- Automation & ControlView all 2,255 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- Motor Soft Starters
- HMI Displays
- Pneumatic Cylinders
- Industrial Computers
- Servo Drives
- Machine Vision
- Automation Software
- Robotics
Brand: ifm
ifm SM8000 Magnetic-Inductive Flow Meter, G 1, 0.2-100 l/min
Description
ifm SM8000 Magnetic-Inductive Flow Meter, G 1, 0.2-100 l/min
The ifm SM8000 is a magnetic-inductive flow meter for conductive liquids from 0.2 to 100 l/min (0.01 to 6 m³/h) with a G 1 external thread (DN25). Compared with the smaller SM6004, it adds a totaliser function, a preset counter and a wider choice of outputs: switching, analogue (4 to 20 mA or 0 to 10 V), pulse and IO-Link. Accuracy is ±(0.8 % of measured value + 0.5 % of final value).
It also measures medium temperature and can monitor it with its own switching point. Seven Star LLC supplies the SM8000 in Oman and the GCC as an independent supplier in Muscat.
SM8000 technical specifications
The table lists the values published by the manufacturer for the SM8000. Where a parameter has several operating modes, the headline value is shown; the full parameter list is in the manufacturer documentation.
| Parameter | Specification |
|---|---|
| Manufacturer / part number | ifm electronic / SM8000 |
| Measuring range | 0.2 to 100 l/min / 0.01 to 6 m³/h |
| Resolution | 0.1 l/min: 0.005 m³/h |
| Process connection | threaded connection G 1 external thread DN25 flat seal |
| Dimensions [mm] | Ø 54 / L = 110 |
| Media | conductive liquids; water; hydrous media |
| Medium temperature [°C] | -10 to 70 |
| Pressure rating | 16 bar / 1.6 MPa |
| Operating voltage [V] | 18 to 30 DC (to SELV/PELV) |
| Current consumption [mA] | 95 (24 V) |
| Output signal | switching signal; analogue signal; pulse signal; IO-Link (configurable) |
| Electrical design | PNP/NPN |
| Output function | normally open / normally closed (parameterisable) |
| Permanent current rating of switching output DC [mA] | 200 |
| Analogue current output [mA] | 4 to 20; (scalable) |
| Max. load [Ω] | 500 |
| Accuracy (in the measuring range) | ± (0.8 % MW + 0.5 % MEW) |
| Accuracy [K] | ± 2.5 (Q > 5 l/min) |
| Repeatability | ± 0.2% MEW |
| Response time [s] | 0.15 (dAP = 0, T19) |
| Communication interface | IO-Link |
| Ambient temperature [°C] | -10 to 60 |
| Protection | IP 67 |
| Weight [g] | 577 |
| Materials | stainless steel (316L/1.4404); PBT-GF20; PC; FKM; TPE |
| Materials (wetted parts) | stainless steel (316L/1.4404); PEEK; FKM |
| Connector | 1 x M12; coding: A; Contacts: 4, gold-plated |
| MTTF [years] | 145 |
| Inlet / outlet pipe length | 3 x DN / 1 x DN |
| Conductivity of the medium | at least 20 uS/cm |
| Viscosity | below 70 mm2/s at 40 degrees C |
How the SM8000 works
The SM8000 is a magnetic-inductive flow meter: a magnetic field is applied across the pipe, and a conductive liquid moving through the field induces a voltage proportional to its velocity. Because nothing protrudes into the flow, there are no moving parts to wear and the pressure loss is very small. A temperature sensor in the same unit adds medium temperature as a second measured value, shown on a four-digit LED display and available on the outputs. The liquid must be conductive; the conductivity and viscosity limits stated in the table must be respected.
Where the SM8000 fits and related parts
The SM8000 is the larger and more flexible sibling of the SM6004. Use it on main cooling branches, dosing lines or process water where batch quantities (totaliser or preset counter) are required, and where the PLC can read IO-Link process data. The similar housing dimensions (54 mm diameter, 110 mm length) make mechanical replacement simple, but the G 1 thread means the adapters differ.
Selection and ordering checklist for the SM8000
Work through the points below before you confirm the order, so that the SM8000 you receive is the one your machine or plant needs.
- Confirm flow range 0.2 to 100 l/min and pipe size to G 1 (DN25)
- Check conductivity of at least 20 µS/cm and viscosity below 70 mm²/s at 40 degrees Celsius
- Check the 16 bar rating and the 10.4 bar value for CRN applications
- Decide whether you use the totaliser, the preset counter or the pulse output
- Select the output type: current, voltage, switching or IO-Link
The manufacturer lists this article under the type designation Magnetic-inductive flow meter, SMR11GGXFRKG/US-100. The article number SM8000 is the reference to quote when ordering, and the type designation is useful for technicians who compare the label on an installed unit.
Installation, commissioning and maintenance
Install the meter with the inlet and outlet pipe lengths shown in the table so that the profile is stable, and keep the pipe full at all times; air pockets cause unstable readings. Flat seals are used on the thread, so make sure the sealing surfaces are clean and the adapters fit the pipe. In cooling circuits and process water loops place the meter where bubbles will not collect at the top. Commissioning involves setting the display unit, the analogue range and the damping value, and then comparing a reading against a reference flow if the application is critical. Keep the M12 connector dry and tight, and flush the line if scale or magnetic debris could build up.
Keep the same pipe-length rules as the smaller meter (3 x DN inlet, 1 x DN outlet) and make sure the pipe stays full. The counter reset input allows batch-wise operation from a PLC. Because the meter has several output modes, document the final parameter setting on the machine, so a replacement sensor can be set up identically.
Typical applications in Oman and the GCC
Typical duties in Oman and the GCC include cooling water circuits to process equipment, chemical dosing and water treatment skids, filling and batching, and monitoring of recirculation flow through heat exchangers. Temperature monitoring on the same device helps in chilled water loops.
Flow meters in the region often sit in cooling and utility circuits that run year-round at high ambient temperature. Scale, bubbles and dirt are the main sources of error, so strainers upstream and a full pipe at the measuring point matter more than any setting in the menu.
SM8000 compared with related ifm types
The table places the SM8000 next to neighbouring types in the same application group, so you can see whether a sibling would suit the job better.
| Part number | Key characteristics | Note |
|---|---|---|
| SD6500 | Compressed air, 4-1250 l/min, R 1/2 | Related type |
| SM6004 | Mag-inductive, 0.1-25 l/min, G 1/2 | Related type |
| SM8000 | Mag-inductive, 0.2-100 l/min, G 1 | This page |
| SA5000 | Calorimetric, water/oil/air, 100 bar | Related type |
Information to send with an RFQ for the SM8000
To prepare an accurate offer for the SM8000, please include the following with your enquiry:
- Pipe size and the type of adapter needed
- Expected flow range and the minimum flow you must detect
- Medium, conductivity and temperature
- Outputs required: analogue, switching, pulse or IO-Link
- Quantity and delivery location
Documents and quotation
No datasheet is attached to this page. Send us the part number SM8000 and we will confirm which documents are available, such as the datasheet and operating instructions, and for IO-Link devices the device description file.
Seven Star LLC is an independent supplier in Muscat serving Oman and the GCC and is not affiliated with the manufacturer; the name ifm is used only to identify the product. Prices are not shown on the page, so send the part number, the quantity and the delivery location to receive a quotation.
Other Models in the Ifm Flow Range
Seven Star LLC supplies models from the Ifm Flow range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
Reviews (0)
How would you rate this product? Cancel reply
About brand
ifm is a German family-owned maker of sensors and automation products, founded in Essen in October 1969 by Robert Buck and Gerd Marhofer. Its first products were inductive proximity sensors sold under the efector name. ifm is still headquartered in Essen, and the founders' sons, Martin Buck and Michael Marhofer, have led it since 2001.
Seven Star LLC lists ifm position, distance and pressure sensors and supplies them by exact article number to plants and machine builders in Oman and the wider Gulf region.
ifm company profile
| Founded | 1969, Essen, Germany |
|---|---|
| Founders | Robert Buck and Gerd Marhofer |
| Headquarters | Essen, Germany |
| Ownership | Family-owned |
| Product families | Inductive and capacitive proximity sensors, PN pressure sensors, O1D laser distance sensors, flow and level sensors, IO-Link masters |
Milestones
- 1969: ifm is founded in Essen.
- 2001: The founders' sons take over management.
ifm sensors listed on this page
ifm identifies every device with a short article number, and that number is what we order against. Three are listed here:
- O1D100: laser distance sensor for position and distance measurement
- PN7093: pressure sensor with local display
- NG5021: inductive proximity sensor with NAMUR output
Other ifm inductive sensors, pressure sensors and connection cables can be quoted on request when you send the article number.
ifm products we list
Ordering ifm sensors: what we need
Send the six-character article number printed on the housing (two letters and four digits, or similar). If the label is worn, a photo plus the thread size, sensing range, output type and connector style is enough for us to check the part against ifm documentation. For NAMUR sensors, tell us which isolating amplifier is in the loop. Buyers in the GCC who need a successor for a discontinued article can send the old number and we will check the replacement the manufacturer names.
Facts checked against ifm's own 50-year chronicle (ifm.com), October 2026.
Browse ifm products by category: Sensors & Transmitters, Pressure Instrumentation.
FAQ
Questions about the ifm SM8000 Magnetic-Inductive Flow Meter, G 1,
Answers from our engineering team on installation, compatibility and integration.
01What is the flow range of the ifm SM8000?
The measuring range is 0.2 to 100 l/min (0.01 to 6 m³/h).
02Does the SM8000 have a totaliser?
Yes. It offers a quantity meter and a preset counter, with a counter reset input and a pulse output for quantity.
03What outputs does the SM8000 offer?
Switching, analogue 4 to 20 mA or 0 to 10 V (scalable), pulse and IO-Link, configured through the menu.
04What is the accuracy of the SM8000?
±(0.8 % of measured value + 0.5 % of the final value of the measuring range), repeatability ±0.2 % of final value.
05What thread does the SM8000 have?
G 1 external thread (DN25) with a flat seal. This is the value published by the manufacturer for the SM8000; confirm details before ordering.