- Automation & ControlView all 2,612 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- HMI Displays
- Pneumatic Cylinders
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Lovato Electric
Lovato ATL900 Automatic Transfer Switch Controller, 3 Sources
Description
Lovato ATL900 automatic transfer switch controller, 3 sources
The Lovato ATL900 is an automatic transfer switch controller for installations with three power sources and two tie breakers, such as two utility feeders and a generator. It has a 128 x 112 pixel backlit graphic display, three expansion slots, built-in RS485 and 12 digital inputs. Seven Star LLC supplies the ATL900 in Oman and the GCC as an independent supplier in Muscat.
In the ATL line the ATL900 is the largest model described here. The ATL100, ATL500, ATL600 and ATL800 are listed in the same catalogue group, and the ATL900 is the model that manages three sources and two tie breakers with closed transition and PLC logic. Pick it when a standard two-source scheme cannot describe the plant.
ATL900 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Lovato / ATL900 |
| Controlled sources / tie breakers | 3 / 2 |
| Display | Backlit graphic LCD, 128 x 112 pixels; 8 languages |
| Expansion | 3 slots for EXP modules |
| AC supply | 100 to 240 V AC (90 to 264 V); 45 to 66 Hz; 16.5 VA |
| DC supply | 12, 24 or 48 V DC (7.5 to 57.6 V) |
| Voltage inputs | 100 to 600 V AC line-to-line; measurement 50 to 720 V; TRMS; accuracy 0.25 percent f.s. plus 1 digit |
| Current inputs | 5 A or 1 A scale through external CTs |
| Digital inputs | 12 |
| Outputs | 10 relays (6 NO plus 4 changeover) and 1 static output |
| Communication | RS485 built in; options for USB, RS232, Ethernet, Profibus, modem; NFC; Wi-Fi dongle |
| Functions | Closed transition, non-priority load management, power thresholds, PLC logic, timers, 250 event log |
| Temperature | -30 to +70 °C |
| Mounting and protection | Flush mount, cut-out 220 x 160 mm; IP65 front, IP20 terminals |
| Size and weight | 240 x 180 x 43.9 mm; 1800 g |
| Immunity | Shock 15 g; vibration 0.7 g |
How the ATL900 manages three sources
The controller measures each source and decides which should feed the load. A typical scheme has mains 1, mains 2 and a generator, with a tie breaker between busbar sections. If the preferred source fails or leaves its voltage and frequency window, the controller starts the generator when needed, waits for the source to stabilise and commands the breakers in the configured order, with interlocks that avoid paralleling unintended sources.
Source types are programmable, so each input can be a utility line or a generator. Closed transition allows a brief overlap when both sources are healthy, so that the load moves without interruption during a planned retransfer. Switching decisions can also depend on power thresholds, which is useful for peak shaving or load management.
Measurements and logic inside the ATL900
True RMS voltage measurement covers 100 to 600 V line-to-line, with 50 to 720 V as the measurement range, and the frequency range includes 360 to 440 Hz. Current can be monitored through external transformers on the 5 A or 1 A scale. Built-in PLC logic, timers, limits and user alarms allow special sequences without extra hardware, and 14 system layouts are shown on the display, with custom layouts possible.
Communication and expansion of the ATL900
RS485 is built in, and optional modules from the EXP1000 range add USB, RS232, Ethernet, Profibus, a modem, analogue inputs and outputs, and extra I/O. A front optical port with a USB or Wi-Fi dongle, and NFC, allow setting without opening the panel. An RGKRR accessory serves for remote alarm repeating.
ATL900 selection checklist
- Three sources and two tie breakers in the single-line diagram
- Voltage levels up to 600 V line-to-line, or via transformers
- Closed transition or open transition requirement
- Number of digital inputs and relay outputs needed
- Communication options and protocols
- Panel cut-out of 220 x 160 mm
- Control power from AC mains and DC battery
Installing and commissioning the ATL900
Fit through the panel cut-out so the front is IP65, wire the voltage sense through suitable fuses, and connect breaker feedback and command circuits as drawn. Always add hardware interlocks on the breakers; the controller logic should never be the only protection against paralleling.
Commissioning involves simulating each source failure and recovery, checking all timers, and testing the generator start and stop signals. Keep the event log as part of the commissioning record, and save the configuration file.
Typical ATL900 applications in Oman and the GCC
This controller suits data centres, hospitals, airports, large commercial buildings and plants where two utility feeders and standby generation share a bus. High ambient temperatures are handled by the -30 to +70 °C range, and the IP65 front resists the dust that enters switch rooms.
ATL controllers in the catalogue
| Part | Notes |
|---|---|
| ATL100 | Related controller, see its data sheet |
| ATL500 | Related controller, see its data sheet |
| ATL600 | Related controller, see its data sheet |
| ATL800 | Related controller, see its data sheet |
| ATL900 | This part: 3 sources, 2 tie breakers |
A transfer scheme is only as reliable as its testing routine. Plan regular tests with a load transfer at least once a year, and use the event log to review each transfer time and any alarms. Check the generator start signal and the cool-down timers, since many failures on real outages come from batteries and fuel rather than from the controller. The expansion slots make later additions possible, for example analogue inputs for fuel level or extra relays for annunciation, so design the panel with space and cable routes for these modules from the start.
Information to send with an RFQ for the ATL900
- Part number ATL900 and quantity
- Single-line diagram and source types
- Voltage and CT ratios
- Communication needs and expansion modules
- Control supply
- Delivery location
Documents and quotation
Send the part number ATL900 and we will confirm the documents available for it, such as the technical data sheet, wiring diagram and instruction sheet, together with availability and lead time.
Seven Star LLC is an independent supplier in Muscat and is not an official channel of the manufacturer. Share the quantity, delivery location and project reference with the request and we will answer with a formal quotation.
Datasheets & Documents
- Datasheet Lovato ATL900 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.
Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.
Lovato Electric at a glance
| Established | 1922, Bergamo, Italy |
|---|---|
| Headquarters | Gorle (Bergamo), Italy |
| Ownership | Private, family-run for four generations |
| Product families | Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs |
Lovato products we list
| Family | Models | Typical use |
|---|---|---|
| Contactors | BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing | Switching motors, heaters, lighting and capacitor banks |
| Motor protection and starters | SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay | Short-circuit and overload protection and direct starting of motors |
| Soft starters | ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 | Reducing starting current and mechanical shock on pumps, fans and compressors |
| Variable speed drives | VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 | Speed control of pumps, fans and conveyors to save energy |
| Power management and control | DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC | Power factor correction, mains/generator changeover and energy monitoring |
Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.
Where Lovato products are used
In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.
Ordering Lovato products: what we need
Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.
Facts checked against Lovato Electric company profile brochures, October 2026.
Browse Lovato Electric products by category: Motor Soft Starters, Automation Accessories, Controllers & Data Acquisition, PLC & I/O Cards, Circuit Breakers, Diesel Generator Spare Parts.
FAQ
Questions about the Lovato ATL900 Automatic Transfer Switch Controller,
Answers from our engineering team on installation, compatibility and integration.
01How many sources can the ATL900 manage?
Three power sources and two tie breakers according to the catalogue.
02Does it support closed transition?
Yes, closed transition is listed among its functions.
03What display does it have?
A backlit graphic LCD of 128 x 112 pixels with 8 languages.
04What communication is built in?
RS485 is built in; further interfaces are added with EXP modules, an NFC link and optional dongles.
05What size is the panel cut-out?
The flush-mount cut-out is 220 x 160 mm and the front protection is IP65.


















Reviews
There are no reviews yet.