Brand: JUMO
JUMO meroVIEW 104/108/116 Digital Indicator with PLC Function
Description
Multifunction panel indicator with PLC-style logic in four DIN formats
The JUMO meroVIEW data sheet 701551 covers four universal indicators in different DIN formats: 701551 (format 116, 48 x 48 mm), 701552 (108H, 48 x 96 mm), 701553 (108Q, 96 x 48 mm) and 701554 (104, 96 x 96 mm). Each has a universal analog input, a digital input, a switchable digital input/output and two relay outputs, and shows values on two 18-segment LCD lines. The three larger types add a pixel-matrix text display.
What separates it from a simple indicator is the optional logic layer. Extra code 214 adds a math and logic module with up to four formulae, and extra code 221 adds structured text (ST code) so users can write their own functions, including direct access to the display and keys. Four menu levels, four languages and lockable levels let the supplier adapt the operation to the plant. The photo shows the series.
Three limit-value functions with two alarm functions each can use any signal from the selector, and a timer, service counter and operating-hours counter are built in. Signals are routed through analog and digital selectors, so assignment of inputs to outputs is flexible rather than hard-wired.
Technical specifications
| Parameter | Specification |
|---|---|
| Types / formats | 701551 (116, 48 x 48 mm); 701552 (108H, 48 x 96 mm); 701553 (108Q, 96 x 48 mm); 701554 (104, 96 x 96 mm) |
| Panel cut-outs | 116: 45 x 45 mm; 108H: 45 x 92 mm; 108Q: 92 x 45 mm; 104: 92 x 92 mm (+0.6/+0.8 mm tolerance) |
| Analog input | Universal: RTD, thermocouple, 0(4) to 20 mA, 0 to 10 V, 0 to 1 V, resistance transmitter 0 to 4000 Ohm, resistance/potentiometer 0 to 400/4000 Ohm; heater current input |
| Sampling | Min. 50 ms (configurable); digital filter 2nd order, 0 to 100 s; up to 5 analog inputs with options |
| Standard outputs | 2 relays (N/O, 3 A at AC 230 V or DC 24 V); logic output 0/14 V, 20 mA |
| Optional outputs | Relay changeover 8 A; solid-state relay 1 A at AC 230 V; logic 0/22 V (30 mA, isolated, for 2-wire transmitter supply); 2 open-collector outputs 1.3 A at DC 24 V; analog output 0 to 10 V or 0(4) to 20 mA, accuracy 0.5 % |
| Counting inputs | Up to 4, 12.5 kHz max., 0/24 V or contact |
| Interfaces | USB device (Micro-B); USB host (type A, flash drive); RS485 Modbus RTU master/slave; Ethernet Modbus TCP; PROFINET IO device (conformity class C) |
| Display digit height | Upper line 12.3 mm (116), 11.5 mm (108H), 15 mm (108Q), 24.8 mm (104); lower line 5.9 to 12 mm |
| Supply | AC 110 to 240 V +10/-15 % or AC/DC 24 V +10/-15 %; max. 4.3 to 8.9 W depending on type and supply |
| Approvals as printed | UL (E201387, UL 61010-1) all versions; DNV TAA00001B3 for 701554 with extra code 062 and without Ethernet |
| Ambient / storage | Operation -10 to +55 °C; storage -30 to +70 °C; max. 90 % rel. humidity; site altitude max. 2000 m |
| Vibration / shock | 0.15 mm at 10 to 58.1 Hz, 20 m/s2 to 150 Hz; shock 150 m/s2, 11 ms |
| Housing | Panel mounting to IEC 61554; IP65 front, IP20 back; weight max. 170 g (116), 271 g (108), 417 g (104) |
Choosing the format and option set
The order code has ten blocks: type, version (8 default, 9 customer-specific), device language, options 1 to 4 (the analog, digital and counting inputs and outputs), options 5 and 6 (Ethernet or PROFINET and RS485, only on 701554), supply (23 or 42) and extra codes (062 DNV, 214 math and logic, 221 structured text, 879 AMS2750/CQI-9). An example from the sheet is 701554/8-01-03-09-09-12-11-23/214. Certain inputs and outputs cannot be used together, so check the connection diagram when choosing options.
Extra code 879 is for permanently installed use with a calibration certificate; the sheet states it may not be used as a mobile field-test unit for SAT and TUS tests, and it applies only with customer-specific configuration. PROFINET excludes Ethernet and RS485 on the same device.
Applications and data handling
Use the small 116 format on machine fronts and the 104 format where operators read values from a distance, up to 24.8 mm digits. The data logger can be read out through the USB-host port with a flash drive, which also carries firmware updates and device configurations. A retain memory keeps service, counter, timer and ST-code data through a power failure.
Typical jobs include temperature and pressure displays with limit relays, weighing or batching with the taring and timer functions, and flow totalizing from counter inputs. Confirm the exact type and option string in your quotation request, as the data sheet describes four types in one document.
Extra care is needed with the AMS2750/CQI-9 code: the thermocouple type and the calibration points must be defined for the certificate, which makes the option suitable for heat-treatment furnaces with permanently installed instruments in the automotive and aerospace supply chain.
Mount the instrument in a panel with the cut-out from the data sheet, and keep the supply voltage within the stated tolerance. A clean, vibration-free panel gives the longest service life for the display and the keypad.
Documents and quotation
For engineering details, open the attached PDF (JUMO meroVIEW 104/108/116 data sheet 701551 V4.00 (EN)). When you are ready to buy, submit the order code and project requirements through the request form, and our team will confirm what can be supplied and when. Browse the category Controllers & Data Acquisition for alternatives.
Datasheets & Documents
- Datasheet JUMO meroVIEW 104/108/116 data sheet 701551 V4.00 (EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
JUMO is the German maker of temperature sensors, process controllers, pressure transmitters and liquid analysis instruments. Moritz Kurt Juchheim founded it in Fulda in 1948 as M. K. Juchheim KG, making glass thermometers with six employees. The name JUMO comes from the founder's name. It is still a family company headquartered in Fulda, and the parent company has been called JUMO GmbH & Co. KG since 2003.
Seven Star LLC is an independent supplier in Muscat. We list JUMO RTD and thermocouple probes, thermowells, transmitters, controllers, recorders and water analysis instruments, and supply them to process plants, OEMs, HVAC contractors and water utilities in Oman and the GCC by type number.
JUMO company profile
| Established | 1948, Fulda, Germany, by Moritz Kurt Juchheim |
|---|---|
| First products | Glass and contact thermometers; platinum glass sensors from 1966 |
| Ownership | Family-owned; renamed JUMO GmbH & Co. KG in 2003 |
| Product families | RTD and thermocouple probes, thermowells, temperature and pressure transmitters, controllers and thermostats, safety temperature limiters, paperless recorders, liquid analysis and flow and level instruments |
Milestones
- 1948: Moritz Kurt Juchheim founds M. K. Juchheim KG in Fulda, making glass thermometers with six employees.
- 1966: Platinum glass temperature sensors are added.
- 2003: The parent company is renamed JUMO GmbH & Co. KG.
JUMO products we list
| Family | Models | Typical use |
|---|---|---|
| RTD and thermocouple probes | 902020, 902030, 902050, 902120, 902006 2xPt100, PROCESStemp, mineral-insulated RTD, 901020 thermocouple, 901210, 902810 hygienic, 902550 surface, 902520 HVAC, MarineTemp | Temperature measurement in pipes, vessels, machines, HVAC and food plants |
| Thermowells and inserts | 909710 thermowells, 909740 measuring inserts | Protecting sensors and replacing them without opening the process |
| Temperature transmitters | dTRANS T01, T03, T04, T05, T06 SIL, T07 HART, T09, T1000 IO-Link, DELOS T switch | Converting sensor signals to 4-20 mA, HART or IO-Link |
| Pressure and level | dTRANS p20, p30, p31 hygienic, p33 Ex, p02 DELTA, MIDAS S05, MIDAS DP10, DELOS S02, MAERA S25, NESOS R20 | Pressure in process, hydraulic and OEM systems; tank and well level |
| Controllers, limiters and recorders | DICON touch, IMAGO 500, dTRON 316, iTRON, cTRON, diraTRON 104, eTRON T, safetyM STB/STW, safetyM TB/TW, LOGOSCREEN 601, mTRON T | Furnace, oven and process control, over-temperature protection and recording |
| Liquid analysis and flow | AQUIS touch S, AQUIS touch P, AQUIS 500 pH, AQUIS 500 CR, dTRANS pH 02, pH electrode, digiLine DO, ecoLine NTU, flowTRANS MAG H20, flowTRANS US W01 | pH, conductivity, oxygen and turbidity in water treatment; liquid flow |
Choosing a temperature sensor starts with the range and accuracy. A Pt100 RTD is accurate and stable from about -200 to 600 °C and is the usual choice in process plants. A thermocouple (type K or J, for example) covers much higher temperatures and responds faster but is less accurate. The wiring also matters: a 3-wire or 4-wire Pt100 connection cancels the resistance of the cable, while a 2-wire connection adds an error that grows with cable length. That is why a head-mounted transmitter is often fitted close to the sensor.
Where JUMO products are used
In Oman and the GCC, JUMO sensors and controllers are used in oil and gas and chemical plants, food and beverage production, plastics and metal heat treatment, HVAC and district cooling, water and wastewater treatment, swimming pools and marine applications.
Ordering JUMO products: what we need
Send the JUMO type number and the full order code from the label (for example 902020/10-...). For probes, add the sensor type (Pt100, Pt1000, type K or J), the number of wires, the insertion length and diameter, and the process connection. For controllers, add the input, outputs and supply voltage.
Facts checked against JUMO's company history, October 2026.
Browse JUMO products by category: Temperature Instrumentation, Pressure Instrumentation, Liquid Analysis Sensors, Controllers & Data Acquisition, Level Transmitter.
Related products
Frequently Asked Questions
116 (48 x 48 mm), 108H (48 x 96 mm), 108Q (96 x 48 mm) and 104 (96 x 96 mm).
Structured text for user-specific functions, available with extra code 221, with access to display and keys.
RS485 Modbus RTU, Ethernet Modbus TCP and PROFINET IO device on type 701554.
Yes, the data logger can be extracted through the USB host interface with a flash drive.
IP65 at the front and IP20 at the back.