Pepperl+Fuchs KFD2-WAC2-Ex1.D-Y1 Strain Gauge Barrier

Description

Pepperl+Fuchs KFD2-WAC2-Ex1.D-Y1: bridge input inside the hazardous area

Load cells in grain silos, solvent tanks and powder hoppers sit in classified zones, and that is exactly where the KFD2-WAC2-Ex1.D-Y1 is meant to reach. It is an isolated barrier whose bridge input on terminals 1+ and 2- is certified Ex ia IIC and Ex ia IIIC (dust), so the strain gauge can be in Zone 0, 1 or 2, while the converter itself stays in the safe area or in Zone 2.

The Y1 suffix identifies a variant with a quick measurement cycle: reaction time is 150 ms, shorter than the 300 to 850 ms of the standard WAC2 types, at the price of a wider accuracy figure of 0.2 percent. That makes it attractive for dosing, fast filling and dynamic checkweighing.

Principal characteristics

  • Entity values of input I: Uo 14 V, Io 238 mA, Po 833 mW (linear)
  • EU-type examination certificate TUV 04 ATEX 2531, marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
  • Outputs: two relays, plus an analogue output of 0 to plus or minus 20 mA, 4 to 20 mA or 0 to plus or minus 10 V
  • Reaction time 150 ms; resolution and accuracy 0.2 percent including non-linearity and hysteresis
  • FM control drawing 116-0302 (cFMus)

KFD2-WAC2-Ex1.D-Y1 data table

Parameter Value
Supply Power Rail or terminals 23+ and 24-, Um 40 V DC
Bridge input terminals 1+ and 2-, -100 to 100 mV, above 1 megohm
Tare range 0 to 500 percent of span
Inputs II and III terminals 13+/14- and 15+/14-: tare, calibration, zero; open-circuit 18 V, short-circuit 5 mA
Analogue output terminals 7-, 8+, 9-; load up to 550 ohm; line fault downscale 2 mA or -21.5 mA, upscale 21.5 mA
Relay rating 253 V AC / 2 A / 500 VA / cos phi 0.7 or better; 40 V DC / 2 A
Deviation 0.2 percent incl. non-linearity and hysteresis
Temperature effect 0.01 percent per K
Reaction time 150 ms
Isolation safe electrical isolation, peak 375 V (IEC/EN 60079-11), input I to other circuits
Interface RS-485 programming jack
Housing 40 x 119 x 115 mm, type C2, about 250 g, IP20
Temperature -20 to 60 degrees C

Where the fast version earns its place

A batching skid for chemical additives needs to close a valve within a fraction of a second of reaching target weight. A 150 ms converter lets the relay act earlier than a unit that needs up to 850 ms, reducing overshoot. Likewise, a crane hook load alarm in a classified area benefits from a quick response when load changes abruptly.

Why KFD2-WAC2-Ex1.D-Y1 is not the same as KFD2-WAC2-Ex1.D

Both are Ex ia barriers, but the standard Ex1.D device is slower and more precise, while KFD2-WAC2-Ex1.D-Y1 reacts in 150 ms with 0.2 percent accuracy. Choose according to whether static accuracy or dynamic response drives the loop. The non-Ex KFD2-WAC2-1.D has no intrinsically safe input at all and is therefore limited to safe-area load cells.

Installation and entity checks

Add up the cable capacitance and inductance of the bridge cable and compare it with the permitted values for the gas group, since the 833 mW power budget allows long cable runs but a four-gauge parallel load must still be verified. Use the blue terminal block for the intrinsically safe side. Program tare, zero and final value with the keypad or PACTware, then document the set values.

Maintenance

Re-check calibration with certified weights at each statutory inspection. Inspect the load cell cable for damage, because a partial break changes the bridge resistance and can drift the reading before the line-fault detection trips.

Documentation trail

File the datasheet, the certificate number and the control drawing reference with the loop dossier. Inspectors often ask for the certificate on the first page, and having the number TUV 04 ATEX 2531 recorded speeds up the review of Oman and GCC site audits.

Sizing the bridge circuit for Ex ia use

A hazardous-area weighing loop is more than a converter and a cell. The cell itself must be certified or classed as simple apparatus, the junction box must keep intrinsically safe wiring separate, and the cable must stay within the capacitance and inductance limits for the group. With a source of 14 V and 238 mA, the barrier can supply up to four 350 ohm cells in parallel, but each additional cell lowers the net bridge resistance towards the 116 ohm floor mentioned in the datasheet, so a summing box and cell matching deserve careful design. Where the structure is a tank on three or four legs, the corner trimming in the summing box has a greater effect on accuracy than the converter has.

The converter also offers two relay alarms with programmable high and low limits, so a local overload lamp can be driven without involving the control system. Because relay terminals are non-intrinsically safe, keep them on the safe-area side of the separation.

Behaviour during faults

If the bridge cable breaks or a gauge shorts, the analogue output moves to the configured fault level: downscale at 2 mA (1 V) or minus 21.5 mA (minus 10.75 V), or upscale at 21.5 mA (10.75 V). Choose the direction that places the plant in a safe state, and make sure the DCS interprets the value as a fault instead of a real weight. The collective error message travels on the Power Rail so one alarm contact can watch a whole row of modules.

Questions buyers ask about KFD2-WAC2-Ex1.D-Y1

What does the Y1 variant of KFD2-WAC2-Ex1.D-Y1 offer? The datasheet for this part lists a low response time, a reaction time of 150 ms, with a deviation of 0.2 percent.

What are the safe-area values of the bridge input on KFD2-WAC2-Ex1.D-Y1? Input I on terminals 1+ and 2- is Ex ia with Uo 14 V, Io 238 mA and Po 833 mW (linear characteristic).

Which ATEX certificate covers KFD2-WAC2-Ex1.D-Y1? The EU-type examination certificate is TUV 04 ATEX 2531 with marking [Ex ia Ga] IIC, [Ex ia Da] IIIC and [Ex ia Ma] I.

What analogue outputs can KFD2-WAC2-Ex1.D-Y1 provide? Output III supplies 0 to plus or minus 20 mA or 4 to 20 mA into up to 550 ohm, or 0 to plus or minus 10 V with the bridge between terminals 7 and 9.

How is KFD2-WAC2-Ex1.D-Y1 configured? Configuration uses the keypad or the PACTware software, and tare, zero point and final value measurements can be entered through either route.

Documents and quotation

The manufacturer datasheet for KFD2-WAC2-Ex1.D-Y1 accompanies this listing as a PDF so your engineers can verify terminals, ratings and approvals before purchase. Tell us whether the load cell is in Zone 1 or Zone 2. To request a quotation, send the RFQ with the exact part number KFD2-WAC2-Ex1.D-Y1, the quantity, the delivery location in Oman or the GCC and any project reference. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Other Models in the Wac2 Strain Range

Seven Star LLC supplies models from the Wac2 Strain range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Pepperl+Fuchs KFD2-WAC2-1.D Strain Gauge ConverterIsolator & BarrierView details
Pepperl+Fuchs KFD2-WAC2-Ex1.D-Y1 Strain Gauge BarrierIsolator & BarrierYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Pepperl+Fuchs KFD2-WAC2-Ex1.D-Y1 Strain Gauge Barrier Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFD2-WAC2-Ex1.D-Y1 Strain Gauge

Answers from our engineering team on installation, compatibility and integration.

01What does the Y1 variant of KFD2-WAC2-Ex1.D-Y1 offer?
The datasheet for this part lists a low response time, a reaction time of 150 ms, with a deviation of 0.2 percent.
02What are the safe-area values of the bridge input on KFD2-WAC2-Ex1.D-Y1?
Input I on terminals 1+ and 2- is Ex ia with Uo 14 V, Io 238 mA and Po 833 mW (linear characteristic).
03Which ATEX certificate covers KFD2-WAC2-Ex1.D-Y1?
The EU-type examination certificate is TUV 04 ATEX 2531 with marking [Ex ia Ga] IIC, [Ex ia Da] IIIC and [Ex ia Ma] I.
04What analogue outputs can KFD2-WAC2-Ex1.D-Y1 provide?
Output III supplies 0 to plus or minus 20 mA or 4 to 20 mA into up to 550 ohm, or 0 to plus or minus 10 V with the bridge between terminals 7 and 9.
05How is KFD2-WAC2-Ex1.D-Y1 configured?
Configuration uses the keypad or the PACTware software, and tare, zero point and final value measurements can be entered through either route.