Brand: Schneider Electric
Schneider Electric C63N3 ComPacT NSX630N 3P Basic Frame 630A
Description
C63N3: ComPacT NSX630N 3P basic frame without trip unit
The C63N3 is the basic frame of a ComPacT NSX630N, three-pole, 630 A at 40 °C, listed on its datasheet as a product type of basic frame with the protection entry without protection. Seven Star LLC supplies the C63N3 in Oman and the GCC as an independent supplier based in Muscat.
The frame carries the poles, the switching mechanism and the connections, and it is completed with a trip unit chosen to suit the feeder. It carries the breaking code N 50 kA 415 V AC, so the fault rating is already fixed by the frame.
C63N3 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / C63N3 |
| Product type | Basic frame |
| Range / device | ComPacT / NSX630N |
| Application | Distribution |
| Poles | 3P |
| Rated current [In] | 630 A at 40 °C |
| Rated operational voltage [Ue] | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Insulation / impulse [Ui / Uimp] | 800 V AC 50/60 Hz conforming to IEC 60947-2 / 8 kV conforming to IEC 60947-2 |
| Isolation suitability | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity code | N 50 kA 415 V AC |
| Ultimate breaking capacity [Icu] | 22 kA at 525 V AC; 85 kA at 220/240 V AC; 10 kA at 660/690 V AC; 50 kA at 380/415 V AC; 30 kA at 500 V AC; 42 kA at 440 V AC |
| Service breaking capacity [Ics] | 11 kA at 525 V AC; 85 kA at 220/240 V AC; 10 kA at 660/690 V AC; 50 kA at 380/415 V AC; 30 kA at 500 V AC; 42 kA at 440 V AC |
| Protection | Without protection |
| Control / mounting | Toggle / Fixed, Backplate |
| Connections / pitch | Front top, Front bottom / 45 mm |
| Mechanical durability | 15000 cycles conforming to IEC 60947-2 |
| Dimensions W x H x D | 140 mm x 255 mm x 110 mm |
| Standards | EN/IEC 60947-2; UL 60947-4-1 |
| Protection degree | IP40 conforming to IEC 60529; IK07 conforming to IEC 62262 |
| Operating temperature | -25 to 70 °C |
Selection and RFQ checklist for the C63N3
- Frame: NSX630N with 3P, 630 A.
- Fault level: 50 kA Icu at 380/415 V AC against the prospective current at the board.
- Trip unit: type, rating and protection functions, ordered as a separate reference.
- Neutral handling and space available: 140 mm wide.
- Accessories: auxiliary contacts, handles, terminal covers.
For the quotation please send the part number C63N3, the trip unit you plan to use, quantity, system voltage and frequency, and delivery date.
Related references to the C63N3
The C63N3 sits in a group of ComPacT NSX400 and NSX630 references. The table shows the frames, complete breakers and trip units of the same size covered by these datasheets. Complete breakers on the same frame in this group of datasheets include C63N32D630, C63N42D630.
| Part number | Frame | Poles | Trip unit | Rating | Icu at 380/415 V |
|---|---|---|---|---|---|
| C6336E630 | Trip unit | 3P | MicroLogic 6.3 E | 630 A | – |
| C63F32D630 | NSX630F | 3P | MicroLogic 2.3 | 630 A | 36 kA |
| C63F4 | NSX630F | 4P | none (basic frame) | 630 A | 36 kA |
| C63F42D630 | NSX630F | 4P | MicroLogic 2.3 | 630 A | 36 kA |
| C63H32D630 | NSX630H | 3P | MicroLogic 2.3 | 630 A | 70 kA |
| C63N3 | NSX630N | 3P | none (basic frame) | 630 A | 50 kA |
| C63N32D630 | NSX630N | 3P | MicroLogic 2.3 | 630 A | 50 kA |
| C63N4 | NSX630N | 4P | none (basic frame) | 630 A | 50 kA |
| C63N42D630 | NSX630N | 4P | MicroLogic 2.3 | 630 A | 50 kA |
Commissioning and maintenance notes for this frame
Before energising a frame that has just been completed with its trip unit, check that the terminals are tightened to the torque in the manufacturer instructions, that the toggle operates freely, and that the trip unit settings match the coordination study rather than the factory position.
In service, include the breaker in the periodic thermography and inspection round of the board. Look for discoloured terminals, dust build-up on the front and signs of condensation, all of which are common in coastal and desert sites. Keep a record of the trip unit settings so a replaced device can be restored to the same values.
If a breaker has interrupted a heavy fault, follow the manufacturer guidance on inspection before putting it back in service, and keep a spare frame or complete breaker available for critical boards where a long delivery would stop production.
Size and mounting of the C63N3
The frame measures 140 mm wide, 255 mm high and 110 mm deep. It mounts on a backplate with front connections at top and bottom on a 45 mm pitch, with a toggle control.
It is the three-pole frame; if you need a switched neutral, the four-pole frame of the same rating is the alternative.
Breaking capacity and ratings of the C63N3
The code N 50 kA 415 V AC corresponds to 50 kA Icu at 380/415 V AC. At 660/690 V AC the Icu is 10 kA, at 440 V AC it is 42 kA and at 500 V AC it is 30 kA. The service capacity Ics at 380/415 V AC is 50 kA.
The rated insulation voltage is 800 V AC 50/60 Hz conforming to IEC 60947-2, the impulse withstand 8 kV conforming to IEC 60947-2, and the datasheet lists suitability for isolation. Electrical durability is given at 440 V and 690 V in cycles in the table above, and mechanical durability is 15000 cycles conforming to IEC 60947-2.
Using this frame in Oman and GCC installations
Frames of this size are used for incomers and large feeders in low-voltage boards at substations, desalination plants, oil and gas facilities, industrial halls and large buildings. The datasheet gives an operating range of -25 to 70 °C, humidity of and altitude of .
Board temperature in summer and dust ingress are the two points we ask customers to check. Protection degrees are IP40 conforming to IEC 60529 and IK07 conforming to IEC 62262.
What this frame does and does not include
Because the C63N3 is sold without a trip unit, it does not protect against overload or short circuit on its own: the datasheet states Without protection. The protection stage, the settings and the current range come from the trip unit that is added.
The datasheet for the trip unit C6336E630 (MicroLogic 6.3 E, 630 A, listed for ComPacT NSX630) shows one candidate. Check the manufacturer compatibility information for the rating and function you need, and do not assume that any trip unit of a given brand fits any frame.
Documents and quotation
A datasheet for the C63N3 is attached on this page so you can check the figures quoted here against the original document before committing to a purchase order.
To proceed, send the part number, the quantity and the project background and we will confirm availability and prepare a quotation. Seven Star LLC works as an independent supplier based in Muscat and is separate from the brand’s own sales network.
Other Models in the Se Compact Nsx Frame Range
Seven Star LLC supplies models from the Se Compact Nsx Frame range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric C40F3 ComPacT NSX400F 3P Basic Frame 400A | Circuit Breakers | View details |
| Schneider Electric C40N3 ComPacT NSX400N 3P Basic Frame 400A | Circuit Breakers | View details |
| Schneider Electric C63N3 ComPacT NSX630N 3P Basic Frame 630A | Circuit Breakers | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric C63N3 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric C63N3 ComPacT NSX630N 3P Basic
Answers from our engineering team on installation, compatibility and integration.
01Does the C63N3 include a trip unit?
No. The datasheet lists it as a basic frame with the protection entry Without protection; the trip unit is a separate reference.
02What is the breaking capacity of the C63N3?
The datasheet lists 50 kA Icu at 380/415 V AC and 10 kA at 660/690 V AC, with the code N 50 kA 415 V AC.
03How many poles does the C63N3 have?
3P, with the neutral position listed as not applicable on this three-pole frame.
04What are the dimensions of the C63N3?
The datasheet gives 140 mm wide, 255 mm high and 110 mm deep.
05How is the C63N3 mounted and connected?
It is fixed on a backplate, with front connections at top and bottom and a 45 mm pitch.


















Reviews