- Automation & ControlView all 3,044 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Isolator & Barrier
- Controllers & Data Acquisition
- Safety Switches & Guard Locking
- Motor Soft Starters
- Encoders
- CCTV & Security
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Weidmüller
Weidmuller 1176000000 ACT20M-AI-AO-S Isolating Amplifier
Description
Weidmuller 1176000000 ACT20M-AI-AO-S: configurable isolating amplifier in 6.1 mm
Weidmuller 1176000000 is the ACT20M-AI-AO-S, a configurable analogue isolating amplifier from the ACT20M family. One input and one output share a housing only 6.1 mm wide, and both can be set to a voltage or a current standard signal. It galvanically separates and converts a signal, for example a 4 to 20 mA transmitter output into a 0 to 10 V controller input, with an accuracy better than 0.05 percent of the measuring range. The datasheet also lists a sensor supply, so the module can power a 2-wire transmitter directly.
Input, output and power of 1176000000
The input accepts a voltage source, a current source or a 2-wire transmitter without own power supply. Voltage ranges are 0(2) to 10 V and 0(1) to 5 V with input resistance above 500 kilohm; current ranges are 0 to 20 mA and 4 to 20 mA with 70 ohm input resistance and a voltage drop below 1.5 V. The sensor supply provides more than 17 V DC at 20 mA. The output is configurable to the same voltage or current ranges: a current output drives up to 600 ohm at a maximum of 23 mA, and a voltage output needs a load of at least 10 kilohm. The output is active, so the connected control input must be passive. Cut-off frequency is 100 Hz and step response time is 7 ms or less. Supply is 24 V DC plus or minus 30 percent at the terminals or through the CH20M mounting-rail bus, and power consumption is 0.84 W typical and 1.2 W maximum.
Datasheet table for 1176000000
| Parameter | Value |
|---|---|
| Order No. / Type | 1176000000 / ACT20M-AI-AO-S |
| Version | Analogue isolating amplifier, configurable, with sensor supply |
| Input | 1; voltage, current, 2-wire transmitter |
| Input ranges | 0(2) to 10 V; 0(1) to 5 V; 0 to 20 mA; 4 to 20 mA |
| Input resistance | more than 500 kilohm (U); 70 ohm (I) |
| Sensor supply | more than 17 V DC at 20 mA |
| Output | 1; configurable voltage or current; active |
| Load | 600 ohm or less (current); 10 kilohm or more (voltage) |
| Accuracy | less than 0.05 percent of range |
| Step response | 7 ms or less |
| Temperature coefficient | 0.01 percent per C or less |
| Isolation | 3-way, 2.5 kV rms for 1 minute, 300 V rms rated |
| Supply | 24 V DC plus or minus 30 percent; 0.84 W typical |
| Configuration | DIP switch (delivery state 0 to 20 mA in, 0 to 20 mA out) |
| Dimensions / weight | 6.1 x 112.5 x 114.3 mm / 80 g |
| Temperature | operating minus 25 to 70 C |
| Ex marking | II 3 G Ex nA IIC T4 Gc (zone 2) |
| Approvals | cULus E337701; SIL none per IEC 61508 |
How 1176000000 differs from other ACT20M modules
- ACT20M-CI-CO-S (1175980000): current-in, current-out only, not adjustable, no sensor supply, 87 g, accuracy 0.05 percent.
- ACT20M-CI-CO-ILP-S (1176070000): passive, loop-powered by the input, 2-way isolation, accuracy 0.1 percent, 30 mW, no auxiliary supply.
- ACT20M-UI-AO-S (1176030000): temperature converter accepting thermocouples, RTDs, potentiometers and standard signals, configured with FDT/DTM software, 400 ms step response.
- The AI-AO-S is the one that mixes voltage and current at both ends, with a DIP switch and a sensor supply of more than 17 V at 20 mA.
Applications of the 1176000000 isolating amplifier
Common duties include isolating a 4 to 20 mA signal between a field transmitter and a DCS card to break ground loops, converting a 0 to 10 V position signal into 4 to 20 mA for a long cable, and powering a loop transmitter while passing the signal on to a recorder. Process plants and utilities in the Gulf use these units in marshalling cabinets and in packaged skids to separate different grounding systems. The Ex nA marking permits installation in zone 2, while the field-side sensor still has to be selected for its own area.
Installation and DIP switch configuration for 1176000000
Clip the module on a TS 35 rail, optionally with the CH20M rail bus for common 24 V DC distribution, and wire the screw terminals with up to 2.5 mm² conductors at 0.4 to 0.6 Nm. Set input and output ranges with the DIP switches according to the table on the housing; the delivery state is 0 to 20 mA at both ends. Check with a loop calibrator, and note that the datasheet also offers FDT/DTM configuration for the family.
Maintenance and diagnostics
These isolators need no routine adjustment. The temperature coefficient of 0.01 percent per degree keeps drift low in hot cabinets. When a loop reads wrongly, first check the DIP switch positions and the supply before suspecting the module.
Signal conversion examples with 1176000000
Take a legacy controller that outputs 0 to 10 V for a valve position while the new positioner expects 4 to 20 mA. Set the input DIP switches to 0 to 10 V and the output to 4 to 20 mA; the module converts and isolates in one step with a response of 7 ms or less, quick enough for control loops. In the opposite direction, a 4 to 20 mA transmitter can be turned into 1 to 5 V for an older recorder. Because the input also works as an active loop with a sensor supply above 17 V at 20 mA, the same module may power a 2-wire transmitter while sending the signal to a 0 to 10 V input.
Keep the output load in range: 600 ohm or less for current outputs and 10 kilohm or more for voltage outputs. Where the load might be missing during maintenance, remember that a current output without a closed loop will drive to its compliance limit and a voltage output simply floats to its set value. The datasheet notes the operating altitude limit of 2000 m, pollution severity 2 and surge voltage category II, with EMC to EN 61326-1 and safety to IEC 61010-1.
Documents and quotation
The datasheet for 1176000000 is attached to this page. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Send an RFQ with part number 1176000000, quantity and delivery location for a quotation.
Spares and Lifecycle Considerations
For critical service, many plants hold one Weidmüller 1176000000 as an operational spare rather than waiting for a failure. When you plan spares, look at how many identical isolator & barrier units are installed, how long a replacement would take to arrive, and the cost of an unplanned stop. Store spare units in their original packaging in a dry, temperature-controlled area and record the part number and serial number in your maintenance system. We can quote single units or a small spares package and confirm the lead time for each item in writing.
Other Models in the Act20m Range
Seven Star LLC supplies models from the Act20m range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Weidmuller 1175980000 ACT20M-CI-CO-S Signal Isolator | Isolator & Barrier | View details |
| Weidmuller 1176030000 ACT20M-UI-AO-S Temperature Converter | Isolator & Barrier | View details |
| Weidmuller 1176070000 ACT20M-CI-CO-ILP-S Passive Isolator | Isolator & Barrier | View details |
| Weidmuller 1176000000 ACT20M-AI-AO-S Isolating Amplifier | Isolator & Barrier | You are viewing this model |
Datasheets & Documents
- Datasheet Weidmuller 1176000000 ACT20M-AI-AO-S Isolating Amplifier Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Weidmüller is a German family-owned maker of electrical connection and industrial electronics products, headquartered in Detmold. The company dates from 1850 and was re-established in Detmold in 1948; it specialised in terminal blocks from the 1940s onward. Weidmüller makes Klippon terminal blocks, power supplies, remote I/O and enclosures, and reported over one billion euros in revenue in 2023.
Seven Star LLC lists Weidmüller PRO MAX power supplies and SAK terminal blocks, and supplies Weidmüller components to panel shops and plants in Oman and the GCC.
Weidmüller company profile
| Founded | 1850, Germany |
|---|---|
| Headquarters | Detmold, Germany (since 1948) |
| Ownership | Family-owned |
| Revenue | Over €1 billion (2023) |
| Product families | Klippon Connect terminal blocks, PRO MAX and PRO TOP power supplies, u-remote I/O and fieldbus couplers, Klippon enclosures, connectors and tools |
Milestones
- 1850: Weidmüller is founded.
- 1948: The company is re-established in Detmold.
Weidmüller products listed here
The listed power supplies are DIN rail switch-mode units with 24 V DC output: a PRO MAX single-phase unit rated 180 W and 7.5 A (85 to 277 V AC input), and a PRO MAX3 three-phase unit rated 240 W and 10 A (320 to 575 V AC input). The SAK series is the screw clamp feed-through terminal block family found in many existing panels. Weidmüller now flags several SAK types as being phased out and names a replacement for some of them.
Weidmüller products we list
Ordering Weidmüller parts: what we need
Weidmüller identifies every item by a ten-digit order number, and that number is the surest way to quote. Without it, send the type printed on the part. For power supplies add input voltage and phases, output voltage and current. For terminal blocks add the conductor cross-section, color, and the end plates, cross-connections and markers you need, since accessories are specific to each series.
Facts checked against Weidmüller milestone lists and distributor profiles, October 2026.
Browse Weidmüller products by category: Electrical & Power Modules.
FAQ
Questions about the Weidmuller 1176000000 ACT20M-AI-AO-S Isolating
Answers from our engineering team on installation, compatibility and integration.
01What signals can the 1176000000 convert?
Voltage 0(2) to 10 V and 0(1) to 5 V, or current 0 to 20 mA and 4 to 20 mA, on both input and output, configured by DIP switch.
02Can it power a 2-wire transmitter?
Yes, the datasheet lists a sensor supply of more than 17 V DC at 20 mA and a 2-wire transmitter input.
03How accurate is it?
Accuracy is better than 0.05 percent of the measuring range with a temperature coefficient of 0.01 percent per C or less.
04What is its isolation?
It is a 3-way isolator with 2.5 kV rms insulation voltage for 1 minute and 300 V rms rated voltage.
05May it be installed in a hazardous area?
It carries marking II 3 G Ex nA IIC T4 Gc, so it may be installed in zone 2 or safe areas.


















Reviews
There are no reviews yet.