Brand: MTL (Eaton)
MTL MTL5549 Two-Channel HART Isolating Driver
Description
What the MTL5549 does for HART valve positioners
Control valves in classified areas are usually positioned by an I/P converter or a HART smart positioner fed with 4-20 mA. The MTL MTL5549 is a dual-channel isolating driver purpose-built for that job. It accepts two floating 4-20 mA signals from the safe-area controller, passes each to a hazardous-area loop, and allows bi-directional digital communication for HART devices in the 500 Hz to 10 kHz band.
Line fault detection is included. A process controller with a readback facility sees the loop current drop to a preset level if the field wiring is open or short circuited, so a broken cable is announced instead of silently leaving a valve stuck.
MTL5549 key points
- Two channels in a 16 mm wide DIN-rail module
- Working range 4 to 20 mA, under-range 1 mA, over-range 24 mA with load up to 520 ohm
- Maximum load 800 ohm (16 V at 20 mA); minimum load 90 ohm
- Output resistance above 1 megohm
- Transfer accuracy better than 20 microamps, drift below 1.0 microamp per degree C
- Input and output ripple below 40 microamps peak to peak
- Safety description per channel: Uo 28 V, Io 93 mA, Po 0.65 W, Um 253 V
- Green LED for power indication
MTL5549 technical data
| Model | MTL5549 |
|---|---|
| Type | isolating driver, 4-20 mA, HART, line fault detection |
| Channels | two |
| Load location | Zone 0, IIC, T4-T6 if suitably certified; Div. 1 Group A |
| Working range | 4 to 20 mA |
| Digital bandwidth | 500 Hz to 10 kHz |
| Maximum load | 800 ohm (16 V at 20 mA) |
| Minimum load | 90 ohm; short-circuit detection below 50 ohm |
| Normal input voltage | below 6.0 V |
| Open-circuit input current | below 0.9 mA |
| Short-circuit input current | below 0.9 mA |
| Settling time | within 200 microamps of final value in 100 ms |
| Supply current | 70 mA at 24 V (20 mA into 250 ohm) |
| Power dissipation | 1.6 W at 24 V |
| SIL | SIL2 capable (HFT=0); SIL3 capable with HFT=1 |
| Supply | 20 to 35 V dc |
How MTL5549 compares with MTL5549Y and MTL4549 types
The two-channel driver family has several versions. The MTL4549 is the backplane equivalent, and the MTL4549C and MTL4549Y/MTL5549Y are similar but offer only open-circuit detection. The datasheet tabulates the field wiring states: all three versions read below 6.0 V in normal operation, but for an open circuit the MTL5549 and MTL4549C draw less than 0.9 mA while the Y type draws less than 0.5 mA, and for a short circuit only the MTL5549 and MTL4549 (full-detection types) report less than 0.9 mA, the C and Y types are not applicable.
Select the full MTL5549 when the controller should alarm on both fault types, and the Y type only when the receiving system expects the lower open-circuit threshold.
Where MTL5549 is used in the Gulf region
Control-valve loops in gas processing, refinery process units and power plant fuel systems rely on positioners in hazardous areas. Two valves served by one module lowers rack space, so the MTL5549 is common in marshalling cabinets that serve compressor anti-surge valves, separator level valves and flow-control valves. Water and desalination plants with chemical dosing valves use it too, as do manufacturers with solvent areas.
Because HART communication passes through, asset-management software can read valve diagnostics without disturbing the 4-20 mA control signal.
Selecting and wiring the MTL5549
Confirm that the I/P converter or positioner has a load between 90 and 800 ohm at 20 mA and that its certification accepts 28 V, 93 mA, 0.65 W. For HART positioners, check that the control system output card tolerates HART signals, or that a HART-compatible card is used. The 24 mA over-range capability supports controllers that drive above 20 mA for diagnostics, as long as the load stays at or below 520 ohm.
Wiring follows the plug-in terminal arrangement shown in the datasheet, with each channel’s hazardous-area and safe-area pair on separate plugs.
Commissioning, proof testing and maintenance
Inject 4, 12 and 20 mA from the controller and read the field-side current; the transfer accuracy is better than 20 microamps. Simulate an open circuit and confirm the controller sees the preset fault current. The module is assessed for SIL use, so refer to the safety manual and the proof-test intervals set by the plant safety case. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Worked example: sizing a valve loop on the MTL5549
Suppose a positioner presents 250 ohm to the loop. At 20 mA the voltage across it is 5 V, well below the 16 V that an 800 ohm load would need, so the module has plenty of compliance. Add 100 ohm of cable and the total is 350 ohm, or 7 V at 20 mA. Even a larger positioner at 520 ohm still allows the 24 mA over-range current, which equals about 12.5 V. On the other side, the minimum load of 90 ohm means a very low-resistance load, such as an unloaded cable, would be read as a short circuit when it falls below 50 ohm, and the controller would see the fault current of less than 0.9 mA.
Because each channel has its own isolation, a fault on one valve loop does not disturb the other. With a current consumption of 70 mA at 24 V and 1.6 W dissipation for the whole module, the heat load per valve is only 0.8 W, which helps in cabinets with high ambient temperature.
Plan the HART multiplexer or asset-management connection ahead of time. The digital band of 500 Hz to 10 kHz passes the HART frequency shift keying signal, so a handheld communicator can usually be connected at the safe-area terminals.
Documents and quotation
Request the MTL4500 and MTL5500 dataset for the circuit and approval details. Send your RFQ stating MTL5549, quantity and delivery point, and mention if the Y variant is needed.
Typical Questions From Maintenance Teams
Maintenance engineers replacing a MTL MTL5549 usually ask whether the new unit is a direct fit, whether settings can be copied from the old one, and whether any accessories must be ordered separately. The answer depends on the exact order code and the generation of the installed isolator & barrier, so the nameplate details are the best starting point. Send them with your request and we will check the match, point out any differences in connections or options, and list the parts needed so that the job can be finished in one visit.
Datasheets & Documents
- Datasheet MTL MTL5549 Two-Channel HART Isolating Driver Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.
Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.
MTL (Eaton) company profile
| Founded | 1971, Luton, England, as Measurement Technology Ltd |
|---|---|
| Origin | Spin-off from Kent Instrumentation |
| Headquarters | Luton, England |
| Ownership | Eaton (Crouse-Hinds), via Cooper Industries from 2008 |
| Product families | MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points |
Milestones
- 1971: Measurement Technology Ltd is founded in Luton.
- 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
- 2008: Cooper Industries acquires MTL Instruments for £144 million.
- 2012: Eaton acquires Cooper Industries.
MTL product families listed here
Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.
Where MTL barriers and isolators are used
These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.
MTL (Eaton) products we list
Ordering MTL modules: what we need
Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.
Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.
Browse MTL (Eaton) products by category: Isolator & Barrier, Automation Software.
FAQ
Questions about the MTL MTL5549 Two-Channel HART Isolating Driver
Answers from our engineering team on installation, compatibility and integration.
01How many I/P converters can one MTL5549 drive?
Two. The module accepts two floating 4-20 mA signals from the safe-area controller and drives two current-to-pressure converters or any other load up to 800 ohm in the hazardous area.
02What load range is allowed per channel?
The maximum load is 800 ohm, which is 16 V at 20 mA, and the minimum load is 90 ohm, with short-circuit detection below 50 ohm.
03How does the MTL5549 report field wiring faults?
If the field wiring opens or shorts, the current drawn at the safe-area terminals falls to a preset level, which a controller with readback detects. The datasheet gives less than 0.9 mA for both faults on the MTL5549.
04What is the difference between MTL5549 and MTL5549Y?
The MTL5549Y provides open-circuit detection only, with no short-circuit detection, and its open-circuit current is below 0.5 mA instead of 0.9 mA.
05What functional safety level applies to the MTL5549?
The module is SIL2 capable as a single device (HFT=0) and SIL3 capable in redundant configurations with hardware fault tolerance of 1.