Pepperl+Fuchs KFD2-SH-Ex1.T.OP Switch Amplifier SIL 3

Description

KFD2-SH-Ex1.T.OP: SIL 3 switch amplifier with an active voltage output

Emergency shutdown loops start with a contact or a proximity sensor that someone must trust. The Pepperl+Fuchs KFD2-SH-Ex1.T.OP reads an SN or S1N proximity sensor, or an approved dry contact, from a hazardous area and reproduces its state in the safe area on three outputs: an active, short-circuit-proof voltage output that feeds a logic input directly, a relay with a normally-open contact, and a second relay that signals faults.

The module is certified for use in safety functions up to SIL 3 according to IEC/EN 61508 with systematic capability SC 3, and up to performance level d according to EN/ISO 13849. For SIL 3, output I (the voltage output) must be used; for SIL 2, outputs I and II may both be used.

What the three outputs do

  • Output I, terminals 7+ and 8-: 0 V in the off state, 19 V at 15 mA up to 31 V at no load in the on state, 0 V on fault
  • Output II, terminals 9 and 10: relay with NO contact, 48 V AC/DC, 250 mA
  • Output III, terminals 11 and 12: relay for fault signalling, 48 V AC/DC, 250 mA
  • On a fault, the fault output and outputs I and II de-energise
  • Switching frequency up to 50 Hz on output I and up to 5 Hz on the relays

KFD2-SH-Ex1.T.OP data

Parameter Value
Supply 20 to 30 V DC on Power Rail or terminals 14+ and 15-; up to 100 mA
Dissipation / consumption 1.5 W / 1.7 W maximum
Input terminals 4+ and 6-
Open-circuit voltage / short-circuit current about 8.4 V / about 11.7 mA
Lead resistance up to 50 ohm
Relays de-energised / output off input current below 2.1 mA or above 5.9 mA
Relays energised / output on input current between 2.8 mA and 5.3 mA
Response delay 1 ms or less
Safe-side values Uo 9.56 V, Io 16.8 mA, Po 41 mW
Certificates PTB 00 ATEX 2041; TUV 99 ATEX 1493 X (Ex ec nC IIC T4 Gc); IECEx PTB 21.0010; IECEx TUN 19.0013X
Safety SIL 3, SC 3, PL d
Dimensions, mass 20 x 119 x 115 mm, housing B2, about 150 g
Ambient -20 to 70 degrees C, with derating conditions in the datasheet

Mechanical contacts need resistors

Unlike an SN/S1N proximity sensor, a mechanical contact must be fitted with a 10 kilohm resistor across it and a 1.5 kilohm resistor in series. These resistors let the module tell an open contact from a broken wire and a closed contact from a short circuit, and lead breakage and short circuit are monitored continuously. Omitting them will cause permanent fault indication.

KFD2-SH-Ex1.T.OP versus KFD2-SH-Ex1 and KHA6-SH-Ex1

KFD2-SH-Ex1.T.OP adds the active voltage output (the OP in the part number) and a separate fault relay to the principal switching function. The ordinary KFD2-SH-Ex1 type lacks that output pair, and the mains-powered KHA6-SH-Ex1 already on this catalogue is a different supply version. The T in the type designation indicates the fault output on terminals 11 and 12.

Applications

Position feedback of emergency shutdown valves, overspeed trip contacts on turbines, door interlocks on hazardous process enclosures and burner-flame supervision contacts commonly wire through such an amplifier, with the voltage output taken directly to a safety PLC digital input.

Proof testing and maintenance

Function-test the three outputs at the interval defined by the safety manual, by operating the field contact and checking that output I and relay II follow within a few milliseconds. Verify fault behaviour by disconnecting the field wiring. Keep records, as safety audits ask for them.

Temperature derating

The datasheet permits operation up to 70 degrees C subject to mounting conditions and derating curves. When modules are packed tightly on a Power Rail in a warm cabinet, fit spacing as instructed or derate the load.

Ordering

The OP suffix is essential. Do not substitute the plain SH-Ex1 for this part in a loop that relies on the voltage output. Quote the full part number.

Design checklist for a SIL 3 input channel

A safety designer working with this amplifier should confirm the sensor entity parameters against Uo 9.56 V, Io 16.8 mA and Po 41 mW, the cable capacitance and inductance, the loop resistance (maximum 50 ohm of lead resistance) and the logic solver input threshold against the 19 V minimum on-state level at 15 mA. The 0 V fault output ensures that a loss of supply or a detected line fault de-energises the safety input, producing a safe trip. Document the proof-test coverage claimed, and verify that any series resistors for mechanical contacts are mounted at the contact, not at the amplifier, to retain the monitoring of the whole cable.

Questions buyers ask about KFD2-SH-Ex1.T.OP

What safety level does KFD2-SH-Ex1.T.OP reach? The datasheet gives up to SIL 3 according to IEC/EN 61508 with SC 3, and PL d according to EN/ISO 13849.

Which output must be used for SIL 3 on KFD2-SH-Ex1.T.OP? Output I, the active voltage output on terminals 7+ and 8-, must be used for SIL 3; outputs I and II may be used up to SIL 2.

What input devices can connect to KFD2-SH-Ex1.T.OP? Proximity sensors of type SN or S1N, or approved dry contacts fitted with a 10 kilohm parallel resistor and a 1.5 kilohm series resistor.

What voltage does the active output of KFD2-SH-Ex1.T.OP provide? It gives 19 V at 15 mA up to 31 V at no load as 1-signal, and 0 V as 0-signal or fault.

How fast does KFD2-SH-Ex1.T.OP respond? The response delay is 1 ms or less, with switching frequencies up to 50 Hz on output I and 5 Hz on the relays.

Documents and quotation

The manufacturer datasheet for KFD2-SH-Ex1.T.OP accompanies this listing as a PDF so your engineers can verify terminals, ratings and approvals before purchase. Mention if the field device is a proximity sensor or a mechanical contact. To request a quotation, send the RFQ with the exact part number KFD2-SH-Ex1.T.OP, the quantity, the delivery location in Oman or the GCC and any project reference. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Datasheets & Documents
  • PDF Datasheet Pepperl+Fuchs KFD2-SH-Ex1.T.OP Switch Amplifier SIL 3 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFD2-SH-Ex1.T.OP Switch Amplifier SIL

Answers from our engineering team on installation, compatibility and integration.

01What safety level does KFD2-SH-Ex1.T.OP reach?
The datasheet gives up to SIL 3 according to IEC/EN 61508 with SC 3, and PL d according to EN/ISO 13849.
02Which output must be used for SIL 3 on KFD2-SH-Ex1.T.OP?
Output I, the active voltage output on terminals 7+ and 8-, must be used for SIL 3; outputs I and II may be used up to SIL 2.
03What input devices can connect to KFD2-SH-Ex1.T.OP?
Proximity sensors of type SN or S1N, or approved dry contacts fitted with a 10 kilohm parallel resistor and a 1.5 kilohm series resistor.
04What voltage does the active output of KFD2-SH-Ex1.T.OP provide?
It gives 19 V at 15 mA up to 31 V at no load as 1-signal, and 0 V as 0-signal or fault.
05How fast does KFD2-SH-Ex1.T.OP respond?
The response delay is 1 ms or less, with switching frequencies up to 50 Hz on output I and 5 Hz on the relays.