Brand:

Pepperl+Fuchs KFD2-USC-1.D Signal Converter with Trip Value

Description

KFD2-USC-1.D universal current and voltage signal converter with trip relay

The KFD2-USC-1.D is a configurable isolator for standard analog signals. It accepts a current, voltage or millivolt input from a field device, converts and scales it into a current or voltage output for the control system, and adds a relay contact that works as a trip value switch. A display and a front keypad let a technician set the ranges on site, with no configuration cable or PC needed.

Seven Star LLC supplies the KFD2-USC-1.D in Oman and the GCC as an independent supplier in Muscat. The sections below show where the converter belongs, what its measurement limits are and what to settle before ordering.

KFD2-USC-1.D designation and intended use

The KFD2-USC-1.D is a type designation of the Pepperl+Fuchs K-System, and the datasheet names it a signal converter with trip value, 1-channel, 24 V DC supply through the Power Rail. The display-and-keypad configuration is part of the feature list. The manufacturer states that the device provides isolation for non-intrinsically safe applications, which is an important limit: the module is for the safe area and does not replace an intrinsically safe barrier.

The input ranges named on the datasheet are 0 to 20 mA, 0 to 10 V and 0 to 60 mV, and any sub-range of these can be selected. Outputs are 0/4 to 20 mA, 0/2 to 10 V or 0/1 to 5 V.

Technical specifications of the KFD2-USC-1.D

Parameter Specification
Manufacturer / part number Pepperl+Fuchs / KFD2-USC-1.D
Function Signal converter with trip value, 1 channel, galvanic isolation, safe area
Input Current 0 … 20 mA (terminals 2+, 3-); voltage 0 … 10 V or 0 … 60 mV (terminals 1+, 3-)
Input resistance Voltage: 1 MΩ; current: max. 100 Ω
Input limit 30 V
Resolution 15 bit
Analog output 0/4 … 20 mA (load max. 550 Ω) or 0/1 … 5 V, 0/2 … 10 V (load min. 1 kΩ)
Relay output 250 V AC / 2 A / cos φ 0.7; 40 V DC / 2 A; mechanical life 2 x 107 cycles
Accuracy Deviation 0.1 % of full scale
Temperature drift 0.003 %/K (30 ppm)
Reaction time ≥ 150 ms / ≤ 300 ms
Supply 20 … 30 V DC, ≤ 80 mA, power consumption ≤ 1.6 W
Isolation Input/output, input/supply, output/supply: reinforced insulation, 300 V rms (IEC/EN 61010-1)
Ambient temperature -20 … 60 °C
Housing Type B2, 20 x 119 x 115 mm, approx. 150 g, 35 mm DIN rail, IP20

How the KFD2-USC-1.D converts and monitors a signal

The input stage digitizes the field signal at 15 bit resolution and the converter rescales it to the output range chosen at the keypad. Because the output ranges and the input sub-ranges are independent, the same module can convert a 4-20 mA transmitter signal into 1-5 V for an old recorder, or turn a 0-10 V position feedback into a 4-20 mA value for a PLC card. A line fault detection function monitors the field wiring.

The relay works as a trip value contact. The user sets the switching threshold, and the display can show the process value in engineering units, which makes the module useful as a local indicator-and-alarm point as well as an isolator. The datasheet quotes a reaction time of not more than 300 ms, so the relay is suited to alarming, not to fast protection.

All three circuits, input, outputs and supply, are separated by reinforced insulation rated at 300 V rms, which protects the receiving system from common-mode voltages and ground loops between the plant and the control room.

Where the KFD2-USC-1.D fits

The module belongs to the display-and-keypad branch of the K-System, alongside the KFD2-GUT-1.D temperature converter, the KFD2-UFC-1.D frequency converter and the KFD2-CRG2-1.D transmitter supply. All of them share the same family of Power Rail, KFD2-EB2 power feed and K-DUCT wiring accessories.

Use the KFD2-USC-1.D when the field device is a non-Ex source that already has its own power: a drive output, a variable-speed signal, a mV shunt or an analog output from a package unit. When the field device needs loop power, the KFD2-CRG2-1.D or the STC5 transmitter supplies are the right choice.

Selection and ordering checklist for the KFD2-USC-1.D

  • Define the input signal type and range: current, voltage or millivolt
  • Define the required output signal and check the 550 Ω current or 1 kΩ voltage load limits
  • Specify the trip value and the relay contact rating needed
  • Confirm that the application is in the safe area, since the module is not for intrinsically safe circuits
  • Confirm the 20 to 30 V DC supply and rail arrangement
  • Confirm the cabinet ambient range against -20 to 60 °C

Setting up and maintaining the KFD2-USC-1.D

After mounting and wiring, set the input range, output range, scaling and trip point with the keypad. Check the line fault behaviour against the plant philosophy and verify the relay state during start-up and when power is lost. Record the settings on the loop sheet because a replacement module will need the same configuration.

For maintenance, use a calibrator at the input and verify the output and the relay threshold. With a deviation limit of 0.1 % of full scale, periodic verification only needs to be as frequent as the plant instrument policy requires.

Typical applications in Oman and the GCC

Typical places for a converter of this type include utilities and packaged equipment where drives, rectifiers or analyser panels deliver 0-10 V or 4-20 mA signals to a plant control system, and boiler and water treatment systems where a local alarm contact is needed at a measured value. In Gulf cabinets the 60 °C upper ambient limit of this module is lower than some other K-System modules, so confirm the actual cabinet temperature.

KFD2-USC-1.D and related display-type K-System modules

Based on the manufacturer datasheets.

Part number Input Outputs Width
KFD2-USC-1.D mA, V or mV Analog output and 1 relay 20 mm
KFD2-GUT-1.D RTD, thermocouple, potentiometer, voltage Analog output and 2 relays 40 mm
KFD2-UFC-1.D Frequency 1 mHz … 10 kHz Analog output, 2 relays, 1 transistor 40 mm
KFD2-CRG2-1.D Loop-powered 0/4 … 20 mA Analog output and 2 relays 40 mm

Information to send with an RFQ for the KFD2-USC-1.D

Provide these details for a quick quotation.

  • Input and output signal types and ranges
  • Trip value and relay requirement
  • Whether a display and keypad variant (.D) is required
  • Quantity and delivery date

Documents and quotation

The manufacturer datasheet for the KFD2-USC-1.D is attached on this page, so the electrical data, terminal assignment and ambient limits quoted above can be checked against the original document before an order is placed.

Seven Star LLC supplies Pepperl+Fuchs products in Oman and the GCC as an independent supplier in Muscat. Send the quantity, the signal types and the project delivery date, and we will confirm availability and lead time in a written quotation.

Other Models in the Pf Kfd2 D Series Range

Seven Star LLC supplies models from the Pf Kfd2 D Series range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Pepperl+Fuchs KFD2-USC-1.D Signal Converter with Trip ValueIsolator & BarrierYou are viewing this model
Pepperl+Fuchs KFD2-GUT-1.D Temperature Converter, 2 RelaysIsolator & BarrierView details
Pepperl+Fuchs KFD2-UFC-1.D Frequency Converter with Trip ValuesIsolator & BarrierView details
Datasheets & Documents
  • PDF Datasheet Pepperl+Fuchs KFD2-USC-1.D Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFD2-USC-1.D Signal Converter with

Answers from our engineering team on installation, compatibility and integration.

01What input signals does the KFD2-USC-1.D accept?
The datasheet lists 0 to 20 mA, 0 to 10 V and 0 to 60 mV, with selectable sub-ranges of these.
02Can it be used in intrinsically safe circuits?
No. The manufacturer describes it as providing isolation for non-intrinsically safe applications. For intrinsically safe loops an appropriate barrier is needed.
03What is the relay rating?
250 V AC / 2 A at cos phi 0.7 and 40 V DC / 2 A, with a mechanical life of 2 x 10 to the power 7 cycles.
04How is it configured?
By the keypad and display on the front of the unit, which also shows the measured value in selectable physical units.
05What accuracy is stated?
The datasheet gives a deviation of 0.1 % of full-scale value and a temperature influence of 0.003 %/K.