Schneider Electric A9F94102 iC60L 1P 2A C Breaker

Description

A9F94102: single-pole 2 A C-curve iC60L breaker

The A9F94102 is a Schneider Electric Acti9 iC60L miniature circuit breaker, listed as iC60L – miniature circuit breaker – 1P – 2A – C curve. The datasheet describes a 1P thermal-magnetic device rated 2 A with a C trip curve for AC and DC networks, standardised to EN/IEC 60947-2 and EN/IEC 60898-1. Its headline breaking capacity is 100 kA Icu in the 220–240 V AC band. Seven Star LLC supplies the A9F94102 in Oman and the GCC as an independent supplier based in Muscat.

The datasheet header marks the A9F94102 as Discontinued; the document is dated 8 Nov 2026 and states no replacement. Treat availability as limited and ask about stock or an equivalent before designing a new board around it. A 2 A rating suits very small circuits: signalling supplies, instrument feeders and small control transformers where the load is a fraction of an ampere and the conductor is thin. Add-on residual current protection listed as compatible: Vigi iC60 single terminal add-on residual current device 25/40/63 A; Quick Vigi iC60 single terminal add-on residual current device 25/40 A.

Technical specifications of the A9F94102

Parameter Specification
Manufacturer / part number Schneider Electric / A9F94102
Range / product name Acti9 / Acti9 iC60
Device short name iC60L
Poles 1P (1 protected poles)
Rated current [In] 2 A
Curve / trip unit C curve, thermal-magnetic
Network type / frequency AC and DC, 50/60 Hz
Magnetic tripping limit 8 x In ± 20 %
Rated operational voltage [Ue] 12–60 V AC 50/60 Hz; 100–133 V AC 50/60 Hz; 220–240 V AC 50/60 Hz; 12–60 V DC; 60–72 V DC
Rated insulation voltage [Ui] 500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Impulse withstand [Uimp] 6 kV conforming to EN/IEC 60947-2
Standards EN/IEC 60947-2 and EN/IEC 60898-1
Suitability for isolation Yes conforming to EN/IEC 60947-2 / Yes conforming to EN/IEC 60898-1
Dimensions (H x W x D) 85 mm x 18 mm x 78.5 mm
Rail pitches / weight 2 pitches of 9 mm; 0.215 kg
Terminals Single terminal, top or bottom: 25 mm² rigid and 16 mm² flexible copper
Stripping length / torque 14 mm; 2 N.m
Durability 20000 cycles mechanical, 10000 cycles electrical
Protection degree IP20 (IEC 60529); IP40 in modular enclosure
Operating temperature / altitude -35–70 °C; 0–2000 m
Storage temperature -40–85 °C
Relative humidity 95 % at 55 °C
Colour White

The A9F94102 among iC60L 1P references

The closest neighbours by rating are A9F94106 (C 6 A) and A9F94110 (C 10 A); they share the housing and differ in thermal setting and, in some cases, in curve and breaking-capacity figures. The table lists the 1P references of this iC60L batch.

Reference Curve / rating Icu at 220–240 V AC Status in datasheet
A9F94102 (this page) C / 2 A 100 kA Discontinued
A9F94106 C / 6 A 25 kA Discontinued
A9F94110 C / 10 A 25 kA Active
A9F94120 C / 20 A 25 kA Discontinued
A9F94132 C / 32 A 20 kA Discontinued

Installation and maintenance of the A9F94102

The A9F94102 clips onto a 35 mm DIN rail. Strip conductors to 14 mm and tighten with a calibrated screwdriver to 2 N.m. Because heavy fault energy is possible, keep conductors short and supported near the terminals.

Inspect periodically for discoloured terminals, a free-moving handle and a clear trip indicator. Mechanical life is 20000 cycles and electrical life 10000 cycles. A breaker that has cleared a large fault should be inspected and normally replaced instead of assumed intact. As a discontinued reference, keep a spare if the board is critical.

1P construction of the A9F94102

A single-pole device interrupts one live conductor and takes two 9 mm pitches (18 mm) of rail. It is the right unit for the phase conductor of a single-phase circuit, or for individual phases in an installation that protects each one separately. If the neutral also has to be opened, a two-pole version is needed.

The body is 18 mm wide, 85 mm high and 78.5 mm deep and weighs 0.215 kg. A layout should reserve 18 mm of rail per device. Terminals take 25 mm² rigid or 16 mm² flexible copper, tightened to 2 N.m, and the datasheet lists comb busbar and distribution block compatibility at top or bottom.

Where the A9F94102 is used in Oman and the GCC

The iC60L family targets places where the available fault current is high, such as main distribution boards close to a transformer, utility auxiliary panels, industrial plant and commercial towers. The A9F94102 fits circuits that need a 2 A single-pole C-curve breaker with a strong breaking capacity in a compact 9 mm module. Gulf installations combine heat, dust and humidity, so compare site conditions with the temperature and humidity limits above, and with the derating practice of the board builder.

Information to send with an RFQ for the A9F94102

  • Full reference (this unit), quantity and whether it is a spare or a new installation
  • System voltage, frequency, and AC or DC use at the installation point
  • Prospective short-circuit current and the cable or load being protected
  • Existing board, neighbouring devices and any add-on residual current device
  • Delivery location and required timing

Environmental and logistics data for the A9F94102

The datasheet lists operation from -35–70 °C, storage from -40–85 °C, relative humidity of 95 % at 55 °C and tropicalisation class 2, with pollution degree 3. Country of origin is shown as FR and the contractual warranty as 18 months. A total lifecycle carbon footprint of 11 kg CO2 eq. is declared, with a recyclability potential of 54 %. A single unit packs at about 112.000 g, with 12 units in the intermediate carton.

Breaking capacity of the A9F94102 across voltage bands

Icu is the ultimate breaking capacity and Ics the service capacity, quoted as a share of Icu. The iC60L is the high-breaking-capacity member of the iC60 family, and the table shows how the figure changes with voltage for this 1P 2 A reference. The first listed band is 12–60 V AC 50/60 Hz at 100 kA Icu, while the 380–415 V AC band is not listed.

Voltage band Icu Ics
12–60 V AC 50/60 Hz 100 kA 100 kA (100 % of Icu)
100–133 V AC 50/60 Hz 100 kA 100 kA (100 % of Icu)
220–240 V AC 50/60 Hz 100 kA 100 kA (100 % of Icu)
12–60 V DC 25 kA 25 kA (100 % of Icu)
60–72 V DC 20 kA 20 kA (100 % of Icu)

The datasheet also gives a household-standard Icn of 15000 A at 230 V AC 50/60 Hz under EN/IEC 60898-1, and limitation class 3, which describes how strongly the device limits let-through energy. Compare every figure with the prospective fault current at the installation point; if the supply can exceed the band that applies, a different device or upstream back-up is required.

Documents and quotation

A datasheet for the this unit is attached on this page. It lists the electrical, mechanical and environmental data summarised above and should be read with the manufacturer’s installation instructions.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric A9F94102 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9F94102 iC60L 1P 2A C Breaker

Answers from our engineering team on installation, compatibility and integration.

01What is the rated current and curve of the A9F94102?
The datasheet gives 2 A with a C curve and a thermal-magnetic trip unit. The magnetic tripping limit is 8 x In plus or minus 20 %.
02What breaking capacity does the A9F94102 have at 230 V AC?
The datasheet lists 100 kA Icu in the 220 to 240 V AC band, with a service capacity of 100 kA. Compare it with the prospective fault current at the installation point.
03How wide is the A9F94102 and how many poles does it have?
It is a 1P device, 18 mm wide, 85 mm high and 78.5 mm deep, using 2 pitches of 9 mm on the rail.
04What conductors fit the A9F94102 terminals?
Single terminals at top or bottom accept 25 mm2 rigid and 16 mm2 flexible copper, with a tightening torque of 2 N.m.
05Can the A9F94102 be used on DC circuits?
The datasheet lists AC and DC network types. DC ratings: 25 kA Icu at 12–60 V DC; 20 kA Icu at 60–72 V DC. Verify polarity and voltage against the real circuit.