Schneider Electric C10F1TM030 NSX100F 1P 30 A TM-D AC/DC Breaker

Description

C10F1TM030: ComPacT NSX100F 1P breaker, TM-D 30 A

The C10F1TM030 is a Schneider Electric ComPacT NSX100F circuit breaker with one pole, a TM-D thermal-magnetic trip unit rated 30 A, designed for both AC and DC. The datasheet describes it as: ComPacT NSX100F AC/DC, 18 kA at 240 VAC, TMD trip unit 30 A, 1 pole 1d. Seven Star LLC supplies the C10F1TM030 in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference: the NSX100 frame carries up to 100 A, the F letter is the breaking-capacity level (18 kA at 240 V AC for this one-pole version), and the datasheet’s trip unit name is TM-D with a fixed 30 A thermal setting and a fixed magnetic setting of 300 A.

Technical specifications of the C10F1TM030

Parameter Specification
Manufacturer / part number Schneider Electric / C10F1TM030
Device short name NSX100F
Product type Circuit breaker, distribution application
Poles / protected poles 1P / 1D
Rated current In 30 A at 40 °C
Network AC 50/60 Hz and DC
Rated operational voltage Ue 277 V AC 50/60 Hz; 250 V DC
Ui / Uimp 750 V AC / 8 kV
Breaking capacity Icu 18 kA at 220/240 V AC; 36 kA at 250 V DC
Service breaking capacity Ics 18 kA at 220/240 V AC; 36 kA at 250 V DC
Breaking capacity code F 18 kA 240 V AC
Trip unit TM-D, thermal-magnetic, protection functions LI
Thermal pick-up Ir Fixed, 1 x In = 30 A
Magnetic pick-up Ii Fixed, 300 A
Isolation / category Suitable for isolation (EN/IEC 60947-2); category A
Mechanical / electrical durability 20000 cycles; 20000 cycles at 277 V In/2 and 10000 cycles at 277 V In
Power dissipation per pole 4.03 W
Control / mounting Toggle / fixed, backplate or flat on the back; front connections, 35 mm pitch
Dimensions W x H x D 35 x 161 x 86 mm
Net weight 0.7 kg
Degree of protection IP40 (IEC 60529), IK07 (IEC 62262)
Overvoltage category / shock class IV / Class II on front face
Ambient temperature, operation / storage -25 to 70 °C / -50 to 85 °C
Standard EN/IEC 60947-2

TM-D thermal-magnetic protection on the C10F1TM030

The TM-D unit is thermal-magnetic: a bimetal element for overload (L) and a magnetic element for short-circuit (I). Both are fixed on this reference. The long-time pick-up is fixed at 1 x In, which is 30 A, and the instantaneous pick-up is fixed at 300 A, about 10.0 times In (calculated).

Fixed settings keep the device simple and free from mis-adjustment, but they also mean the protection cannot be tuned for motor inrush or for selectivity. The datasheet lists no earth-leakage protection. If a load needs adjustable thresholds, a breaker with an adjustable or electronic trip unit is the route.

Voltage, breaking capacity and DC use of the C10F1TM030

The datasheet gives two sets of ratings. On AC, Ue is 277 V and Icu and Ics are 18 kA at 220/240 V; on DC, Ue is 250 V and Icu and Ics are 36 kA. A single-pole breaker has one contact gap, so it fits circuits where one conductor is switched: a phase-to-neutral circuit on a 400 V system, a single-phase supply, or a DC circuit up to 250 V where the polarity arrangement permits it.

For three-phase loads or for circuits that need all poles to open together, a multi-pole device is the correct choice; a multi-pole NSX100F version with its own datasheet ratings is the right basis.

Supply Ue Icu / Ics
AC 50/60 Hz 277 V 18 kA at 220/240 V
DC 250 V 36 kA

Dimensions and dissipation of the C10F1TM030

The datasheet lists 4.03 W of dissipation per pole. With a width of only 35 mm and a weight of 0.7 kg, the C10F1TM030 allows high-density boards; the heat from adjacent poles should be included when the cubicle ventilation is calculated.

Mounting is on a backplate or flat on the back, with front connections at 35 mm pitch. The front face is Class II; IP40 and IK07 apply, so installation is inside an enclosed panel. The overvoltage category is IV for this single-pole version.

Related references to the C10F1TM030

The same single-pole NSX100F family is available at other ratings. The closest neighbour in the range we handle is C10F1TM020, which differs in the thermal setting and the fixed magnetic pick-up (20 A and 190 A), while the frame, voltage and breaking capacity are the same. Other ratings exist in the family; ask us for current availability.

Choose between neighbouring ratings on the load current and conductor size, not on the breaker alone: the breaker rating must protect the cable.

Installing and maintaining the C10F1TM030

Mount the C10F1TM030 on the backplate or flat on the back as the installation instructions allow, connect the cable to the front terminals and torque it to the manufacturer’s value. Switch the toggle through its positions to confirm free operation, and record the nominal 30 A setting on the circuit schedule.

Maintenance is limited: periodic inspection of terminals for heat discolouration, a manual operation test and, after any trip, a check of the cause before reclosing. Mechanical durability is 20000 cycles; electrical durability is 20000 cycles at 277 V In/2 and 10000 cycles at 277 V In.

Applications in Oman and the GCC

In Oman and the GCC, a 30 A one-pole breaker fits branch circuits for small motors, heaters, socket outlets on industrial sites and dc auxiliary supplies up to 250 V in substations. In hot rooms, the thermal element sees ambient heat, so ratings should be checked against the operating temperature.

Selection and RFQ information for the C10F1TM030

  • Load current and cable size, against the 30 A fixed rating.
  • System: AC up to 277 V or DC up to 250 V, and the fault level.
  • Pole count: single-pole here; two- or three-pole devices need different references.
  • Accessories required.
  • Quantity and delivery location in Oman or the GCC.

Send the part number C10F1TM030, the quantity and the delivery location, and if possible the circuit voltage and fault level.

Documents and quotation

The official English datasheet for the C10F1TM030 is attached on this page. It lists the trip settings, ratings, dimensions and environmental data used above.

To request a quotation, send the part number C10F1TM030, the quantity and the delivery location. Seven Star LLC is an independent supplier in Muscat and quotes according to current availability.

Other Models in the Se Nsx100f 1p Range

Seven Star LLC supplies models from the Se Nsx100f 1p range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric C10F1TM020 NSX100F 1P 20 A TM-D AC/DC BreakerCircuit BreakersView details
Schneider Electric C10F1TM030 NSX100F 1P 30 A TM-D AC/DC BreakerCircuit BreakersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric C10F1TM030 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric C10F1TM030 NSX100F 1P 30 A TM-D

Answers from our engineering team on installation, compatibility and integration.

01What is the rated current of the C10F1TM030?
30 A at 40 °C with a fixed thermal setting of 1 x In.
02What is the magnetic trip level of the C10F1TM030?
The datasheet gives a fixed instantaneous pick-up of 300 A.
03Can the C10F1TM030 be used on DC?
Yes. The datasheet lists AC and DC networks, with Ue 250 V DC and a breaking capacity of 36 kA at 250 V DC.
04What is the breaking capacity of the C10F1TM030 on AC?
18 kA Icu and Ics at 220/240 V AC; Ue is 277 V AC.
05What are the dimensions of the C10F1TM030?
35 mm wide, 161 mm high and 86 mm deep, weight 0.7 kg.