- Automation & ControlView all 2,466 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Motor Soft Starters
- Encoders
- Safety Switches & Guard Locking
- HMI Displays
- Pneumatic Cylinders
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Rittal
Rittal SK 3305.500 Blue e Wall-Mounted Cooling Unit 1.6 kW
Description
SK 3305.500 wall-mounted cooling unit decoded
The Rittal SK 3305.500 is a wall-mounted cooling unit of the Blue e (TopTherm wall-mounted) range, 400 x 950 x 260 mm. It shares the 400 x 950 x 260 mm housing of the 1.1 kW unit but carries a stronger refrigeration circuit rated 1.6 kW. Seven Star LLC supplies SK 3305.500 in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.
The table below decodes the main identifiers of SK 3305.500 so that it can be matched to a cabinet drawing.
| Element | Value | Meaning |
|---|---|---|
| SK | Product family prefix | Climate control accessory for enclosures |
| SK 3305.500 | Article number | Fixes size, output class and voltage in the manufacturer catalogue |
| 1.6 kW cooling output at 50 Hz (L35 L35) | Duty point | Headline output or air figure used to pick this unit |
| 230 V, 1~, 50/60 Hz | Supply | Single-phase supply usable at 50 Hz and 60 Hz |
| 400 x 950 x 260 mm | Outer dimensions | Width x height x depth of the unit |
SK 3305.500 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Rittal / SK 3305.500 |
| Cooling output L35 L35 (DIN EN 14511) | 1.6 kW at 50 Hz, 1.73 kW at 60 Hz |
| Rated operating voltage | 230 V, 1~, 50/60 Hz |
| Rated current (max.) | 6.1 A at 50 Hz, 6.5 A at 60 Hz |
| Start-up current (max.) | 12 A at 50 Hz, 14 A at 60 Hz |
| Power consumption (L35 L35) | 0.87 kW at 50 Hz, 0.96 kW at 60 Hz |
| Energy efficiency ratio (EER) | 1.83 (50 Hz), 1.79 (60 Hz) |
| Air throughput (unimpeded) | External circuit 805 m³/h, internal circuit 585 m³/h |
| Refrigerant | R-513A, 0.61 kg (GWP 631, 0.38 t CO₂ equivalent) |
| Condensate evaporation | Integral electric evaporator |
| Temperature control | e-Comfort controller, factory setting +35 °C |
| Operating temperature range | 10 °C to 55 °C |
| Setting range | 20 °C to 55 °C |
| Storage temperature range | -40 °C to +70 °C |
| IP rating (IEC 60529) | External circuit IP 34, internal circuit IP 54 |
| NEMA / UL type | UL Type 12 |
| Permissible operating pressure (max.) | 28 bar |
| Pre-fuse | 16 A miniature circuit-breaker / fuse |
| Dimensions (W x H x D) | 400 x 950 x 260 mm |
| Net weight | 39.75 kg |
| Approvals listed on the article page | KC Korea, UL + C-UL (listed), UL + C-UL FTTA |
Values come from the manufacturer article page for SK 3305.500. Cooling data are catalogue test points; real performance depends on the temperature difference, the condition of the filters and the airflow around the unit.
How the SK 3305.500 wall-mounted cooling unit works
The unit contains a closed refrigeration circuit with compressor, evaporator, condenser and expansion device, using refrigerant R-513A. Warm air from the enclosure is drawn across the evaporator and returned cooler, while the condenser rejects the heat to the surrounding air. The two air circuits stay separate, which is why the internal side is rated IP 54 and the external side IP 34. The condenser has a hydrophobic coating that helps it shed dirt, and an e-Comfort controller holds the set temperature, factory set to +35 °C.
Sizing SK 3305.500 for an enclosure
A simple sizing rule is: required cooling output = dissipated power inside the enclosure + heat gain through the shell when the surrounding air is warmer than the setpoint. For painted sheet steel a coefficient of about 5.5 W per m² and kelvin is often used. Example: an enclosure with 4 m² of free surface, 1300 W of internal losses, a setpoint of 35 °C and 45 °C ambient needs about 1520 W, which sits below the 1600 W catalogue rating of SK 3305.500. Cooling output falls as ambient temperature rises, so at hot sites also read the L35 L50 point in the datasheet before you commit.
Selection and ordering checklist for SK 3305.500
- Total dissipated power of all equipment in the enclosure, in watts, plus the heat gain from sun and hot walls.
- Maximum permitted internal temperature of the most sensitive device, and the setpoint you want.
- Ambient temperature range on site, including summer peaks in Oman and the GCC.
- Cut-out and clearance for a 400 x 950 x 260 mm unit, with free air in front of the external circuit.
- Supply: 230 V, 1~, 50/60 Hz, pre-fuse 16 A.
- Where condensate will go: the unit has an integral electric evaporator.
Installation, commissioning and maintenance of SK 3305.500
- Mount the unit in the cut-out with the supplied template and gasket, keeping the airflow free on both circuits.
- Run the unit only after the enclosure door is closed; an open door floods the evaporator with warm humid air.
- Clean the condenser and external filter at intervals suited to the dust level; in sandy sites this can be monthly.
- Check the condensate path and the controller alarms during service.
- Keep the refrigerant circuit untouched; leave refrigerant work to a qualified refrigeration technician.
Apply local rules for electrical connection, and record the setpoint and alarm settings used at commissioning.
Typical applications of SK 3305.500 in Oman and the GCC
Used on larger drive cabinets, compressor and pump control cabinets and multi-section control panels where the dissipated power is above one kilowatt. Because the housing size is the same as the 1.1 kW unit, an existing cut-out can often be reused when a panel is upgraded, subject to checking the 16 A pre-fuse and the supply.
Conditions in the Gulf are hard on enclosure electronics: summer ambient temperatures regularly exceed 45 °C, humidity near the coast leads to condensation when panels cool at night, and fine dust blocks filters quickly. Oil and gas, power, desalination and petrochemical sites therefore treat climate control as part of the panel design rather than an add-on.
Blue e units compared against SK 3305.500
The table places SK 3305.500 next to the other Blue e units described on this site. The output figures are at 50 Hz for 35 °C inside and outside (L35 L35).
| Article | Design | Output (L35 L35, 50 Hz) | W x H x D (mm) |
|---|---|---|---|
| SK 3303.500 | Wall-mounted | 0.52 kW | 280 x 550 x 210 |
| SK 3304.500 | Wall-mounted | 1.1 kW | 400 x 950 x 260 |
| SK 3305.500 (this item) | Wall-mounted | 1.6 kW | 400 x 950 x 260 |
| SK 3359.500 | Roof-mounted | 0.77 kW | 597 x 417 x 380 |
Information to send with an RFQ for SK 3305.500
To quote correctly we need a few details:
- Exact article number SK 3305.500 and the quantity.
- Enclosure size, material and surface area, and the room or site where it stands.
- Total heat loss in watts and the highest internal temperature allowed.
- Ambient temperature range, dust and humidity conditions.
- Supply voltage, frequency and available pre-fuse.
- Mounting position, cut-out availability and any condensate or water connection constraints.
- Delivery location in Oman or the GCC and the date needed.
Documents and quotation
A technical details document for SK 3305.500 is attached on this page, giving dimensions and installation drawings; check the article number printed on it.
Send the part number SK 3305.500 and the quantity to Seven Star LLC and we will confirm availability, lead time and delivery to your site in Oman or the GCC.
Other Models in the Rittal Blue E Cooling Range
Seven Star LLC supplies models from the Rittal Blue E Cooling range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Rittal SK 3303.500 Blue e Wall-Mounted Cooling Unit 0.52 kW | Enclosure Climate Control | View details |
| Rittal SK 3304.500 Blue e Wall-Mounted Cooling Unit 1.1 kW | Enclosure Climate Control | View details |
| Rittal SK 3305.500 Blue e Wall-Mounted Cooling Unit 1.6 kW | Enclosure Climate Control | You are viewing this model |
Datasheets & Documents
- Datasheet Rittal SK 3305.500 Technical Details Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Rittal is a German manufacturer of enclosures, power distribution, climate control and IT infrastructure, founded in 1961 by Rudolf Loh in Rittershausen, Hesse, as Rudolf Loh Elektrogerätebau. In its first year it launched the first standard enclosure, built in series and available from stock instead of made to order. Rittal is headquartered in Herborn and belongs to the family-owned Friedhelm Loh Group.
Seven Star LLC is an independent supplier in Muscat. We list Rittal enclosures, cooling units and power distribution products for panel builders and maintenance teams in Oman and the GCC.
Rittal company profile
| Founded | 1961, Rittershausen (Dietzhölztal), Germany, by Rudolf Loh |
|---|---|
| Headquarters | Herborn, Hesse, Germany |
| Ownership | Friedhelm Loh Group (Loh family); sister companies include Eplan and Cideon |
| Idea | Standard enclosures in series production, available from stock |
| Product families | VX25 and AX/KX enclosures, TS 8 baying systems, Blue e+ cooling units and fan-and-filter units, RiLine busbar systems, IT racks and data centre modules |
Milestones
- 1961: Rudolf Loh founds the company and launches the first standard enclosure.
- 1969: The company takes the Rittal name, according to Rittal.
- 2021: Rittal marks 60 years.
Rittal product series
Enclosures include the TS 8 free-standing bayable system, AE compact enclosures such as the AE 1380.500 and AE 1034.500, and the CS outdoor wall-mounted enclosure. For hazardous areas there are the KEL 9404.600 stainless steel and AX 9206.100 plastic Ex enclosures. Power distribution is covered by the VX25 Ri4Power switchgear system and its 185 mm busbar system.
Climate control includes Blue e+ wall-mounted cooling units, the TopTherm Blue e SK 3273.500 roof-mounted unit and the LCP Inline CW liquid cooling package for IT racks.
Where Rittal products are used
Machine and process control panels, motor control and power distribution switchboards, outdoor telecom and utility cabinets, junction boxes in hazardous areas and IT racks. In the Gulf, cabinet cooling is often the deciding factor for reliable electronics.
Rittal products we list
Ordering Rittal products: what we need
Rittal parts are ordered by a seven-digit model number such as 9404.600. Send that number, or the width, height and depth, material, protection category and door arrangement. For cooling units add the cooling output, rated voltage and mounting cut-out of the unit being replaced; for Ex enclosures, the zone and marking required.
Facts checked against Rittal's own company pages and Friedhelm Loh Group material, October 2026.
Browse Rittal products by category: Automation Accessories, Switchgear, Enclosures & Distribution, Enclosure Climate Control.
FAQ
Questions about the Rittal SK 3305.500 Blue e Wall-Mounted Cooling Unit
Answers from our engineering team on installation, compatibility and integration.
01What is the cooling output of SK 3305.500?
At 35 °C inside and outside (L35 L35) the page lists 1.6 kW at 50 Hz and 1.73 kW at 60 Hz under DIN EN 14511. Output falls as ambient temperature rises, so check the datasheet for hot-site duty.
02What supply does SK 3305.500 need?
It runs on 230 V, 1~, 50/60 Hz. The page lists a maximum current of 6.1 A at 50 Hz, 6.5 A at 60 Hz and a pre-fuse of 16 A.
03Which refrigerant does SK 3305.500 use?
The unit uses R-513A, 0.61 kg (GWP 631, 0.38 t CO₂ equivalent). Refrigerant work must be done by qualified technicians; the owner only needs to keep the condenser and filters clean.
04What protection and temperature range does SK 3305.500 have?
The page lists IP 54 for the internal circuit and IP 34 for the external circuit, with an operating range of 10 °C to 55 °C and a setting range of 20 °C to 55 °C.
05Does Seven Star LLC provide a document for SK 3305.500?
Yes, a technical details document is attached on this page. Send the part number SK 3305.500 and the quantity to Seven Star LLC for availability and lead time in Oman and the GCC.


















Reviews