- Automation & ControlView all 2,476 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Motor Soft Starters
- Encoders
- Safety Switches & Guard Locking
- HMI Displays
- Pneumatic Cylinders
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Rittal
Rittal SK 3126.100 Wall-Mounted Air/Air Heat Exchanger 17.5 W/K
Description
SK 3126.100 air/air heat exchanger decoded
The Rittal SK 3126.100 is a air/air heat exchanger of the TopTherm air/air heat exchanger range, 280 x 550 x 150 mm. This wall-mounted unit keeps the enclosure air and the ambient air in two separate circuits, so dust and moisture outside never enter the cabinet. Seven Star LLC supplies SK 3126.100 in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.
The table below decodes the main identifiers of SK 3126.100 so that it can be matched to a cabinet drawing.
| Element | Value | Meaning |
|---|---|---|
| SK | Product family prefix | Climate control accessory for enclosures |
| SK 3126.100 | Article number | Fixes size, output class and voltage in the manufacturer catalogue |
| 17.5 W/K specific thermal output | Duty point | Headline output or air figure used to pick this unit |
| 230 V, 1~, 50/60 Hz | Supply | Single-phase supply usable at 50 Hz and 60 Hz |
| 280 x 550 x 150 mm | Outer dimensions | Width x height x depth of the unit |
SK 3126.100 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Rittal / SK 3126.100 |
| Specific thermal output | 17.5 W/K |
| Air throughput, external circuit | 265 m³/h at 50 Hz, 315 m³/h at 60 Hz |
| Air throughput, internal circuit | 265 m³/h at 50 Hz, 315 m³/h at 60 Hz |
| Rated operating voltage | 230 V, 1~, 50/60 Hz |
| Rated current (max.) | 0.22 A at 50 Hz, 0.26 A at 60 Hz |
| Temperature control | Electronic control with digital display, factory setting +35 °C |
| Fault signal | Floating contact for overtemperature |
| Operating temperature range | -5 °C to 55 °C |
| IP rating (IEC 60529) | Internal circuit IP 54, external circuit IP 34 |
| Electrical connection | Plug-in terminal strip |
| Dimensions (W x H x D) | 280 x 550 x 150 mm |
| Pre-fuse | 2 A miniature circuit-breaker / fuse |
| Net / gross weight | 8.904 kg / 9.373 kg |
| Approvals listed on the article page | UR + C-UR (recognized) |
Values come from the manufacturer article page for SK 3126.100. Cooling data are catalogue test points; real performance depends on the temperature difference, the condition of the filters and the airflow around the unit.
How the SK 3126.100 air/air heat exchanger works
An air/air heat exchanger passes warm enclosure air and cooler ambient air through a plate core that keeps the two airstreams apart, so heat flows from inside to outside with no mixing. It can only cool the enclosure down to a level above the ambient temperature, and its effect scales with the temperature difference, which is what the figure of 17.5 W per kelvin expresses.
Sizing SK 3126.100 for an enclosure
The sizing is direct: heat removed = 17.5 W/K x (internal temperature – ambient temperature). With the factory setpoint of +35 °C and an ambient of 25 °C the unit removes about 175 W; with 15 K of difference about 263 W. If your losses are 150 W, the unit holds the enclosure about 9 K above ambient. If the ambient air is above the setpoint, an air/air unit cannot help and a compressor or water unit is required.
Selection and ordering checklist for SK 3126.100
- Total dissipated power of all equipment in the enclosure, in watts, plus the heat gain from sun and hot walls.
- Maximum permitted internal temperature of the most sensitive device, and the setpoint you want.
- Ambient temperature range on site, including summer peaks in Oman and the GCC.
- Ambient temperature always below the internal setpoint, with margin.
- Mounting cut-out and a free path for both airstreams.
- Supply of 230 V and a 2 A pre-fuse; fault contact wiring if overtemperature must be signalled.
Installation, commissioning and maintenance of SK 3126.100
- Mount in the cut-out so that both airstreams are unobstructed, and keep the plate core clean.
- Clean or blow out the core at regular intervals; dust on the outer circuit cuts the output.
- Check the fault signal contact wiring during commissioning and test the overtemperature alarm.
- Replace fans only with matching parts after switching off.
- Keep the door and cut-outs of the cabinet sealed to maintain the rated protection.
Apply local rules for electrical connection, and record the setpoint and alarm settings used at commissioning.
Typical applications of SK 3126.100 in Oman and the GCC
It is the answer for dusty or aggressive sites where the enclosure must stay closed but ambient air is cooler than the allowed internal temperature, such as outdoor panels in winter nights, ventilated plant rooms and cabinets near process dust.
Conditions in the Gulf are hard on enclosure electronics: summer ambient temperatures regularly exceed 45 °C, humidity near the coast leads to condensation when panels cool at night, and fine dust blocks filters quickly. Oil and gas, power, desalination and petrochemical sites therefore treat climate control as part of the panel design rather than an add-on.
Cooling principles compared against SK 3126.100
Choosing between heat exchangers and compressor units depends on ambient temperature, water availability and dust. The table compares SK 3126.100 with other cooling principles described on this site.
| Article | Principle | Headline figure | W x H x D (mm) |
|---|---|---|---|
| SK 3126.100 (this item) | Air/air heat exchanger | 17.5 W/K | 280 x 550 x 150 |
| SK 3209.500 | Air/water heat exchanger | 2.5 kW (L35 W10) | 597 x 417 x 475 |
| SK 3359.500 | Roof-mounted compressor unit | 0.77 kW (L35 L35) | 597 x 417 x 380 |
Information to send with an RFQ for SK 3126.100
To quote correctly we need a few details:
- Exact article number SK 3126.100 and the quantity.
- Enclosure size, material and surface area, and the room or site where it stands.
- Total heat loss in watts and the highest internal temperature allowed.
- Ambient temperature range, dust and humidity conditions.
- Supply voltage, frequency and available pre-fuse.
- Mounting position, cut-out availability and any condensate or water connection constraints.
- Delivery location in Oman or the GCC and the date needed.
Documents and quotation
A technical details document for SK 3126.100 is attached on this page, giving dimensions and installation drawings; check the article number printed on it.
Send the part number SK 3126.100 and the quantity to Seven Star LLC and we will confirm availability, lead time and delivery to your site in Oman or the GCC.
Other Models in the Rittal Sk Heat Exchanger Range
Seven Star LLC supplies models from the Rittal Sk Heat Exchanger range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Rittal SK 3209.500 Roof-Mounted Air/Water Heat Exchanger 2.5 kW | Enclosure Climate Control | View details |
| Rittal SK 3126.100 Wall-Mounted Air/Air Heat Exchanger 17.5 W/K | Enclosure Climate Control | You are viewing this model |
Datasheets & Documents
- Datasheet Rittal SK 3126.100 Technical Details Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Rittal is a German manufacturer of enclosures, power distribution, climate control and IT infrastructure, founded in 1961 by Rudolf Loh in Rittershausen, Hesse, as Rudolf Loh Elektrogerätebau. In its first year it launched the first standard enclosure, built in series and available from stock instead of made to order. Rittal is headquartered in Herborn and belongs to the family-owned Friedhelm Loh Group.
Seven Star LLC is an independent supplier in Muscat. We list Rittal enclosures, cooling units and power distribution products for panel builders and maintenance teams in Oman and the GCC.
Rittal company profile
| Founded | 1961, Rittershausen (Dietzhölztal), Germany, by Rudolf Loh |
|---|---|
| Headquarters | Herborn, Hesse, Germany |
| Ownership | Friedhelm Loh Group (Loh family); sister companies include Eplan and Cideon |
| Idea | Standard enclosures in series production, available from stock |
| Product families | VX25 and AX/KX enclosures, TS 8 baying systems, Blue e+ cooling units and fan-and-filter units, RiLine busbar systems, IT racks and data centre modules |
Milestones
- 1961: Rudolf Loh founds the company and launches the first standard enclosure.
- 1969: The company takes the Rittal name, according to Rittal.
- 2021: Rittal marks 60 years.
Rittal product series
Enclosures include the TS 8 free-standing bayable system, AE compact enclosures such as the AE 1380.500 and AE 1034.500, and the CS outdoor wall-mounted enclosure. For hazardous areas there are the KEL 9404.600 stainless steel and AX 9206.100 plastic Ex enclosures. Power distribution is covered by the VX25 Ri4Power switchgear system and its 185 mm busbar system.
Climate control includes Blue e+ wall-mounted cooling units, the TopTherm Blue e SK 3273.500 roof-mounted unit and the LCP Inline CW liquid cooling package for IT racks.
Where Rittal products are used
Machine and process control panels, motor control and power distribution switchboards, outdoor telecom and utility cabinets, junction boxes in hazardous areas and IT racks. In the Gulf, cabinet cooling is often the deciding factor for reliable electronics.
Rittal products we list
Ordering Rittal products: what we need
Rittal parts are ordered by a seven-digit model number such as 9404.600. Send that number, or the width, height and depth, material, protection category and door arrangement. For cooling units add the cooling output, rated voltage and mounting cut-out of the unit being replaced; for Ex enclosures, the zone and marking required.
Facts checked against Rittal's own company pages and Friedhelm Loh Group material, October 2026.
Browse Rittal products by category: Automation Accessories, Switchgear, Enclosures & Distribution, Enclosure Climate Control.
FAQ
Questions about the Rittal SK 3126.100 Wall-Mounted Air/Air Heat
Answers from our engineering team on installation, compatibility and integration.
01How is the output of SK 3126.100 specified?
It is given as a specific thermal output of 17.5 W per kelvin of temperature difference between the enclosure air and the ambient air. At a 10 K difference this removes about 175 W.
02When can SK 3126.100 not cool an enclosure?
Whenever the ambient air is as warm as the permitted internal temperature, because the unit only transfers heat from warmer inside air to cooler outside air. In that case a compressor or water unit is needed.
03What protection does SK 3126.100 offer?
The two air circuits are separate, with IP 54 on the internal side and IP 34 on the external side, so ambient dust and moisture do not enter the enclosure.
04What control and signalling does SK 3126.100 have?
It has electronic control with a digital display, factory set to +35 °C, and a floating fault contact for overtemperature that can be wired to a plant alarm system.
05Does Seven Star LLC provide a document for SK 3126.100?
Yes, a technical details document is attached on this page. Send the part number SK 3126.100 and the quantity to Seven Star LLC for availability and lead time in Oman and the GCC.


















Reviews