Schneider Electric CAD50MD TeSys D Relay 5NO 220V DC

Description

CAD50MD control relay with a 220 V DC coil

Control circuits that need five switching points from one command often turn to the CAD50MD, a Schneider Electric TeSys Deca control relay with five normally open contacts and a 220 V DC coil. The manufacturer describes it as: TeSys D control relay – 5 NO – up to 690 V – 220 V DC standard coil. Seven Star LLC supplies the CAD50MD in Oman and the GCC as an independent supplier based in Muscat.

The code is easy to decode once you know the pattern. CAD50 sets the five-pole contact block (five normally open contacts), the letter M marks 220 V, and the closing D marks a standard DC coil. The datasheet confirms this reference as a 220 V DC coil version.

Using five normally open contacts on the CAD50MD

Choose it when a single initiating contact, for example a PLC output or a protection relay trip contact, has to be repeated on five independent circuits: alarm annunciation, a shutdown loop, a remote indication, an interlock to another panel and a counter or logger. If any of those circuits needs a contact that opens when the relay operates, the 3 NO + 2 NC member of the family is the right choice instead.

Contact data from the datasheet apply to all five poles: 10 A conventional thermal current at 60 °C, utilisation categories AC-15, AC-14 and DC-13, a rated operational voltage up to 690 V AC, and a minimum switching capability of 17 V and 5 mA, which makes the contacts suitable for low-level signals as well as for 24 V PLC inputs.

Datasheet values for the CAD50MD

Parameter Specification
Manufacturer / part number Schneider Electric / CAD50MD
Range / type TeSys Deca control relay (TeSys CAD)
Pole contact composition 5 NO
Utilisation categories DC-13; AC-15; AC-14
Rated operational voltage (Ue) ≤ 690 V AC 25 to 400 Hz
Control circuit voltage (Uc) 220 V DC
Control voltage limits 0.1 to 0.25 Uc (-40 to 70 °C):drop-out DC; 0.7 to 1.25 Uc (-40 to 60 °C):operational DC; 1 to 1.25 Uc (60 to 70 °C):operational DC
Operating time 53 to 72 ms coil energisation and NO closing; 16 to 24 ms coil de-energisation and NO opening
Inrush / hold-in power 5.4 W (at 20 °C) / 5.4 W at 20 °C
Thermal current (Ith) 10 A (at 60 °C)
Rated making capacity 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1
Associated fuse 10 A gG conforming to IEC 60947-5-1
Insulation voltage (Ui) 690 V IEC 60947-5-1; 600 V UL and CSA
Mechanical durability / rate 30 Mcycles / 180 cyc/mn
Mounting / terminals DIN rail or plate; screw clamp 1 to 4 mm², 1.7 N.m
Dimensions (H x W x D) 77 mm x 45 mm x 93 mm
Net weight 0.58 kg
Degree of protection IP2X front face conforming to VDE 0106
Ambient temperature, operation -40 to 60 °C; 60 to 70 °C with derating
Ambient temperature, storage -60 to 80 °C
Certifications CB; CCC; UL; CSA; EAC; CE; UKCA

How the 220 V DC coil of the CAD50MD behaves

The coil is the one part that distinguishes the CAD50MD from its siblings, so it deserves the closest reading.

A 220 V DC coil belongs to older or larger power-station and substation designs that use a 220 V battery system for control. Several power and desalination plants in the Gulf were built that way, and spare control relays for such boards are still requested years after the original supply. The datasheet coil power of 5.4 W is about 24.5 mA at 220 V, a very light load on a battery of that size.

At 220 V the operating window of 0.7 to 1.25 Uc is about 154 to 275 V and the drop-out band of 0.1 to 0.25 Uc is about 22 to 55 V. The higher voltage makes coil suppression more important, because a DC coil at 220 V releases a lot of energy on opening and can damage the contact of whatever device interrupts it. Use a suppressor suited to the voltage, and keep the wiring of this coil clearly separated and labelled from any 24 V circuits in the same panel.

The datasheet gives operating times of 53 to 72 ms coil energisation and NO closing, 16 to 24 ms coil de-energisation and NO opening. The DC coil closes in 53 to 72 ms and opens in 16 to 24 ms, with a time constant of 28 ms, which is slower than an AC coil and should be kept in mind in tight timing circuits.

Installation and maintenance of the CAD50MD

Fit the relay in an enclosure with the front face reachable for inspection: the datasheet quotes IP2X at the front face, which protects against finger contact but not against dust. The weight of 0.58 kg is modest, so the relay is held securely by its rail clip, but plate mounting is preferable on machines with strong vibration. The datasheet lists vibration resistance of 2 Gn open and 4 Gn closed (5 to 300 Hz) and shock resistance of 10 Gn open and 15 Gn closed for 11 ms.

For spares planning, the CAD50MD is a good candidate for a stocked spare because it is physically identical to its siblings and the coil is the only part that differs. Mark the coil voltage clearly on the terminal block door or on the panel diagram, test it after any control-supply change, and keep a record of the coil code. The datasheet gives an 18-month warranty from the manufacturer, which applies to the product as supplied by its own channel.

Typical applications for the CAD50MD in the region

A 110, 125 or 220 V DC coil is a substation and power-plant part. In the utilities, desalination plants and large industrial sites of the region, the station battery feeds protection and control, and a multiplying relay of this kind repeats trip, alarm and interlock signals inside switchgear panels and relay rooms. It is a natural spare for outage planning, because panel relays at that voltage are hard to buy quickly when a shutdown is under way.

For the CAD50MD, that means five normally open contacts from one 220 V DC command, sitting next to LC1D contactors of the same TeSys D family on the same rail.

Checks before ordering the CAD50MD

  • Coil: 220 V DC, confirmed from the supply drawing or the nameplate of the relay being replaced.
  • Contacts: five normally open contacts, matched to the interlock and signalling circuits.
  • Supply sizing: about 24.5 mA continuously, because the datasheet gives the same power for inrush and hold-in (derived figure).
  • Window: operates within 154 to 275 V (0.7 to 1.25 Uc) and releases at 22 to 55 V (0.1 to 0.25 Uc).
  • Contact load of the CAD50MD: 10 A thermal, AC-15, AC-14 or DC-13 duties; use a contactor for motor-power loads.
  • Space: 77 mm high, 45 mm wide and 93 mm deep.
  • Environment: operation up to 60 °C, up to 70 °C with derating; storage -60 to 80 °C.

Related references to the CAD50MD

The CAD50MD is one member of a family of TeSys D control relays that share the housing, the contact data and the mounting. Only the coil voltage and type change from one reference to the next, together with the contact arrangement: the CAD32 series is 3 NO + 2 NC and the CAD50 series is 5 NO. The table lists the CAD50 references we are asked for most.

If the supply is not in the table, ask us; the CAD32 series has the other contact arrangement. AC-coil versions are 84 mm deep and DC-coil versions 93 mm, which matters in a shallow enclosure.

Reference Coil voltage and type Contacts
CAD50B7 24 V AC 50/60 Hz 5 NO
CAD50BD 24 V DC standard 5 NO
CAD50BL 24 V DC low consumption 5 NO
CAD50E7 48 V AC 50/60 Hz 5 NO
CAD50FD 110 V DC standard 5 NO
CAD50GD 125 V DC standard 5 NO
CAD50MD (this page) 220 V DC standard 5 NO
CAD50P7 230 V AC 50/60 Hz 5 NO
CAD50U7 240 V AC 50/60 Hz 5 NO

What to include when you request a quote for the CAD50MD

  • Delivery location in Oman or the GCC and the date required
  • Panel or machine the relay must fit, and whether it is a spare, a replacement or a new installation
  • The load or circuit each contact will switch (voltage, current, signal level)
  • The coil voltage and type seen on the supply drawing or on the old relay nameplate
  • Full reference CAD50MD and the quantity

Documents and quotation

A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it is worth reading beside the panel drawing before you order.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Cad50 Range

Seven Star LLC supplies models from the Se Cad50 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric CAD50B7 TeSys D Relay 5NO 24V ACContactors & Overload RelaysView details
Schneider Electric CAD50BD TeSys D Relay 5NO 24V DCContactors & Overload RelaysView details
Schneider Electric CAD50BL TeSys D Relay 5NO 24VDC Low PowerContactors & Overload RelaysView details
Schneider Electric CAD50E7 TeSys D Relay 5NO 48V ACContactors & Overload RelaysView details
Schneider Electric CAD50FD TeSys D Relay 5NO 110V DCContactors & Overload RelaysView details
Schneider Electric CAD50GD TeSys D Relay 5NO 125V DCContactors & Overload RelaysView details
Schneider Electric CAD50MD TeSys D Relay 5NO 220V DCContactors & Overload RelaysYou are viewing this model
Schneider Electric CAD50P7 TeSys D Relay 5NO 230V ACContactors & Overload RelaysView details
Schneider Electric CAD50U7 TeSys D Relay 5NO 240V ACContactors & Overload RelaysView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric CAD50MD Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric CAD50MD TeSys D Relay 5NO 220V DC

Answers from our engineering team on installation, compatibility and integration.

01What coil does the CAD50MD have?
The datasheet lists a 220 V DC standard DC coil. The operational window is 154 to 275 V and drop-out is 22 to 55 V.
02How many contacts does the CAD50MD have?
It has five normally open contacts, with a 10 A conventional thermal current at 60 °C and utilisation categories AC-15, AC-14 and DC-13.
03How much power does the coil of the CAD50MD draw?
The datasheet gives 5.4 W for inrush and for hold-in. At 220 V that is about 24.5 mA both at pull-in and held in, derived from the stated power.
04What are the dimensions and weight of the CAD50MD?
77 mm high, 45 mm wide and 93 mm deep, with a net weight of 0.58 kg. It mounts on a DIN rail or a plate.
05Can the CAD50MD work in a hot panel?
Operation is listed from -40 to 60 °C, and up to 70 °C with derating; storage is -60 to 80 °C. Altitude is 0 to 3000 m.