Schneider Electric ATV212HU15N4 1.5 kW HVAC Drive 480 V
Description
ATV212HU15N4: a 1.5 kW Altivar 212 drive for fans and pumps
The ATV212HU15N4 is a Schneider Electric variable speed drive listed in the datasheet as: variable speed drive, Altivar 212, 1.5kW, 2hp, 480V, 3 phases, with EMC, IP21. The Altivar 212 line is the HVAC and building-services drive of the family, tuned for centrifugal fans and pumps where torque falls with speed. This 1.5 kW unit is the smallest practical size for a single exhaust fan, a circulation pump or a small booster set. Seven Star LLC supplies the ATV212HU15N4 in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference: ATV212 is the range, the H and U15 part carries the form factor and the 1.5 kW rating, and N4 marks the 400/480 V three-phase supply class. The datasheet title confirms 1.5 kW, 2 hp, 480 V, 3 phases, so use the title and the ordering table together when you confirm a replacement.
Technical specifications of the ATV212HU15N4
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / ATV212HU15N4 |
| Description | variable speed drive, Altivar 212, 1.5kW, 2hp, 480V, 3 phases, with EMC, IP21 |
| Device short name | ATV212 |
| Product destination | Asynchronous motors |
| Phase | 3 phase |
| Motor power kW | 1.5 kW |
| Maximum Horse Power Rating | 2 hp |
| Supply voltage limits | 323 to 528 V |
| Supply frequency | 50 to 60 Hz (tolerance -5 % / +5 %) |
| Line current | 2.5 A 480 V; 3.2 A 380 V |
| Range of Product | Altivar 212 |
| Product or Component Type | Variable speed drive |
| Product Specific Application | Pumps and fans in HVAC |
| Communication Port Protocol | APOGEE FLN; BACnet; Modbus; LonWorks; METASYS N2 |
| [Us] rated supply voltage | 380 to 480 V (tolerance -15 % / +10 %) |
| EMC filter | Class C2 EMC filter integrated |
| IP degree of protection | IP20 on upper part without blanking plate on cover IEC 61800-5-1; IP20 on upper part without blanking plate on cover IEC 60529 |
| Apparent power | 2.8 kVA 380 V |
| Continuous output current | 3.7 A 380 V; 3.7 A 460 V |
| Maximum transient current | 4 A 60 s |
| Speed drive output frequency | 0.5 to 200 Hz |
| Speed range | 1 to 10 |
| Speed accuracy | ± 10 % of nominal slip 0.2 Tn to Tn |
| Local signalling | 1 LED (red) for DC bus energized |
| Output voltage | <= power supply voltage |
| Isolation | Electrical between power and control |
| Type of cable | Without mounting kit 1 IEC cable 45 °C, copper 90 °C / XLPE/EPR; Without mounting kit 1 IEC cable 45 °C, copper 70 °C / PVC |
| Electrical connection | VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 2.5 mm² / 14; AWG; L1/R, L2/S, L3/T terminal 6 mm² / 10 AWG |
| Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC ± 5 %, <10 A overload and short-circuit protection |
| Sampling duration | 2 ms ± 0.5 ms F discrete; 2 ms ± 0.5 ms R discrete; 2 ms ± 0.5 ms RES discrete; 3.5 ms ± 0.5 ms VIA analog |
| Response time | FM 2 ms ± 0.5 ms analog; FLA, FLC 7 ms ± 0.5 ms discrete; FLB, FLC 7 ms ± 0.5 ms discrete; RY, RC 7 ms ± 0.5 ms discrete |
| Accuracy | ± 0.6 % VIA for a temperature variation 60 °C; ± 0.6 % VIB for a temperature variation 60 °C; ± 1 % FM for a temperature variation 60 °C |
| Linearity error | VIA ± 0.15 % of maximum value input; VIB ± 0.15 % of maximum value input; FM ± 0.2 % output |
| Analogue output type | FM switch-configurable voltage 0 to 10 V DC 7620 Ohm 10 bits; FM switch-configurable current 0 to 20 mA 970 Ohm 10 bits |
| Discrete output type | Configurable relay logic FLA, FLC NO – 100000 cycles; Configurable relay logic FLB, FLC NC – 100000 cycles |
| Minimum switching current | 3 mA 24 V DC configurable relay logic |
| Maximum switching current | 5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R; 5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R |
| Discrete input type | F programmable 24 V DC level 1 PLC 4700 Ohm; R programmable 24 V DC level 1 PLC 4700 Ohm; RES programmable 24 V DC level 1 PLC 4700 Ohm |
| Discrete input logic | Positive logic (source) F, R, RES, <= 5 V, >= 11 V; Negative logic (sink) F, R, RES, >= 16 V, <= 10 V |
| Dielectric strength | 3535 V DC between earth and power terminals; 5092 V DC between control and power terminals |
| Insulation resistance | >= 1 mOhm 500 V DC for 1 minute |
| Frequency resolution | Display unit 0.1 Hz; Analog input 0.024/50 Hz |
Motor, supply and output ratings of the ATV212HU15N4
The rated motor power is stated as 1.5 kW. Continuous output current figures: 3.7 A 380 V; 3.7 A 460 V. The supply voltage range is 380 to 480 V (tolerance -15 % / +10 %). Phase information from the datasheet: 3 phase.
Overload capability: 4 A 60 s. Motor control profiles: Voltage/frequency ratio – Energy Saving, quadratic U/f. Speed range: 1 to 10. Switching frequency: 6 to 16 kHz adjustable; 12 to 16 kHz with derating factor. Line short-circuit rating: 5 kA.
Control, communication and safety functions of the ATV212HU15N4
Communication protocols listed: APOGEE FLN; BACnet; Modbus; LonWorks; METASYS N2. EMC filter: Class C2 EMC filter integrated. Analogue inputs: 2. Braking: By DC injection. Because the range is aimed at building services, it brings functions such as a simple PID loop, multiple presets and a serial link so a building management system can start, stop and read speed without extra hardware. Always check the protocol list above against your network.
What makes the ATV212HU15N4 different from a general-purpose machine drive
A machine drive is judged on starting torque and positioning; an HVAC drive is judged on energy saved at partial load. For a centrifugal fan, power falls roughly with the cube of speed, so a 20 percent speed reduction can cut absorbed power by about half. That is why the ATV212HU15N4 class of drive pays back quickly on fans and pumps that run throttled today.
Typical set-up work on this unit is therefore about limits rather than dynamics: minimum speed so a pump never runs dry, a skip frequency to avoid a duct resonance, and an acceleration time long enough not to stress a belt. Document these settings after commissioning because the next engineer will need them.
Installation, wiring and commissioning of the ATV212HU15N4
Mount the drive vertically in a ventilated cabinet with the clearances in the installation guide, and keep the power cables physically separated from the control and fieldbus wiring. Use a motor cable length and screening consistent with the EMC statement of the datasheet, and ground both ends of the screen.
During commissioning enter the motor nameplate data, run the auto-tune if the datasheet procedure offers it, and test the rotation direction with the coupling off. Check the heatsink fan and clean the vents on every shutdown; in dusty Gulf sites, filter mats on the cabinet door extend the life of the drive.
Typical applications of the ATV212HU15N4 in Oman and the GCC
In Oman and the GCC a 1.5 kW variable-torque drive typically drives air-handling fans, cooling-water circulation pumps, small jockey pumps and ventilation fans in utility buildings and plant rooms. High ambient temperature is the main concern: derate if the cabinet runs hot, and prefer an air-conditioned electrical room.
Dimensions, environment and approvals of the ATV212HU15N4
For the ATV212HU15N4, plan the mounting space from the datasheet: 107 mm (W) x 143 mm (H) x 150 mm (D). The ATV212HU15N4 weighs 2 kg. Mounting, derating and enclosure choices follow the environmental data below, which should be compared with the actual panel temperature and the dust and humidity of the site in Oman and the GCC.
Ambient temperature limits in the datasheet: -10 to 40 °C (without derating). Relative humidity: 5 to 95 % without condensation IEC 60068-2-3; 5 to 95 % without dripping water IEC 60068-2-3. Ingress protection: IP20 on upper part without blanking plate on cover IEC 61800-5-1; IP20 on upper part without blanking plate on cover IEC 60529. Operating altitude: 1000 to 3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m; <= 1000 m without derating. Vibration resistance: 1.5 mm (f= 3 to 13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13 to 200 Hz) conforming to EN/IEC 60068-2-8. Shock resistance: 15 gn 11 ms IEC 60068-2-27. Standards listed: EN 55011 class A group 1; IEC 61800-3 environments 2 category C1; EN 61800-3 category C3; IEC 61800-3; IEC 61800-3 environments 2 category C2. Certifications listed for this reference: UL; NOM 117; C-tick; CSA.
Information to send with an RFQ for the ATV212HU15N4
- Full reference and quantity required
- Existing equipment, panel or rack it must fit
- Supply voltage, load or signal details of the application
- Required delivery location and timing
- Whether a spare, a replacement or a new installation
Documents and quotation
A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and does not represent itself as an official channel of the manufacturer.
Datasheets & Documents
- Datasheet Schneider Electric ATV212HU15N4 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric ATV212HU15N4 1.5 kW HVAC Drive
Answers from our engineering team on installation, compatibility and integration.
01What power and supply is the ATV212HU15N4 for?
The datasheet lists 1.5 kW.
02Which communication protocol does the ATV212HU15N4 use?
Listed: APOGEE FLN; BACnet; Modbus; LonWorks; METASYS N2.
03Does the ATV212HU15N4 have an EMC filter?
The datasheet states: Class C2 EMC filter integrated.
04What degree of protection has the ATV212HU15N4?
Stated as IP20 on upper part without blanking plate on cover IEC 61800-5-1; IP20 on upper part without blanking plate on cover IEC 60529; IP21 IEC 61800-5-1; IP21 IEC 60529; IP41 on upper part IEC 61800-5-1.
05What is the supply voltage of the ATV212HU15N4?
It is 380 to 480 V (tolerance -15 % / +10 %).