Schneider Electric LRD3365 TeSys 80-104 A Overload Relay

Description

LRD3365 thermal overload relay for 80 to 104 A motors

The LRD3365 is a Schneider Electric product listed in the datasheet as: TeSys LRD thermal overload relays – 80 to 104 A – class 10A. In a motor starter it is the part that watches the current of the motor and opens the control circuit when an overload or a lost phase would otherwise overheat the windings. Seven Star LLC supplies the LRD3365 in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference: the datasheet identifies the LRD3365 as part of the TeSys LRD family, and the title gives the figure that matters, namely the adjustable window of 80 to 104 A with thermal class 10A. It is built as the largest frame in this group (70 mm wide) used with LC1D80 and LC1D95 contactors. The 80 to 104 A range is the top of the LRD3 frame in this group and pairs with the LC1D80 and LC1D95 contactors. It suits large motors whose nameplate current lies between 80 and 104 A.

Technical specifications of the LRD3365

Parameter Specification
Manufacturer / part number Schneider Electric / LRD3365
Description TeSys LRD thermal overload relays – 80 to 104 A – class 10A
Range TeSys
Product name TeSys LRD; TeSys Deca
Product or component type Differential thermal overload relay
Relay application Motor protection
Thermal overload class Class 10A conforming to IEC 60947-4-1
Thermal protection adjustment range 80 to 104 A
Tripping threshold 1.14 ± 0.06 Ir conforming to IEC 60947-4-1
Phase failure sensitivity Tripping current 130 % of Ir on two phase, the last one at 0
Network type / frequency AC; DC / 0 to 400 Hz
Rated operational voltage [Ue] 1000 V AC 0 to 400 Hz for power circuit conforming to IEC 60947-4-1
Rated insulation voltage [Ui] Power circuit: 1000 V conforming to IEC 60947-4-1; Power circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL
Rated impulse withstand [Uimp] 6 kV conforming to IEC 60947-1
Auxiliary contact composition 1 NO + 1 NC
Signalling circuit permissible current 0.72 A at 500 V AC-15 for signalling circuit; 0.06 A at 440 V DC-13 for signalling circuit
Associated fuse (signalling circuit) 4 A gG for signalling circuit; 4 A BS for signalling circuit
Product compatibility LC1D80, LC1D95
Mounting support Plate, with specific accessories; Rail, with specific accessories; Under contactor
Temperature compensation -20 to 60 °C
Power circuit connection screw clamp terminals 1 cable 4 to 35 mm² flexible without cable end; screw clamp terminals 1 cable 4 to 35 mm² flexible with cable end; screw clamp terminals 1 cable 4 to 35 mm² solid without cable end
Tightening torque Control circuit: 1.7 N.m – on screw clamp terminals; Power circuit: 9 N.m – on screw clamp terminals
Dimensions (W x H x D) 70 mm x 81 mm x 115 mm
Net weight 0.51 kg
IP degree of protection IP20 conforming to IEC 60529
Ambient air temperature (operation) -20 to 60 °C without derating conforming to IEC 60947-4-1
Ambient air temperature (storage) -60 to 70 °C
Flame retardance V1 conforming to UL 94
Product certifications IEC; UL; CSA; CCC; EAC; ATEX INERIS; UKCA

Contactors and mounting for the LRD3365

The datasheet lists the contactors compatible with the LRD3365 as LC1D80, LC1D95. The mounting options are plate, with specific accessories; rail, with specific accessories; under contactor. In practice the relay plugs straight under a TeSys Deca contactor of the listed frames, so the contactor and relay together form a compact direct-on-line or reversing starter without extra wiring in the power circuit.

The relay body measures 70 mm wide, 81 mm high and 115 mm deep and weighs 0.51 kg. It belongs to the largest frame in this group (70 mm wide) used with LC1D80 and LC1D95 contactors. The setting range climbs past 100 A, so the associated power cables, short-circuit protective device and contactor rating must all be checked together; the relay only protects against overload, not short circuits.

Where the LRD3365 is used in Oman and the GCC

The largest frame in this group is used for big utility motors, such as main cooling-water pumps and large ventilation or process fans, where the starter is a major item in the panel. In Oman and the GCC such starters appear in water and desalination plants, oil and gas auxiliaries, power station balance-of-plant and building services.

Heat and dust are the main enemies. Overload relays are temperature-compensated, but a hot, dusty panel still ages terminals and contacts faster, so inspect the connections of the LRD3365 during planned shutdowns and keep the front cover and dial clean.

How the LRD3365 reacts to overload

The setting dial of the LRD3365 covers 80 to 104 A. The datasheet gives the tripping threshold as 1.14 ± 0.06 Ir conforming to IEC 60947-4-1, which means the relay is built to trip when the motor current reaches about 1.14 times the dialled value, with a tolerance of 0.06 times. At the top of the scale, 1.14 times 104 A works out to about 118.56 A; at the bottom of the scale, 1.14 times 80 A is about 91.2 A.

The relay is also a differential type. For the phase failure case, the datasheet states a tripping current of 130 % of Ir on two phases while the third carries nothing, which at 104 A corresponds to about 135.2 A in the two live phases. This sensitivity is what protects a three-phase motor from running on two phases after a blown fuse or a loose terminal, and it is the reason the type is chosen over a simple thermal element for pumps and fans.

Class 10A is the common choice for motors that start quickly. Under IEC 60947-4-1 the class number is the longest tripping time in seconds at 7.2 times the setting current, so a class 10A relay reacts faster to a locked rotor than a class 20 relay. The relay has temperature compensation over -20 to 60 °C, so the setting does not drift within that band.

Before ordering the LRD3365

  • Motor nameplate current: it must sit between 80 and 104 A, ideally in the middle of the dial.
  • Contactor: the starter must use one of LC1D80, LC1D95.
  • Trip class: this relay is class 10A; confirm that it suits the starting time of the load.
  • Signalling circuit: the contact is rated 0.72 A at 500 V AC-15 for signalling circuit; 0.06 A at 440 V DC-13 for signalling circuit.
  • Space: allow 70 mm x 81 mm x 115 mm and a weight of 0.51 kg.
  • Status: say whether you need a spare for an existing starter or a new installation.

Neighbouring ranges around the LRD3365

The table below places the LRD3365 between its neighbours by current range, using the datasheet data of each reference. It helps when the nameplate current falls near a boundary or when the contactor decides the frame.

Reference Setting range Thermal class Listed contactors Width x height x depth
LRD365 48 to 65 A Class 10A LC1D50A, LC1D65A 55 mm x 70 mm x 123 mm
LRD3363 63 to 80 A Class 10A LC1D80, LC1D95 70 mm x 81 mm x 115 mm
LRD3365 80 to 104 A Class 10A LC1D80, LC1D95 70 mm x 81 mm x 115 mm

Testing and servicing the LRD3365

Set the dial of the LRD3365 to the nameplate current of the motor, not to the contactor rating. Press the red stop push-button to confirm that the contactor drops, then use the blue reset push-button to restore the relay. The relay should be checked after any short-circuit event, because a short-circuit protective device is still needed upstream; the overload relay does not replace it.

For spares, keep the same reference rather than guessing from the range, because the frame and the terminals differ between the compact, large and largest groups. If you need a relay for a different current, send us the contactor reference and the nameplate current and we will confirm the correct member of the family.

Information to send with an RFQ for the LRD3365

  • Full reference LRD3365 and the quantity required
  • Motor nameplate current, voltage and power
  • Contactor reference the relay will be fitted to
  • Required delivery location and timing
  • Whether it is a spare, a replacement or a new installation

Documents and quotation

A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it is the document to check against your own drawings.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Lrd F3 Range

Seven Star LLC supplies models from the Se Lrd F3 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric LRD3363 TeSys 63-80 A Overload RelayContactors & Overload RelaysView details
Schneider Electric LRD3365 TeSys 80-104 A Overload RelayContactors & Overload RelaysYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric LRD3365 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric LRD3365 TeSys 80-104 A Overload

Answers from our engineering team on installation, compatibility and integration.

01What current range does the LRD3365 cover?
The datasheet gives a thermal protection adjustment range of 80 to 104 A with class 10A tripping, so the motor nameplate current should fall inside that window.
02Which contactors can the LRD3365 be mounted on?
The datasheet lists LC1D80, LC1D95. The relay mounts under the contactor and can also be used on a plate or rail with specific accessories.
03How does the LRD3365 react to a lost phase?
It is a differential relay. The datasheet states a tripping current of 130 % of Ir on two phases with the third at zero, in addition to the 1.14 +/- 0.06 Ir overload threshold.
04What auxiliary contacts does the LRD3365 have?
The datasheet lists 1 NO + 1 NC, with a signalling-circuit rating of 0.72 A at 500 V AC-15 for signalling circuit; 0.06 A at 440 V DC-13 for signalling circuit. The normally closed contact is normally wired into the contactor coil circuit.
05What are the size and weight of the LRD3365?
The datasheet gives 70 mm wide, 81 mm high, 115 mm deep and a net weight of 0.51 kg.