Brand: Weidmüller
Weidmuller 1176070000 ACT20M-CI-CO-ILP-S Passive Isolator
Description
Weidmuller 1176070000 ACT20M-CI-CO-ILP-S: loop-powered passive isolator
Weidmuller 1176070000 is the ACT20M-CI-CO-ILP-S, a passive isolator that takes its operating power from the 4 to 20 mA input loop instead of from an auxiliary supply. The datasheet calls it a 1-channel passive isolator with input current loop feed, converting a 0(4) to 20 mA input to a 0(4) to 20 mA output with 2-way isolation. Because no 24 V supply is needed, wiring is reduced to four conductors per channel, which is attractive when the cabinet has no spare supply terminals.
How the loop-powered 1176070000 works
The module draws its energy from the input loop, so some loop voltage is consumed: the input voltage must exceed 3 V at 20 mA and the voltage drop of the current input is given as 1.25 V plus 0.015 times the output voltage at 25 C. The designer must therefore verify that the source can provide enough compliance voltage, particularly with long cables or other devices in the loop. The output is an active current signal for loads up to 600 ohm at a maximum of 23 mA. Accuracy is better than 0.1 percent of the measuring range, step response is given as 5 ms and 0.5 ms, power consumption is only 30 mW (0.05 VA nominal), and the cut-off frequency is 100 Hz. The housing is 6.1 mm wide, 112.5 mm high and 114.3 mm deep and weighs 80 g.
Technical data for 1176070000
| Parameter | Value |
|---|---|
| Order No. / Type | 1176070000 / ACT20M-CI-CO-ILP-S |
| Version | Passive isolator, input current loop feed, 1 channel |
| Input | current source, 0(4) to 20 mA |
| Input voltage requirement | more than 3 V at 20 mA |
| Voltage drop | 1.25 V plus 0.015 times output voltage at 25 C |
| Output | active current 0(4) to 20 mA; 600 ohm at 23 mA |
| Accuracy | less than 0.1 percent of range |
| Step response | 5 ms and 0.5 ms |
| Supply | loop powered through the 4-20 mA input |
| Power consumption | 30 mW; 0.05 VA nominal |
| Isolation | 2-way; 2.5 kV rms for 1 min; 300 V rms |
| Configuration | none |
| Dimensions / weight | 6.1 x 112.5 x 114.3 mm / 80 g |
| Ex marking | II 3 G Ex nA IIC T4 Gc, zone 2 |
| Altitude | up to 2000 m |
| MTBF (as stated) | 699 a |
| Approvals | cULus E337701 |
How 1176070000 differs from other ACT20M isolators
Compared with the ACT20M-CI-CO-S (1175980000) there is no auxiliary supply, only two-way isolation (input to output) instead of three-way, and 0.1 percent accuracy instead of 0.05 percent. Compared with the configurable ACT20M-AI-AO-S (1176000000) there is neither a sensor supply nor voltage signal capability. It is the cheapest-to-wire option and ideal for retrofit situations in which an existing loop has to be isolated without adding supply cabling.
Typical uses of the 1176070000 module
Use it to isolate existing 4 to 20 mA loops into a second system such as a monitoring PLC, a data logger or a historian, with no extra supply. Maintenance departments in the Gulf use passive isolators during plant modifications when a new system must receive an existing signal and the grounding schemes differ.
Installation advice for 1176070000
Calculate the total loop voltage budget before installing. Add the isolator drop, the cable resistance, the other receivers and the transmitter minimum voltage, and compare the sum to the available supply. Wire with up to 2.5 mm² on screw terminals at 0.4 to 0.6 Nm. Fit it on a TS 35 rail in a zone 2 or safe-area cabinet.
Notes on maintenance
With only 30 mW of dissipation the module stays cool. If a loop starts to read low after installing the isolator, the loop compliance voltage is the first thing to check.
Loop voltage budget example for 1176070000
Suppose a 4 to 20 mA signal is generated by a transmitter that supplies loop power from 24 V. At 20 mA the isolator needs more than 3 V at the input, and the drop equals 1.25 V plus 0.015 times the output voltage, with the output voltage given by the load resistance times the current. With a 250 ohm receiver at 20 mA the output voltage is 5 V, so the drop is about 1.33 V. Add the cable drop of perhaps 0.5 V and the isolator needs well under the margin of a 24 V loop, but a source that only provides 12 V of compliance leaves little reserve once other devices are added. This is the check to make before choosing a passive isolator.
Passive isolators are also helpful when no supply exists in the field junction box, because the module takes only a few milliwatts and never needs a fuse or supply rail. The price paid is that the module cannot provide a sensor supply, cannot convert voltage signals and offers a slightly lower accuracy of 0.1 percent.
Specification points to confirm for 1176070000
Before ordering, confirm the following from the datasheet: the signal range is 0 to 20 mA or 4 to 20 mA on both sides, the load is 600 ohm or less, the ambient is within the stated range, and the cabinet is a safe area or zone 2. The datasheet quotes the insulation voltage as 2.5 kV rms for one minute with a rated voltage of 300 V rms and pollution severity 2. These values define the safe working range and should be copied into the loop sheet. Also note that the housing is an add-on module for TS 35 rail mounting, supplied with screw terminals for 2.5 mm² nominal cross-section.
Documents and quotation
The datasheet for 1176070000 is supplied with this page. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Send an RFQ with 1176070000, quantity and delivery location for a quotation.
What to Include in Your Weidmüller 1176070000 Enquiry
An accurate quotation for the Weidmüller 1176070000 depends on a few details. Please share the complete part number, any suffix codes for options or approvals, the operating conditions at the installation point, and whether certificates of conformity or test reports must ship with the goods. It also helps to know whether the unit is for planned maintenance, a shutdown or an urgent breakdown, because that decides how it is sourced and shipped. With this information our team can check compatibility with your existing isolator & barrier and reply with availability and a realistic delivery estimate.
Spares and Lifecycle Considerations
For critical service, many plants hold one Weidmüller 1176070000 as an operational spare rather than waiting for a failure. When you plan spares, look at how many identical isolator & barrier units are installed, how long a replacement would take to arrive, and the cost of an unplanned stop. Store spare units in their original packaging in a dry, temperature-controlled area and record the part number and serial number in your maintenance system. We can quote single units or a small spares package and confirm the lead time for each item in writing.
Other Models in the Act20m Range
Seven Star LLC supplies models from the Act20m range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Weidmuller 1175980000 ACT20M-CI-CO-S Signal Isolator | Isolator & Barrier | View details |
| Weidmuller 1176030000 ACT20M-UI-AO-S Temperature Converter | Isolator & Barrier | View details |
| Weidmuller 1176070000 ACT20M-CI-CO-ILP-S Passive Isolator | Isolator & Barrier | You are viewing this model |
| Weidmuller 1176000000 ACT20M-AI-AO-S Isolating Amplifier | Isolator & Barrier | View details |
Datasheets & Documents
- Datasheet Weidmuller 1176070000 ACT20M-CI-CO-ILP-S Passive Isolator Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Weidmüller is a German family-owned maker of electrical connection and industrial electronics products, headquartered in Detmold. The company dates from 1850 and was re-established in Detmold in 1948; it specialised in terminal blocks from the 1940s onward. Weidmüller makes Klippon terminal blocks, power supplies, remote I/O and enclosures, and reported over one billion euros in revenue in 2023.
Seven Star LLC lists Weidmüller PRO MAX power supplies and SAK terminal blocks, and supplies Weidmüller components to panel shops and plants in Oman and the GCC.
Weidmüller company profile
| Founded | 1850, Germany |
|---|---|
| Headquarters | Detmold, Germany (since 1948) |
| Ownership | Family-owned |
| Revenue | Over €1 billion (2023) |
| Product families | Klippon Connect terminal blocks, PRO MAX and PRO TOP power supplies, u-remote I/O and fieldbus couplers, Klippon enclosures, connectors and tools |
Milestones
- 1850: Weidmüller is founded.
- 1948: The company is re-established in Detmold.
Weidmüller products listed here
The listed power supplies are DIN rail switch-mode units with 24 V DC output: a PRO MAX single-phase unit rated 180 W and 7.5 A (85 to 277 V AC input), and a PRO MAX3 three-phase unit rated 240 W and 10 A (320 to 575 V AC input). The SAK series is the screw clamp feed-through terminal block family found in many existing panels. Weidmüller now flags several SAK types as being phased out and names a replacement for some of them.
Weidmüller products we list
Ordering Weidmüller parts: what we need
Weidmüller identifies every item by a ten-digit order number, and that number is the surest way to quote. Without it, send the type printed on the part. For power supplies add input voltage and phases, output voltage and current. For terminal blocks add the conductor cross-section, color, and the end plates, cross-connections and markers you need, since accessories are specific to each series.
Facts checked against Weidmüller milestone lists and distributor profiles, October 2026.
Browse Weidmüller products by category: Electrical & Power Modules.
FAQ
Questions about the Weidmuller 1176070000 ACT20M-CI-CO-ILP-S Passive
Answers from our engineering team on installation, compatibility and integration.
01Does 1176070000 need a power supply?
No. It is loop powered through the 0(4) to 20 mA input, with power consumption of 30 mW.
02What loop voltage does it need?
The input needs more than 3 V at 20 mA; the voltage drop is 1.25 V plus 0.015 times the output voltage at 25 C.
03What is its accuracy?
Less than 0.1 percent of the measuring range, with step response times of 5 ms and 0.5 ms.
04How many isolation paths?
It is a 2-way isolator, with 2.5 kV rms for 1 minute between input and output.
05Is it approved for zone 2?
The marking is II 3 G Ex nA IIC T4 Gc, so installation in safe area or zone 2 is allowed.