheet quotes, not only the nominal value. The datasheet also lists 500 V AC insulation voltage and a 4 kV impulse withstand voltage. For a 3P circuit, confirm the supply type (phase-neutral or phase-phase) before ordering, because the quoted voltage differs between the references in this group.
How the EZ9F51310 compares with sibling references
These nearby Easy9 C-curve references from the same group show how rating, width and trip band move together. The pole count and the breaking-capacity group are the real differences; the amp rating changes the magnetic range and, at the top end, the terminal torque.
| Part number | Poles | Rated current | Width | Magnetic trip range | Terminal torque |
|---|---|---|---|---|---|
| EZ9F51310 (this page) | 3P | 10 A | 54 mm | 50–100 A | 2 N.m |
| EZ9F51316 | 3P | 16 A | 54 mm | 80–160 A | 2 N.m |
| EZ9F51320 | 3P | 20 A | 54 mm | 100–200 A | 2 N.m |
| EZ9F51332 | 3P | 32 A | 54 mm | 160–320 A | 3.5 N.m |
| EZ9F51340 | 3P | 40 A | 54 mm | 200–400 A | 3.5 N.m |
| EZ9F51363 | 3P | 63 A | 54 mm | 315–630 A | 3.5 N.m |
| EZ9F56306 | 3P | 6 A | 54 mm | 30–60 A | 2 N.m |
| EZ9F56310 | 3P | 10 A | 54 mm | 50–100 A | 2 N.m |
Information to send with an RFQ for the EZ9F51310
- Exact reference EZ9F51310 and the quantity needed.
- Supply voltage, system type and earthing arrangement.
- Prospective short-circuit current at the board, if known.
- Load description and cable size for the circuit.
- Any companion devices needed in the same order, such as other pole counts or ratings.
- Delivery location and project timeline.
Documents and quotation
The manufacturer datasheet for the EZ9F51310 is attached on this page and holds the full specification summarised above.
Send us the reference EZ9F51310, quantity and delivery location and Seven Star LLC will reply to your request. We supply as an independent supplier based in Muscat.
Other Models in the Se Easy9 Mcb C Range
Seven Star LLC supplies models from the Se Easy9 Mcb C range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric EZ9F51163 Easy9 1P 63 A C-curve MCB | Circuit Breakers | View details |
| Schneider Electric EZ9F51310 Easy9 3P 10 A C-curve MCB | Circuit Breakers | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric EZ9F51310 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric EZ9F51310 Easy9 3P 10 A C-curve
Answers from our engineering team on installation, compatibility and integration.
01What is the rating of the EZ9F51310?
The datasheet lists a 10 A rated current, 3P, C curve, thermal-magnetic trip unit, with breaking capacity of 10000 A Icn at 230 V AC 50/60 Hz; 10000 A Icn at 400 V AC 50/60 Hz.
02What is the magnetic trip range of the EZ9F51310?
The magnetic tripping limit is 5 to 10 times In, which for a 10 A device is about 50 to 100 A. This figure is calculated from the datasheet value.
03What size is the EZ9F51310 and how is it mounted?
It is 54 mm wide, 81 mm high and 66.5 mm deep (6 modules of 9 mm) and clips onto a DIN rail.
04What conductors fit the EZ9F51310 terminals?
Tunnel type terminals, top or bottom: 1-25 mm2 rigid; 1-16 mm2 flexible. Tighten to 2 N.m.
05Which standard and certification are listed for the EZ9F51310?
The datasheet names IEC 60898-1 and lists CE certification, with IP20 protection and an 18-month warranty.