Pfannenberg PWS 7062 Air/Water Heat Exchanger, 600 W
Description
Slim air/water heat exchangers for plants with chilled water
The Pfannenberg PWS 7062 is a slim air/water heat exchanger with 600 W cooling capacity, and the PWS 7102 delivers 950 W at the same test condition. Where a plant already has a chilled or cooling water circuit, an air/water heat exchanger removes cabinet heat into the water without a compressor, which makes it simple, quiet and efficient. The device is maintenance-free, can be installed completely inside, outside or partly through the wall, and has a mounting-friendly seal that avoids elaborate rework of the cut-out.
An integrated thermostat and solenoid valve control the water flow, and integrated temperature monitoring with an alarm contact reports a fault. Because the cooling medium is water at +1 to +35 °C, the cabinet can be held below the ambient temperature as long as the water is cooler than the required inside temperature.
Technical specifications
| Parameter | PWS 7102 | PWS 7062 |
|---|---|---|
| Cooling capacity W10/A35, 200 l/h | 950 W | 600 W |
| Rated voltage | 230 V AC 50/60 Hz or 115 V AC 60 Hz | 230 V AC 50/60 Hz or 115 V AC 60 Hz |
| Power consumption (230 V, 50 / 60 Hz) | 82 / 84 W | 68 / 70 W |
| Current consumption (230 V, 50 / 60 Hz) | 0.35 / 0.4 A | 0.35 / 0.38 A |
| Air flow internal (free flow) | 570 m³/h | 440 m³/h |
| Weight | 7.5 kg | 6 kg |
| Article no., 230 V / 115 V | 12051010055 / 12051017055 | 12050610055 / 12050617055 |
| Parameter | Specification |
|---|---|
| Pre-fuse / noise | T 4 A; 48 dB(A) or less (EN ISO 3741) |
| Ambient temperature range | +1 to +70 °C |
| Control range | +8 to +50 °C, factory setting +35 °C |
| Water inlet temperature / pressure | +1 to +35 °C; maximum 10 bar permissible operating pressure |
| Water connection | 13 mm hose nozzle; other connectors on request |
| Duty cycle / condensate | 100 %; condensate drain |
| Protection | IP 55 towards the electrical enclosure (IP 65 on request) |
| Construction | Galvanised steel housing, powder-coated (stainless steel on request); copper pipe with aluminium fins (stainless steel piping on request); RAL 7035 |
Water-side design notes
The listed performance is at 10 °C water and 35 °C ambient with a flow of 200 l/h; changing the water temperature or flow changes the capacity, and the sheet gives the curve against water flow. The manufacturer lists a 10 bar maximum, a +1 to +35 °C inlet range and copper pipe with aluminium fins, so water quality and corrosion inhibitors should be agreed for the circuit, and stainless piping is available on request. Condensate forms when the water is colder than the dew point of the cabinet air, so the unit has a condensate drain; an external condensate evaporation system (18314000001) and a condensate bottle (18314000100) are listed as accessories.
Selection and what to confirm before ordering
Compare the heat load of the cabinet with 600 W for the PWS 7062 or 950 W for the PWS 7102 at the planned water temperature and flow, and check the water supply is available at the cabinet location. Confirm voltage, hose or other water connection, the IP class and the finish. For sites without a water circuit use a refrigerant-based unit such as the DTT 6301 or the Rittal Blue e+ wall-mounted cooling units; see the Cooling category.
Documents and quotation
The Pfannenberg PWS 7102/7062 product sheet is attached to this page and is the manufacturer’s own document, not a Seven Star summary. It includes the water-flow performance curve and outline.
State the water temperature, flow, voltage and finish. Seven Star LLC, an independent supplier in Muscat, quotes the PWS 7062 and PWS 7102 against your application data; send the enclosure size, ambient temperature, supply voltage and quantity so the correct variant and article number can be confirmed before an offer is issued.
Datasheets & Documents
- Datasheet Pfannenberg PWS 7102/7062 product sheet (manufacturer PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pfannenberg is the German maker of thermal management and signalling products for electrical enclosures and industry: filter fans, cooling units, air-to-water heat exchangers, chillers, heaters, sirens and beacons. Otto Pfannenberg, an electrical engineer, founded the company in Hamburg in 1954, and in 1958 he invented the filter fan to stop components in control cabinets from overheating. Pfannenberg is still family-owned and headquartered in Hamburg.
Seven Star LLC is an independent supplier in Muscat. We list Pfannenberg signalling devices and enclosure climate products for panel builders and plant engineers in Oman and the GCC.
Pfannenberg company profile
| Founded | 1954, Hamburg, Germany |
|---|---|
| Founder | Otto Pfannenberg, electrical engineer |
| Headquarters | Hamburg, Germany; North American headquarters in Lancaster, New York |
| Ownership | Family-owned |
| Product families | PF Filterfans, DTS and DTI cooling units, air-to-water heat exchangers, process chillers, enclosure heaters and thermostats, PA and DS sirens, beacons and combined signalling devices |
Milestones
- 1954: Otto Pfannenberg founds the company in Hamburg.
- 1958: Pfannenberg invents the filter fan for control cabinets.
- 1962: The company introduces an industrial flashing light that does not need a bulb change after activation.
Pfannenberg product series
Signalling devices include the PATROL PA X combined flashing sounders from 105 to 122 dB(A), the PYRA flashing light sounder, the PRO 10-Ex sounder for zone 2 and zone 22, and the INTENSE BR 50 modular LED signal tower.
Thermal management covers FLZ enclosure thermostats, twin thermostats, hygrostats and Peltier thermostats, FLH radiant heaters and PFH and FLH-T fan heaters, PF filter fans in several installation sizes up to 785 m3/h and the PTF roof-mounted filter fan, and DTS and DTI cooling units, including the DTI outdoor version.
Where Pfannenberg products are used
Control and drive cabinets on machines and in plant rooms, outdoor enclosures in hot and humid climates, and alarm and evacuation signalling in industrial buildings and process areas. In the Gulf, cabinet cooling and condensation control are the main reasons for specifying Pfannenberg thermal products.
Pfannenberg products we list
Ordering Pfannenberg products: what we need
Send the article number or full designation, such as PA X 1-05 or DTI 8401P. For signalling devices add the supply voltage, lens and housing colour and any required approval such as EN 54-3 or an Ex certificate. For cooling units give the cooling capacity, voltage and frequency, mounting (side or roof, internal or external) and the ambient temperature. For fans and heaters give the installation size, voltage and airflow or heating power.
Facts checked against Pfannenberg's published company history, October 2026.
Browse Pfannenberg products by category: Enclosure Climate Control, Fire & Gas Detectors, Cooling.
Related products
Frequently Asked Questions
600 W for the PWS 7062 and 950 W for the PWS 7102 at W10/A35 and 200 l/h.
+1 to +35 °C.
10 bar permissible operating pressure.
Yes, an integrated thermostat and solenoid valve control the temperature.
IP 55 towards the electrical enclosure, with IP 65 on request.