Lovato ATL800 Automatic Transfer Switch Controller

Description

Controller for automatic changeover between two supplies

Lovato Electric lists the ATL800 as Automatic transfer switch controller for 2 power sources and one tie-breaker, three phase control, with LCD display, built-in RS485, expandable. In a changeover panel it reads the line values of 2 sources and operates relay outputs that close the correct contactor or breaker.

Measuring inputs accept 100-600VAC L-L (346VAC L-N) with true RMS measurement, the supply range is 110-240 VAC, and the display is backlit lcd graphic display 128×80 pixel with 8 languages.

Technical specifications

Parameter Specification
Order code ATL800
Product designation Automatic transfer switch controller for 2 power sources and one tie-breaker, three phase control, with LCD display, built-in RS485, expandable
Product type designation ATL800
Number of controlled power sources 2
Number of tie-breaker controlled 1
Display Backlit LCD graphic display 128×80 pixel
Languages 8
Expandability 3 expansion slost for EXP- Modules
Rated supply voltage AC 110-240 VAC
Operating supply voltage range AC 90-264 VAC
Rated frequency 50/60 Hz
Operating frequency range 45-66 Hz
Immunity time for microbreakings, 110VAC ≤40 ms
Immunity time for microbreakings, 220VAC ≤200 ms
Immunity time for microbreakings (with EXP expantions), 110VAC ≤20 ms
Immunity time for microbreakings (with EXP expantions), 220VAC ≤100 ms
Power consumption AC (Max) 12.5 VA
Rated supply voltage DC 12-24-48 VDC
Operating supply voltage range DC 7.5-57.6 VDC
Current consumption Max 400mA at 12VDC, 220mA at 24VDC, 100mA at 48VDC
Maximum power consumption / dissipation 4.8 W
Maximum rated voltage Ue 100-600VAC L-L (346VAC L-N)
Measurement range 50-720VAC L-L (415VAC L-N)
Frequency range 45-66 Hz
Measurement method True root mean square (TRMS)
phase-phase above 1.10MΩ
phase-neutral above 0.55MΩ
Measuring accurancy ±0.25% f.s. ±1 digit
Wiring mode Single-phase, two-phase, three-phase line with or without neutral and balanced three-phase system
Number of digital input 8
Type of digital input Negative
Digital current inputs ≤8 mA
Low input signal ≤2.2 VDC
High input signal ≥3.4 VDC
Input signal delay ≥50 ms
Backup reserve power Backup capacitor
Operating without power voltage 14 days approximately
Number of relay output 7
Contact arrangement 4 x 1NO-SPST + 3 x C/O-SPDT
Electrical life 10⁵ cycles
Mechanical life 10⁷ cycles
NFC interf. Yes
Front optical USB communication port Yes, with CX01 USB dongle (optional)
Front optical Wi-Fi communication port Yes, with CX02 Wi-Fi dongle (optional)
USB communication EXP1010 (optional)
RS232 communication EXP1011 (optional)
RS485 communication Built-in or EXP1012 (optional)
Ethernet communication EXP1013 (optional)
Profibus communication EXP1014 (optional)
Communication via Modem EXP1015 (optional)
Number of tie breakers that can be managed 1
Functions and protections provided Programmable source type, Closed transition, Non-priority load management, PLC logic, Timer, Custom system layouts, User alarms, Limits, Real time clock with backup reserve energy, Acoustic alarms
System layout available on display 6
Event logging 250
Analogue inputs EXP1004 (optional)
Analogue outputs EXP1005 (optional)
Operating temperature (min) -30 °C
Operating temperature (max) +70 °C
Storage temperature (min) -30 °C
Storage temperature (max) +80 °C
Maximum Pollution degree 2
Overvoltage category 3
Climatic sequence Z/ABDM (IEC/EN 60068-2-61)
Shock resistance 15g (IEC/EN 60068-2-27)
Vibration resistance 0.7g (IEC/EN 60058-2-6)
Execution Flush mount
Material Polycarbonate
Mounting Flush mount – panel cut-out 220×160 mm
Degree of protection IP65 on front, IP20 on terminals
Dimensions (W x H x D) 240 x 180 x 43.9 mm
Weight 1000 g

Selecting the version

The ATL family splits as follows: ATL100 for single-phase two-source panels, ATL500 and ATL600 for three-phase two-source panels, ATL800 for two sources plus a tie-breaker and ATL900 for three sources with two tie-breakers. Pick the one that matches the single-line diagram.

Verify that outputs, inputs and supply voltage fit the switching devices and the generator controller you already have.

Applications and installation

Typical use is a mains and generator changeover panel for pumping stations, telecom sites, data rooms and building services. The controller is panel-mounted or DIN-rail mounted depending on version.

Dimensions are listed in the table. Relay outputs and inputs are programmable; use the Xpress software or the optical interface to configure.

Related Lovato Electric products: Lovato ATL600 Automatic Transfer Switch Controller 2 Sources, Lovato DCRL8 8-Step Automatic Power Factor Controller, Lovato LVM20A240 LVM20 Level Control Relay, Lovato LVM40A240 LVM40 Level Control Relay, Lovato PMIB1A230 Insulation Monitoring Relay for IT Networks and Lovato LVMP30A240 LVMP30 Pump Start-Up Priority Change Relay.

Documents and quotation

The Lovato Electric datasheet for ATL800 (English, exported from the manufacturer’s online catalogue) is attached and is the source of the figures above. Make sure of the number of sources, the supply voltages, the contactor or breaker type and the generator start arrangement before placing an order, since the published values can change. More products of this type are under controllers & data acquisition. Use the quotation form with the code ATL800 and your quantity; availability is confirmed by Seven Star LLC, an independent supplier in Muscat.

Datasheets & Documents
  • PDF Datasheet Lovato Electric ATL800 datasheet (EN, catalogue export) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.

Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.

Lovato Electric at a glance

Established 1922, Bergamo, Italy
Headquarters Gorle (Bergamo), Italy
Ownership Private, family-run for four generations
Product families Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs

Lovato products we list

Family Models Typical use
Contactors BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing Switching motors, heaters, lighting and capacitor banks
Motor protection and starters SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay Short-circuit and overload protection and direct starting of motors
Soft starters ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 Reducing starting current and mechanical shock on pumps, fans and compressors
Variable speed drives VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 Speed control of pumps, fans and conveyors to save energy
Power management and control DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC Power factor correction, mains/generator changeover and energy monitoring

Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.

Where Lovato products are used

In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.

Ordering Lovato products: what we need

Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.

Facts checked against Lovato Electric company profile brochures, October 2026.

Frequently Asked Questions

How many power sources does the ATL800 control?
2.
What display does it have?
Backlit LCD graphic display 128x80 pixel.
What supply range does it accept?
110-240 VAC.
How many relay outputs does it have?
7.
What is the weight of the ATL800?
1000 g.