Brand:

Rittal SK 3209.500 Roof-Mounted Air/Water Heat Exchanger 2.5 kW

Description

SK 3209.500 air/water heat exchanger decoded

The Rittal SK 3209.500 is a air/water heat exchanger of the TopTherm air/water heat exchanger range, 597 x 417 x 475 mm. Instead of a refrigeration circuit it uses a plant chilled-water or cooling-water loop, so it works in surroundings up to +70 °C where a compressor unit would struggle. Seven Star LLC supplies SK 3209.500 in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.

The table below decodes the main identifiers of SK 3209.500 so that it can be matched to a cabinet drawing.

Element Value Meaning
SK Product family prefix Climate control accessory for enclosures
SK 3209.500 Article number Fixes size, output class and voltage in the manufacturer catalogue
2.5 kW at L35 W10, 400 l/h Duty point Headline output or air figure used to pick this unit
230 V, 1~, 50/60 Hz Supply Single-phase supply usable at 50 Hz and 60 Hz
597 x 417 x 475 mm Outer dimensions Width x height x depth of the unit

SK 3209.500 technical specifications

Parameter Specification
Manufacturer / part number Rittal / SK 3209.500
Cooling output 2.5 kW (L35 W10, water flow 400 l/h)
Rated operating voltage 230 V, 1~, 50/60 Hz
Power consumption 95 W at 50 Hz, 110 W at 60 Hz
Rated current (max.) 0.4 A at 50 Hz, 0.48 A at 60 Hz
Cooling medium Water, see manufacturer specification for quality
Water inlet temperature 1 °C to 30 °C
Water connections ½" connector sleeve, G ⅓" external thread
Permissible operating pressure (max.) 10 bar
Temperature control e-Comfort controller, factory setting +35 °C, setting range 20 °C to 55 °C
Operating temperature range 1 °C to 70 °C
Duty cycle 100 %
Electrical connection Plug-in terminal strip
Dimensions (W x H x D) 597 x 417 x 475 mm
IP rating (IEC 60529) IP 55 (IP 65 noted as available on request)
Pre-fuse 4 A miniature circuit-breaker / fuse
Net / gross weight 32.3 kg / 34 kg
Approvals listed on the article page CSA, UR + C-UR (recognized)

Values come from the manufacturer article page for SK 3209.500. Cooling data are catalogue test points; real performance depends on the temperature difference, the condition of the filters and the airflow around the unit.

How the SK 3209.500 air/water heat exchanger works

An air/water heat exchanger has no compressor. Warm air from the enclosure is blown across a water-cooled coil and returned cool, while water from the plant loop carries the heat away. The cooling power therefore depends on water inlet temperature and flow, and it is rated here at a 10 °C inlet and 400 litres per hour. Fans and the e-Comfort controller are the only electrical load, which is why the connected power is as low as 95 W.

Sizing SK 3209.500 for an enclosure

For a water-cooled unit the same heat balance applies, but the limit is the cooling water. Example: an enclosure with 3 m² of surface and 1800 W of internal losses in 40 °C ambient at a +35 °C setpoint adds about 82 W of heat gain, so roughly 1882 W must be removed; the rated 2.5 kW is reached with 10 °C inlet water at 400 l/h, so warmer water or lower flow reduces the margin.

Selection and ordering checklist for SK 3209.500

  • Total dissipated power of all equipment in the enclosure, in watts, plus the heat gain from sun and hot walls.
  • Maximum permitted internal temperature of the most sensitive device, and the setpoint you want.
  • Ambient temperature range on site, including summer peaks in Oman and the GCC.
  • Chilled or cooling water availability, temperature (1 °C to 30 °C inlet) and pressure (max. 10 bar).
  • Water quality and filtration, and the connection fittings (½" sleeve, G ⅓" thread).
  • Condensation risk when the water is colder than the room air dew point.

Installation, commissioning and maintenance of SK 3209.500

  • Connect the water lines with flexible hoses and shut-off valves so that the unit can be removed without draining the plant loop.
  • Vent the water side at commissioning and check for leaks at every joint.
  • Use filtered water that meets the manufacturer specification; deposits reduce cooling output.
  • Inspect the fans and the coil surface regularly.
  • Check that cooling water is available before the enclosure is loaded.

Apply local rules for electrical connection, and record the setpoint and alarm settings used at commissioning.

Typical applications of SK 3209.500 in Oman and the GCC

It fits plants with a cooling water network: power stations, desalination and petrochemical sites, steel and cement plants, where ambient air carries dust, oil mist or heat that would overload a compressor unit. The water circuit takes the heat away without dumping warm air into the room.

Conditions in the Gulf are hard on enclosure electronics: summer ambient temperatures regularly exceed 45 °C, humidity near the coast leads to condensation when panels cool at night, and fine dust blocks filters quickly. Oil and gas, power, desalination and petrochemical sites therefore treat climate control as part of the panel design rather than an add-on.

Cooling principles compared against SK 3209.500

Choosing between heat exchangers and compressor units depends on ambient temperature, water availability and dust. The table compares SK 3209.500 with other cooling principles described on this site.

Article Principle Headline figure W x H x D (mm)
SK 3126.100 Air/air heat exchanger 17.5 W/K 280 x 550 x 150
SK 3209.500 (this item) Air/water heat exchanger 2.5 kW (L35 W10) 597 x 417 x 475
SK 3359.500 Roof-mounted compressor unit 0.77 kW (L35 L35) 597 x 417 x 380

Information to send with an RFQ for SK 3209.500

To quote correctly we need a few details:

  • Exact article number SK 3209.500 and the quantity.
  • Enclosure size, material and surface area, and the room or site where it stands.
  • Total heat loss in watts and the highest internal temperature allowed.
  • Ambient temperature range, dust and humidity conditions.
  • Supply voltage, frequency and available pre-fuse.
  • Mounting position, cut-out availability and any condensate or water connection constraints.
  • Delivery location in Oman or the GCC and the date needed.

Documents and quotation

A technical details document for SK 3209.500 is attached on this page, giving dimensions and installation drawings; check the article number printed on it.

Send the part number SK 3209.500 and the quantity to Seven Star LLC and we will confirm availability, lead time and delivery to your site in Oman or the GCC.

Datasheets & Documents
  • PDF Datasheet Rittal SK 3209.500 Technical Details Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Rittal is a German manufacturer of enclosures, power distribution, climate control and IT infrastructure, founded in 1961 by Rudolf Loh in Rittershausen, Hesse, as Rudolf Loh Elektrogerätebau. In its first year it launched the first standard enclosure, built in series and available from stock instead of made to order. Rittal is headquartered in Herborn and belongs to the family-owned Friedhelm Loh Group.

Seven Star LLC is an independent supplier in Muscat. We list Rittal enclosures, cooling units and power distribution products for panel builders and maintenance teams in Oman and the GCC.

Rittal company profile

Founded 1961, Rittershausen (Dietzhölztal), Germany, by Rudolf Loh
Headquarters Herborn, Hesse, Germany
Ownership Friedhelm Loh Group (Loh family); sister companies include Eplan and Cideon
Idea Standard enclosures in series production, available from stock
Product families VX25 and AX/KX enclosures, TS 8 baying systems, Blue e+ cooling units and fan-and-filter units, RiLine busbar systems, IT racks and data centre modules

Milestones

  • 1961: Rudolf Loh founds the company and launches the first standard enclosure.
  • 1969: The company takes the Rittal name, according to Rittal.
  • 2021: Rittal marks 60 years.

Rittal product series

Enclosures include the TS 8 free-standing bayable system, AE compact enclosures such as the AE 1380.500 and AE 1034.500, and the CS outdoor wall-mounted enclosure. For hazardous areas there are the KEL 9404.600 stainless steel and AX 9206.100 plastic Ex enclosures. Power distribution is covered by the VX25 Ri4Power switchgear system and its 185 mm busbar system.

Climate control includes Blue e+ wall-mounted cooling units, the TopTherm Blue e SK 3273.500 roof-mounted unit and the LCP Inline CW liquid cooling package for IT racks.

Where Rittal products are used

Machine and process control panels, motor control and power distribution switchboards, outdoor telecom and utility cabinets, junction boxes in hazardous areas and IT racks. In the Gulf, cabinet cooling is often the deciding factor for reliable electronics.

Rittal products we list

Family Examples
Automation Accessories AE 1034.500 Compact Enclosure 300 x 400…, AE 1380.500 Compact Enclosure 380 x 380…, AX 9206.100 Ex Plastic Enclosure 600 x 6…, CS 9791.015 Outdoor Wall-Mounted Enclosure, KEL 9404.600 Ex Stainless Steel Enclosur…, VX25 Ri4Power 185 mm Busbar System, VX25 Ri4Power Switchgear and Power Distr…
Enclosure Climate Control Blue e+ Wall-Mounted Enclosure Cooling U…
Cooling SK 3273.500 TopTherm Blue e Roof-Mounted…
Switchgear, Enclosures & Distribution TS 8 Free-Standing Enclosure System

Ordering Rittal products: what we need

Rittal parts are ordered by a seven-digit model number such as 9404.600. Send that number, or the width, height and depth, material, protection category and door arrangement. For cooling units add the cooling output, rated voltage and mounting cut-out of the unit being replaced; for Ex enclosures, the zone and marking required.

Facts checked against Rittal's own company pages and Friedhelm Loh Group material, October 2026.

FAQ

Questions about the Rittal SK 3209.500 Roof-Mounted Air/Water Heat

Answers from our engineering team on installation, compatibility and integration.

01What does SK 3209.500 need to work?
It needs a water supply between 1 °C and 30 °C at up to 10 bar and a 230 V supply. The rated 2.5 kW output applies to 10 °C inlet water at 400 l/h.
02Why choose an air/water exchanger such as SK 3209.500?
It has no compressor, uses only 95 to 110 W of electrical power and is rated for ambient temperatures up to 70 °C, so it suits hot or dirty areas with a cooling water loop.
03What water connections does SK 3209.500 have?
The article page lists a ½" connector sleeve and a G ⅓" external thread. Use flexible hoses and shut-off valves so that the unit can be removed without draining the loop.
04What protection class does SK 3209.500 have?
The listed rating is IP 55, and IP 65 is noted as available on request. Keep the enclosure cut-out sealed to maintain that class.
05Does Seven Star LLC provide a document for SK 3209.500?
Yes, a technical details document is attached on this page. Send the part number SK 3209.500 and the quantity to Seven Star LLC for availability and lead time in Oman and the GCC.