Brand: Schneider Electric
Schneider Electric ATV930D22N4 22 kW Process Drive IP21
Description
ATV930D22N4: 22 kW Altivar Process ATV900 drive with braking unit
The ATV930D22N4 is a Schneider Electric variable speed drive listed in the datasheet as: Variable Speed Drive, Altivar Process ATV900, ATV930, 22kW, 400 to 480V, with braking unit, IP21. The ATV930 is the high-performance member of the ATV900 process family. It is built for heavy-duty industrial lines that need accurate torque, regenerative-energy handling and a choice of safety and communication options. The 22 kW normal-duty size is a mid-power, wall-mounted frame with a braking unit built in. Seven Star LLC supplies the ATV930D22N4 in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference: ATV930 is the product range, D22 the 22 kW rating, and N4 the 400/480 V three-phase supply. The datasheet title lists the braking unit and IP21, and the variant row lists both standard and braking-chopper versions, so quote the full reference when ordering.
Technical specifications of the ATV930D22N4
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / ATV930D22N4 |
| Description | Variable Speed Drive, Altivar Process ATV900, ATV930, 22kW, 400 to 480V, with braking unit, IP21 |
| Range of Product | Altivar Process ATV900 |
| Product Specific Application | Process for industrial |
| Product or Component Type | Variable speed drive |
| Variant | Standard version; With braking chopper |
| Device Application | Industrial Application |
| Product destination | Synchronous motors; Asynchronous motors |
| Phase | 3 phase |
| Mounting Mode | Wall mount |
| Continuous output current | 46.3 A 4 kHz normal duty; 39.2 A 4 kHz heavy duty |
| Communication Port Protocol | Modbus serial; EtherNet/IP; Modbus TCP |
| option module | Slot A communication module Profibus DP V1; Slot A communication module PROFINET; Slot A communication module DeviceNet |
| [Us] rated supply voltage | 380 to 480 V |
| Relative symmetric mains voltage | 10 % |
| Relative symmetric network | 5% |
| nominal output current | 46.3 A |
| Motor power kW | 22.0 kW normal duty; 18.5 kW heavy duty |
| EMC filter | Integrated; With EMC plate option |
| IP degree of protection | IP21 |
| Degree of protection | UL type 1 |
| Electrical connection | Control screw terminal 0.5 to 1.5 mm² 20 AWG–16 AWG; Line side screw terminal 10 to 16 mm² 8 AWG–6 AWG |
| Transmission Rate | 10, 100 Mbits; 4.8 kbps; 9600 bit/s; 19200 bit/s |
| Exchange mode | Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP |
| Data format | 8 bits, configurable odd, even or no parity |
| Type of polarization | No impedance |
| Number of addresses | 1 to 247 |
| Supply | External supply for digital inputs 24 V DC 19 to 30 V, <1.25 mA overload and short- circuit protection |
| Local signalling | Local diagnostic: 3 LED (mono/dual colour); Embedded communication status: 5 LED (dual colour) |
| Input compatibility | DI1–DI8 discrete input level 1 PLC IEC 61131-2; DI7, DI8 pulse input level 1 PLC IEC 65A-68 |
| Discrete input logic | 16 preset speeds |
| Sampling duration | 2 ms ± 0.5 ms DI1–DI8 – discrete input; 5 ms ± 1 ms DI7, DI8 – pulse input; 1 ms ± 1 ms AI1, AI2, AI3 – analog input |
| Accuracy | ± 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input; ± 1 % AQ1, AQ2 for a temperature variation 60 °C analog output |
| Linearity error | AI1, AI2, AI3 ± 0.15 % of maximum value analog input; AQ1, AQ2 ± 0.2 % analog output |
| Refresh time | Relay output R1, R2, R35 ms ± 0.5 ms |
| Isolation | Between power and control terminals |
| Discrete input number | 10 |
| Discrete input type | DI1–DI8 programmable, 24 V DC <= 30 V3.5 kOhm; DI7, DI8 programmable as pulse input 0 to 30 kHz, 24 V DC <= 30 V |
| Discrete output number | 2 |
| Discrete output type | Logic output DQ+ 0 to 1 kHz <= 30 V DC 100 mA; Programmable as pulse output DQ+ 0 to 30 kHz <= 30 V DC 20 mA |
| Analogue input number | 3 |
| Analogue input type | AI1, AI2, AI3 software-configurable voltage 0 to 10 V DC 30 kOhm 12 bits |
Motor, supply and output ratings of the ATV930D22N4
The rated motor power is stated as 22.0 kW normal duty; 18.5 kW heavy duty. The nominal output current is 46.3 A. Continuous output current figures: 46.3 A 4 kHz normal duty; 39.2 A 4 kHz heavy duty. The supply voltage range is 380 to 480 V. Phase information from the datasheet: 3 phase.
Overload capability: 55.6 A 60 s normal duty; 58.8 A 60 s heavy duty. Motor control profiles: Variable torque standard. Switching frequency: 2 to 16 kHz adjustable; 4 to 16 kHz with derating factor. Line short-circuit rating: 50 kA.
Control, communication and safety functions of the ATV930D22N4
Communication protocols listed: Modbus serial; EtherNet/IP; Modbus TCP. Optional modules: Slot A communication module Profibus DP V1; Slot A communication module PROFINET; Slot A communication module DeviceNet. EMC filter: Integrated; With EMC plate option. Discrete inputs: 10. Analogue inputs: 3. Relay outputs: 3. Braking: By DC injection. Typical features of the ATV900 platform are modular option slots for fieldbuses, I/O and encoder feedback, plus safety functions that can be extended by a safety module. Select the options before ordering because they are not interchangeable by software.
Normal duty versus heavy duty on the ATV930D22N4
A drive of this class has two ratings on the same frame. In normal duty it delivers 22 kW with a higher continuous current but a lower overload margin; in heavy duty the rating drops to 18.5 kW with a larger overload for a limited time. The datasheet lists both sets of numbers, and a machine with frequent starts under load should be sized on heavy duty.
The built-in braking chopper only helps if an external braking resistor is added. Resistor power must be sized from the braking energy of the application: a fan with high inertia and a quick stop produces far more regenerative energy than a pump. Do not guess; compute the duty cycle.
Installation, wiring and commissioning of the ATV930D22N4
The ATV930 is wall-mounted in IP21 form and needs the clearances and mounting rules of the installation manual. Use the EMC plate and the screened motor cable, as the datasheet lists an integrated EMC filter with a plate option. Connect the braking resistor to the dedicated terminals and fit its thermal protection into the fault chain.
Commission with the keypad or the commissioning software: nameplate data, motor auto-tuning, then the ramp, current limit and fieldbus. Store a parameter backup. In Gulf plants keep the cabinet below the datasheet temperature limit and inspect the cooling fans every maintenance cycle.
Typical applications of the ATV930D22N4 in Oman and the GCC
Typical uses are larger centrifugal pumps, compressors, extruders and conveyors in process plants, and water-treatment or desalination auxiliaries where the drive must communicate by Ethernet. Where the motor runs in a hot region, check the derating curve before quoting the frame size.
Dimensions, environment and approvals of the ATV930D22N4
For the ATV930D22N4, plan the mounting space from the datasheet: 211 mm (W) x 545.9 mm (H) x 235 mm (D). The ATV930D22N4 weighs 14.3 kg. Mounting, derating and enclosure choices follow the environmental data below, which should be compared with the actual panel temperature and the dust and humidity of the site in Oman and the GCC.
Ambient temperature limits in the datasheet: -15 to 50 °C (without derating). Relative humidity: 5 to 95 % without condensation IEC 60068-2-3. Ingress protection: IP21. Operating altitude: <= 1000 m without derating; 1000 to 4800 m with current derating 1 % per 100 m. Vibration resistance: 1.5 mm peak to peak (f= 2 to 13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13 to 200 Hz) conforming to IEC 60068-2-6. Shock resistance: 15 gn 11 ms IEC 60068-2-27. Standards listed: UL 508C; IEC 61800-3; IEC 61800-5-1; IEC 61000-3-12; IEC 60721-3; IEC 61508; IEC 13849-1. Certifications listed for this reference: CSA; UL; TÜV.
Information to send with an RFQ for the ATV930D22N4
- Full reference and quantity required
- Existing equipment, panel or rack it must fit
- Supply voltage, load or signal details of the application
- Required delivery location and timing
- Whether a spare, a replacement or a new installation
Documents and quotation
A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and does not represent itself as an official channel of the manufacturer.
Other Models in the Se Atv930 Range
Seven Star LLC supplies models from the Se Atv930 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric ATV930D11N4 11 kW Process Drive | AC Drives | View details |
| Schneider Electric ATV930D22N4 22 kW Process Drive IP21 | AC Drives | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric ATV930D22N4 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric ATV930D22N4 22 kW Process Drive
Answers from our engineering team on installation, compatibility and integration.
01What power does the ATV930D22N4 deliver?
The datasheet states: 22.0 kW normal duty; 18.5 kW heavy duty.
02Which communication networks does the ATV930D22N4 support?
Listed: Modbus serial; EtherNet/IP; Modbus TCP.
03Has the ATV930D22N4 a braking unit?
The variants listed are: Standard version; With braking chopper.
04What is the degree of protection of the ATV930D22N4?
It is IP21.
05What supply does the ATV930D22N4 need?
It is rated 380 to 480 V.