- Automation & ControlView all 2,897 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Masoneilan
Masoneilan 12810 Pneumatic Proportional-Reset Level Controller
Description
Overview
The Masoneilan 12810 is the proportional-reset member of the Baker Hughes 12800 Series of pneumatic level controllers. Like the rest of the family it senses level with a displacer hanging from a torque tube and turns the movement into a 3-15 psi or 6-30 psi air signal that positions a control valve without electrical power. What sets the Masoneilan 12810 apart is reset action: it keeps correcting a level offset until the level returns exactly to the set point, instead of leaving the steady-state error that a purely proportional controller can leave behind.
Seven Star LLC supplies the Masoneilan 12810 to refineries, gas plants and process facilities in Oman and the GCC where pneumatic loops still run on separators, accumulators and vessel bottoms. Our Muscat team asks for the nameplate, liquid specific gravity, displacer range and valve action before confirming the model.
Operating Principle of the Masoneilan 12810
A level change alters the buoyant force on the displacer and rotates the torque tube. A reversing arc and control link move a control arm, which positions a flapper against a nozzle, and a relay amplifies the nozzle pressure so that about 3.5 psi at the nozzle gives the full 12 psi change of a 3-15 psi output. Up to here the mechanism is that of a proportional controller.
In the Masoneilan 12810 the bellows spring of the proportional unit is replaced by a reset bellows, and a resistance unit and capacity tank sit in the air circuit between the two bellows. After a deviation the proportional bellows reacts at once while the reset bellows follows more slowly through the resistance. Air flows until the pressures in the two bellows are equal, and equilibrium returns only when the level is back at its set point, so the reset rate is adjusted by changing the resistance.
Choosing Reset Action for the Masoneilan 12810
The proportional band scale shows the percentage of the total level range through which the level must travel to move the output from 3 to 15 psi. Baker Hughes advises setting the band as narrow as the process allows without cycling, because that keeps level variation to a minimum. Where the band cannot be narrowed enough to hold the level within its limits, the manual says reset should be added, which is the case the Masoneilan 12810 is built for. The reset rate knob counts repeats per minute, meaning how many times each minute the reset action repeats the effect of the proportional action for a given deviation.
Engineering Design of the Masoneilan 12810
The two parts that distinguish the 12810 from the proportional 12800 are the resistance unit assembly and the reset bellows tubing. The resistance unit may need occasional cleaning: the manual has the technician back the reset knob off, withdraw the unit body from the frame with a twisting motion, strip the spring retainer, spring, button, plug and O-ring, blow out the ports and wipe the parts with a lint-free cloth. On reassembly the reset knob is turned back to the 0.02 mark.
Alignment and Tuning of the Masoneilan 12810
Alignment follows the proportional procedure after one extra step: with the displacer hanging free, the reset rate index is set at 6 (open) and the control setting index is adjusted for 9 psi output. When 9 psi has held for at least 30 seconds, the index is moved to the white dot, which locks 9 psi in the reset bellows.
For tuning, start with a low reset rate, around 0.02 to 0.2 repeats per minute, and narrow the proportional band as far as the process allows without cycling. Widen the band by about 50 percent, then turn the reset knob slowly clockwise until cycling occurs and set the reset rate to roughly half that value.
Converting a Proportional 12800 to the Masoneilan 12810
The 12800 Series is designed for field conversion between modes using a kit of the parts involved: a bellows tubing assembly, a reset bellows assembly and a resistance unit assembly. The manual has the technician remove the output pressure gauge, disconnect the bellows tubing, move the proportional band index fully left and compress the bellows spring until its button clears the proportional spring thread. The reset bellows slides into the spring’s place, the resistance unit is mounted in the lower left corner of the case and new tubing is fitted with the copper gasket supplied. The gauge is then refitted and the mechanism aligned.
Key Features
- Reset action returns the level to the set point after a disturbance, removing offset.
- The reset rate knob is graduated in repeats per minute.
- The proportional band scale shows the percentage of level range needed to move the output from 3 to 15 psi.
- The control link and reversing arc select direct or reverse action and compensate for specific gravity down to 0.1.
- The Masoneilan 12810 runs on instrument air alone, with no wiring at the controller.
Industrial Applications
Reset action is chosen when a narrow proportional band alone would make the loop cycle or when the process cannot tolerate a permanent offset. The Masoneilan 12810 therefore suits level loops with changing inflow, such as separators and accumulators in oil and gas, refining and petrochemical service at Sohar, Duqm and Salalah. The same torque tube hardware supports interface service between two liquids.
Typical loop partners are the Masoneilan 10000 series double-port control valve and the Masoneilan Type 87/88 spring-diaphragm actuators.
Related published Masoneilan pages: Masoneilan 35002 Series Camflex rotary control valve.
Technical Specifications
Published data for the Masoneilan 12810 from the 12800 Series instruction manual (Baker Hughes, 2022).
| Parameter | Specification |
|---|---|
| Model | Masoneilan 12810 proportional-reset level controller |
| Control mode | Proportional plus reset (integral) action |
| Output signal | 3-15 psi or 6-30 psi |
| Supply and regulator | Filter regulator fed with 50 to 125 psi gauge; set to 20 psi for 3-15 psi output, 35 psi for 6-30 psi |
| Reset adjustment | Knob in repeats per minute; resistance unit and capacity tank between the bellows |
| Reset alignment | 9 psi locked in the reset bellows with the index at the white dot |
| Typical starting reset rate | 0.02 to 0.2 repeats per minute |
| Case limit | Ambient at the case not above 180 degF; 1/4 in. NPT supply and output |
| Service life | 25 years or more with annual inspection |
Related Masoneilan level instruments include the Masoneilan 12800 Series pneumatic level controller, Masoneilan 12400 Series digital level transmitter, Masoneilan 12820 pneumatic level transmitter, Masoneilan 12830 differential-gap level controller and Masoneilan 12840 pneumatic-set level controller.
Request a Quote for Masoneilan 12810
Send a formal RFQ for the Masoneilan 12810 to the Seven Star LLC instrumentation division with the displacer range, mounting arrangement, specific gravity, output range and control action. We confirm the model, advise on availability and lead time and supply the Baker Hughes instruction manual from this page. In Oman and the GCC, Seven Star LLC delivers genuine products with manufacturer documentation and local engineering support.
Datasheets & Documents
- Instruction Manual Masoneilan 12810 Level Controller Instruction Manual Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Masoneilan is a control valve brand of Baker Hughes with roots going back to 1882. Its Camflex eccentric plug rotary valve, 21000 series globe valve and SVI digital positioners are fixtures in refineries, gas plants and power stations. Every valve carries a serial number and a long model number that define the actuator, body and trim.
Seven Star LLC is an independent supplier listing Masoneilan control valves, actuators, regulators, positioners and level instruments for buyers in Oman and the GCC. We source complete valves as well as Masoneilan spare parts against that nameplate data.
Masoneilan at a glance
| Origin | Mason Regulator Company, Boston area, USA (1882). It acquired the Neilan Company of California in 1931, and the two names became Masoneilan. |
|---|---|
| Ownership | Dresser Industries from 1985, then GE Oil & Gas, now Baker Hughes |
| Milestones the company cites | Cv flow coefficient introduced (1944), spring-diaphragm actuators (1955), Camflex rotary globe valve (1968), Lo-dB low-noise trim (1975), LincolnLog axial-flow letdown valve (1982), Varipak (1984), V-Log (1998), SteamForm steam conditioning valve (2002) |
| Product families | Globe, rotary, butterfly and severe-service control valves, actuators, digital positioners, self-operated regulators and displacer level instruments |
| Typical duty | Throttling control of steam, gas, hydrocarbons and water, high-pressure letdown, anti-cavitation and low-noise service |
Masoneilan control valves and actuator series
| Series | Type | Typical use |
|---|---|---|
| 21000, 21009 | Top-guided and cage-guided globe valves | General process control. Cryogenic (21000 C), bellows seal (21000 BS) and API 6A versions are also made |
| 41005 | Cage-guided globe valve | Higher pressure drop and larger sizes, up to 30-36 inch extended sizes; VRT anti-cavitation and API 6A versions |
| 35002 Camflex II | Eccentric plug rotary control valve | Erosive, flashing and dirty service; HC high capacity, DVD low noise and GR globe replacement versions |
| 37002 MiniTork II, 39003/39005, 33000 | Butterfly control valves, high-performance and triple-offset | Large flows at low pressure drop, and tight-shutoff duty |
| 28000 Varipak | Microflow control valve | Very small flows, with adjustable Cv |
| 78400/18400 LincolnLog, 77000, 49000 V-Log | Severe-service multi-stage valves | High-pressure liquid letdown, anti-cavitation and gas noise reduction |
| 84000/84003 SteamForm, DSH | Steam conditioning valves and desuperheaters | Turbine bypass and steam pressure and temperature reduction |
| 87/88, 37/38, 51/52/53 | Spring-diaphragm and piston actuators | Linear and rotary valve actuation; diaphragms and soft-goods kits are listed separately |
| SVI3, SVI II AP, SVi1000, SVI FF | Digital valve positioners | HART or FOUNDATION Fieldbus positioning with valve diagnostics; the SVI II ESD adds partial stroke testing |
| 4700/4800, 8013 | Pneumatic and electro-pneumatic positioners | Older installed base. Many sites move to SVI positioners at overhaul |
| 525/526, 535/536, 171-174 | Self-operated pressure regulators | Pressure reducing and back-pressure control without external power |
| 12400, 12800 | Displacer level transmitters and controllers | Digital (12400, HART, SIL 2 version 12420) and pneumatic (12800) level control on separators and vessels |
Where Masoneilan valves are used
Throttling duty on steam, hydrocarbons, gas and water is the daily work of these valves. Typical services are feedwater and steam conditioning in power plants, separator and compressor loops in gas processing, high-pressure-drop letdown, cryogenic service in LNG and air separation, and general flow, pressure and level control in refineries and chemical plants.
Ordering Masoneilan valves and spare parts: what we need
For spare parts the serial number decides the order, because the factory record behind it lists the trim, materials and actuator. Send a clear nameplate photo with the serial number, model number, size and pressure class. For a new valve, add the process data: fluid, inlet and outlet pressure, temperature, minimum, normal and maximum flow, required leakage class, fail position, air supply and control signal. When an older positioner or valve series is no longer made, we quote the successor that Baker Hughes names and list the mounting kit it needs.
Frequently requested Masoneilan models: Masoneilan 4700E/4800E Electropneumatic Valve Positioner, Masoneilan 28000 Series VariPak Valve Seal & O-Ring Kit, Masoneilan 535H Single-Seat Pressure Reducing Regulator.
Facts checked against Baker Hughes Masoneilan product information and the company's published timeline, October 2026.
Browse Masoneilan products by category: Control Valves, Valve Actuator, Regulators, Valve Positioner, Level Transmitter.
FAQ
Questions about the Masoneilan 12810 Pneumatic Proportional-Reset Level
Answers from our engineering team on installation, compatibility and integration.
01What does reset action add to the Masoneilan 12810?
Reset lets the controller keep correcting until the level returns to its set point, which removes the offset that proportional action alone can leave. It is produced by a reset bellows and a resistance unit in the air circuit between the two bellows.
02How is the reset rate of the Masoneilan 12810 adjusted?
The reset rate knob is graduated in repeats per minute. The manual suggests starting with a low rate, widening the proportional band, raising the reset rate until cycling occurs and then setting it to about half that value.
03Can a proportional 12800 be converted to a Masoneilan 12810?
Yes. Baker Hughes lists a bellows tubing assembly, a reset bellows assembly and a resistance unit assembly as the parts required. The bellows spring is replaced by the reset bellows, the resistance unit is mounted in the lower left corner of the case and the mechanism is realigned, with 9 psi locked in the reset bellows.
04What air supply does the Masoneilan 12810 need?
The filter regulator needs clean, dry air between 50 and 125 psi gauge. It is then set to 20 psi for a 3-15 psi output range or 35 psi for a 6-30 psi range.
05Is Seven Star LLC a trusted supplier for Masoneilan products?
Yes. Seven Star LLC is a trusted supplier for Masoneilan in Oman and the GCC and supplies the Masoneilan 12810 with manufacturer documentation and regional support.


















Reviews
There are no reviews yet.