Lovato 31RC60415 Earth Leakage Relay 60 mm Toroid, Type A

Description

Lovato 31RC60415 earth leakage relay, 60 mm toroid, type A

The Lovato 31RC60415 is a compact residual-current (earth leakage) monitoring relay with a built-in toroidal transformer of 60 mm diameter and one adjustable operating threshold. It detects residual currents of type A and drives a single changeover relay. Seven Star LLC supplies the 31RC60415 in Oman and the GCC as an independent supplier in Muscat.

The code is the catalogue reference: RC identifies the earth leakage relay with built-in toroid, 60 the toroid diameter in millimetres and 415 the top of the auxiliary supply range (110 to 125 V AC/DC, 220 to 240 V AC or 380 to 415 V AC). Siblings with other toroid sizes carry other numbers, such as the 31RC35415 for a smaller toroid.

31RC60415 technical specifications

Parameter Specification
Manufacturer / part number Lovato / 31RC60415
Function Earth leakage (residual current) relay, one threshold
Residual characteristic Type A
Toroid Built in, 60 mm diameter
Trip current IΔn 0.025 to 0.25 A (x0.1), 0.25 to 2.5 A (x1), 2.5 to 25 A (x10)
Trip delay 0.02 to 0.5 s (x1); 0.2 to 5 s (x10)
Setting Multipliers by DIP switches
Reset Automatic or manual, configurable
Auxiliary supply 110 to 125 V AC/DC; 220 to 240 V AC; 380 to 415 V AC
Output 1 changeover contact, 5 A 250 V
Relay state Normally de-energised
Consumption 3 VA maximum
Indication Green ON LED, red TRIP LED, test button
Insulation 2.5 kV for 60 s
Life 50 million mechanical; 300,000 electrical
Temperature -10 to +60 °C
Housing Polycarbonate; DIN rail; 100 x 110 x 70 mm; 485 g

How the 31RC60415 detects earth leakage

All phase conductors and the neutral of the monitored circuit pass through the toroid. In a healthy circuit the vector sum of currents is zero. When some current returns through earth, through a person, a damaged cable or a failing insulation, the sum is no longer zero and the toroid produces a signal proportional to the residual current. The relay compares it with the setting and trips its contact after the chosen delay.

A wide setting window is available: from 25 mA to 25 A, divided into three decades through the multiplier switches. The time delay allows coordination between upstream and downstream devices, so that the device nearest to the fault trips first and the rest of the plant stays supplied.

Using the 31RC60415 in a protection scheme

The relay itself only provides a contact. This contact must trip a breaker through its shunt coil or undervoltage release, or open a contactor. Because the output relay is normally de-energised, the supply is needed for a trip to be effective, and a loss of supply must be handled in the design, for example by a fail-safe wiring or a separate alarm. The device is not a replacement for personal protection where local regulations require a specific residual current device at 30 mA.

31RC60415 selection checklist

  • Conductor bundle must pass through a 60 mm opening
  • Residual waveform of type A matches the loads
  • Trip current and delay needed for coordination
  • Auxiliary supply of 110-125 V, 220-240 V or 380-415 V
  • Breaker or contactor with a coil to receive the trip
  • Manual or automatic reset policy
  • Panel space of 100 x 110 x 70 mm

Installing and testing the 31RC60415

Fit on a 35 mm rail close to the cables, pass all live conductors including the neutral but not the earth conductor through the toroid, and keep cables centred where possible. Select the supply voltage on the correct terminals; connecting the wrong one will damage the unit.

Use the test button during commissioning and periodically in service to confirm that the contact operates. Injecting a known current through a test wire is a more complete method. Record the settings in the maintenance log.

Typical 31RC60415 applications in Oman and the GCC

Typical applications are monitoring of feeders to pumps, heaters, lighting and cable networks in industrial plants, where insulation damage from heat, dust and humidity can create leakage before a full fault. In IT or TN systems the monitoring allows planned maintenance instead of unexpected outage.

31RC relays in the catalogue

Part Toroid Note
31RC35415 35 mm Smaller conductor bundle
31RC60415 60 mm This part
31RC80415 80 mm Larger bundle
31RC110415 110 mm Large cables

A design example shows the logic. A heating cable feeder of 63 A passes through the 60 mm toroid with all four conductors; the relay is set at 0.3 A with a delay of 0.1 s to give an alarm and trip before the damage grows. A downstream relay on a branch is set at 0.1 A with a shorter delay, so branch faults clear locally. Such grading needs the settings of each relay in a table, kept with the single-line diagram. Remember that large capacitive leakage in long cable runs or filters can create nuisance trips, which is solved by raising the threshold rather than removing the relay.

Information to send with an RFQ for the 31RC60415

  • Part number 31RC60415 and quantity
  • Cable size and number of conductors
  • Trip current and delay wanted
  • Supply voltage
  • Breaker or contactor to be tripped
  • Delivery location

Site conditions in Oman for the 31RC60415

Control cabinets in Gulf plants often run hot, because many sit in outdoor kiosks or in rooms where air conditioning is not always reliable. Before you finalise the 31RC60415, check the permitted ambient range and any derating stated by the manufacturer against the real temperature inside your panel, and leave the recommended spacing around the device so that heat can escape. Long cable runs between the field and the marshalling cabinet are common on large sites, so confirm the signal types, wiring limits and earthing arrangement early in the design.

It also helps to standardise on a small number of part numbers across a project. Keeping a few spare 31RC60415 units on site in Oman shortens recovery time after a fault, and documenting configuration settings makes replacement faster for the maintenance team.

Documents and quotation

Send the part number 31RC60415 and we will confirm the documents available for it, such as the technical data sheet, wiring diagram and instruction sheet, together with availability and lead time.

Seven Star LLC is an independent supplier in Muscat and is not an official channel of the manufacturer. Share the quantity, delivery location and project reference with the request and we will answer with a formal quotation.

Datasheets & Documents
  • PDF Datasheet Lovato 31RC60415 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.

Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.

Lovato Electric at a glance

Established 1922, Bergamo, Italy
Headquarters Gorle (Bergamo), Italy
Ownership Private, family-run for four generations
Product families Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs

Lovato products we list

Family Models Typical use
Contactors BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing Switching motors, heaters, lighting and capacitor banks
Motor protection and starters SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay Short-circuit and overload protection and direct starting of motors
Soft starters ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 Reducing starting current and mechanical shock on pumps, fans and compressors
Variable speed drives VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 Speed control of pumps, fans and conveyors to save energy
Power management and control DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC Power factor correction, mains/generator changeover and energy monitoring

Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.

Where Lovato products are used

In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.

Ordering Lovato products: what we need

Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.

Facts checked against Lovato Electric company profile brochures, October 2026.

FAQ

Questions about the Lovato 31RC60415 Earth Leakage Relay 60 mm Toroid,

Answers from our engineering team on installation, compatibility and integration.

01What is the toroid size of the 31RC60415?
The toroidal transformer is built in with a diameter of 60 mm.
02What trip currents can be set?
From 0.025 A to 25 A in three ranges selected with multiplier switches.
03What delay can be set?
From 0.02 to 0.5 s with the x1 multiplier and 0.2 to 5 s with x10.
04What auxiliary supplies are possible?
110 to 125 V AC/DC, 220 to 240 V AC or 380 to 415 V AC.
05What output does it have?
One changeover contact rated 5 A at 250 V, normally de-energised.