Lovato LRD20RA240 Micro PLC 100-240 V AC, 12 In, 8 Relay

Description

Lovato LRD20RA240 micro PLC, 100-240 V AC, 12 inputs and 8 relays

The Lovato LRD20RA240 is a micro PLC base module supplied from 100 to 240 V AC, with twelve AC digital inputs and eight relay outputs and a 4 x 16 character LCD. It can be extended up to 44 I/O points using LRE modules. Seven Star LLC supplies the LRD20RA240 in Oman and the GCC as an independent supplier in Muscat.

The number 20 refers to the 12 plus 8 on-board points, R to relay outputs, A to AC and 240 to the 100 to 240 V supply class. Compared with the LRD12RA024, this part runs straight from mains without a control transformer, which suits small machines and building plant where only line voltage is available.

LRD20RA240 technical specifications

Parameter Specification
Manufacturer / part number Lovato / LRD20RA240
Supply 100 to 240 V AC (85 to 265 V); 47 to 63 Hz
Current / power 100 mA average; 7.5 W maximum
Digital inputs 12, rated 100 to 240 V AC
Input threshold State 1 above 79 V AC
Response times 50/45 ms at 120 V; 22/18 ms on and 90/85 ms off at 240 V
Outputs 8 relay
Maximum I/O 20 on board; up to 44 with LRE modules
Display LCD, 4 x 16 characters
Terminals Screw; 0.14 to 2.5 mm²; 0.6 Nm
Temperature -20 to +55 °C
Mounting 35 mm DIN rail or M4 screws
Protection IP20
Dimensions 126 x 106 x 59.6 mm
Weight 367 g

Mains-voltage inputs on the LRD20RA240

The twelve inputs accept line voltage directly, with state 1 above 79 V AC. That allows push buttons, limit switches and auxiliary contacts powered from the same mains supply to be connected without relays. The response time depends on voltage: at 240 V the turn-on is about 22 ms and the turn-off about 90 ms, a difference that arises from the nature of AC signals and affects timing-critical logic.

Caution is needed when signals come from different phases. Check the terminal diagram in the manual for the common-terminal grouping of the inputs before wiring signals taken from a three-phase machine.

Programming and use of the LRD20RA240

A program is written on a PC using Lovato software and downloaded through the programming interface; run-time values and parameters can be edited on the front display. With 8 relay outputs the module can drive contactor coils, solenoid valves and indicator lamps directly, within the contact ratings in the manual. Use interposing relays for heavy or inductive loads.

LRD20RA240 selection checklist

  • Mains supply of 100 to 240 V AC
  • Twelve AC inputs and eight relay outputs
  • Relay load and contact rating
  • Need for expansion to 44 points
  • Input signal voltage matching the supply
  • Panel space of 126 x 106 mm
  • Programming software and cable

Installing and commissioning the LRD20RA240

Protect the supply with a small fuse or breaker, mount on a DIN rail, and wire inputs and outputs using conductors up to 2.5 mm². Separate signal and power wiring where possible. Test each output with the load disconnected using the forced output function of the software, if available, then enable the program.

Add surge suppression across contactor coils and solenoids. After commissioning, store the program and write down the I/O assignment for the panel documents.

Typical LRD20RA240 applications in Oman and the GCC

Typical uses are pump alternation and level control, ventilation and lighting sequences, simple machine cycles and gate or door logic. A mains-supplied PLC saves a transformer, making retrofit work in older panels easier. Check that panel temperature in summer remains below 55 °C.

LRD micro PLCs in this range

Part Supply I/O
LRD12RA024 24 V AC 8 in, 4 relay out
LRD20RA240 100-240 V AC 12 in, 8 relay out
LRD20RD024 24 V DC 20 on board
LRD10RA240 100-240 V AC Smaller module

Practical details matter for a long service life. Keep the supply and the inputs on the same protected circuit so that a fault in one does not leave the program running with false inputs. Allow the controller a few seconds after power return before outputs are enabled, which prevents a pump from restarting at the same time as all others after a mains outage. Use the display and the program to build a simple fault list, so that an operator can see which input stopped the sequence without a laptop. Spare relay contacts should be reserved for alarm repeating to a central station.

Compare the module with the 24 V AC version when choosing. The LRD20RA240 gives more I/O on board and needs no transformer, but its inputs sit at mains potential, so any wiring fault on a sensor line can bring line voltage into the panel door area. Use proper cable segregation, label input terminals clearly and apply the shutdown and lock-out procedures of the site before working inside the panel. When a machine needs more than 20 points, the expansion path to 44 points avoids buying a larger controller; each expansion module simply clips to the side of the base module and shares the supply.

Information to send with an RFQ for the LRD20RA240

  • Part number LRD20RA240 and quantity
  • Supply voltage
  • I/O count needed
  • Load types on relays
  • Expansion modules
  • Delivery location

Site conditions in Oman for the LRD20RA240

Control cabinets in Gulf plants often run hot, because many sit in outdoor kiosks or in rooms where air conditioning is not always reliable. Before you finalise the LRD20RA240, check the permitted ambient range and any derating stated by the manufacturer against the real temperature inside your panel, and leave the recommended spacing around the device so that heat can escape. Long cable runs between the field and the marshalling cabinet are common on large sites, so confirm the signal types, wiring limits and earthing arrangement early in the design.

It also helps to standardise on a small number of part numbers across a project. Keeping a few spare LRD20RA240 units on site in Oman shortens recovery time after a fault, and documenting configuration settings makes replacement faster for the maintenance team.

Documents and quotation

Send the part number LRD20RA240 and we will confirm the documents available for it, such as the technical data sheet, wiring diagram and instruction sheet, together with availability and lead time.

Seven Star LLC is an independent supplier in Muscat and is not an official channel of the manufacturer. Share the quantity, delivery location and project reference with the request and we will answer with a formal quotation.

Other Models in the Lovato Lrd Plc Range

Seven Star LLC supplies models from the Lovato Lrd Plc range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Lovato LRD12RA024 Micro PLC 24 V AC, 8 In, 4 Relay OutControllers & Data AcquisitionView details
Lovato LRD20RA240 Micro PLC 100-240 V AC, 12 In, 8 RelayControllers & Data AcquisitionYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Lovato LRD20RA240 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.

Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.

Lovato Electric at a glance

Established 1922, Bergamo, Italy
Headquarters Gorle (Bergamo), Italy
Ownership Private, family-run for four generations
Product families Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs

Lovato products we list

Family Models Typical use
Contactors BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing Switching motors, heaters, lighting and capacitor banks
Motor protection and starters SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay Short-circuit and overload protection and direct starting of motors
Soft starters ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 Reducing starting current and mechanical shock on pumps, fans and compressors
Variable speed drives VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 Speed control of pumps, fans and conveyors to save energy
Power management and control DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC Power factor correction, mains/generator changeover and energy monitoring

Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.

Where Lovato products are used

In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.

Ordering Lovato products: what we need

Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.

Facts checked against Lovato Electric company profile brochures, October 2026.

FAQ

Questions about the Lovato LRD20RA240 Micro PLC 100-240 V AC, 12 In, 8

Answers from our engineering team on installation, compatibility and integration.

01What supply does the LRD20RA240 use?
100 to 240 V AC with an operating range of 85 to 265 V and 47 to 63 Hz.
02How many I/O points does it have?
Twelve digital inputs and eight relay outputs, extendable up to 44 points with LRE modules.
03What is the input threshold?
State 1 is above 79 V AC.
04How large is it?
126 x 106 x 59.6 mm, and it weighs 367 g.
05What is its temperature range?
Operating -20 to +55 degrees C, storage -40 to +70 degrees C.