Brand:

Delta DOP-100 B Basic HMI 4.3 and 7 inch IP65

Description

Delta DOP-100 B basic HMI series, 4.3 and 7 inch panels

The Delta DOP-100 B is the Basic type of Delta’s HMI range. It is designed for general machine control where an operator needs a simple touch screen, and it carries an IP65 rating that Delta positions for harsh environments. Two models are listed in the specification: the 4.3 inch DOP-103BQ and the 7 inch DOP-107BV. Seven Star LLC supplies the DOP-100 B in Oman and the GCC as an independent supplier in Muscat.

The series is easy to install and focuses on essential functions rather than cloud or network features. For that reason it suits machines whose controller already handles the logic and only needs a clear operator interface for settings, status and alarms.

Reading the model names

The model names in the DOP-100 B series follow Delta’s panel naming: the digits after DOP- show the screen size class (103 for 4.3 inch, 107 for 7 inch) and the letters that follow identify the type and variant. Rather than guess meanings from the letters, quote the complete model name from the table below.

DOP-100 B technical specifications

The table below uses the published specification for the two models.

Parameter Specification
Manufacturer / part number Delta / DOP-100 B series (models DOP-103BQ, DOP-107BV)
Display 4.3 inch TFT (DOP-103BQ); 7 inch TFT (DOP-107BV)
Resolution 480 x 272 pixels (DOP-103BQ); 800 x 480 pixels (DOP-107BV)
Colour depth 16-bit
CPU Cortex-A8, 800 MHz
ROM / RAM 256 MB / 256 MB
Serial communication 2 serial COM ports (built-in, one D-Sub connector)
USB 1 slave / 1 host
Protection rating IP65
Certification CE / UL
Operating temperature 0 to 50°C
Storage temperature -20 to 60°C
Dimensions W x H x D 137 x 103 x 37.1 mm (DOP-103BQ); 215 x 161 x 35.5 mm (DOP-107BV)
Mounting dimensions W x H 118.8 x 92.8 mm (DOP-103BQ); 196.9 x 142.9 mm (DOP-107BV)

How the DOP-100 B operates

The DOP-100 B is a stand-alone terminal with a Cortex-A8 800 MHz processor. It runs a project downloaded from the configuration software over the USB slave port, and it reads and writes registers in the connected controller through its two serial ports. The USB host port can be used for tasks such as loading data from a USB drive.

Because the panel is built around serial communication, the communication scheme is straightforward: one controller or a few devices on a serial line, polled continuously, with the panel showing values and sending operator commands back. Details such as the supported protocol driver for a particular PLC brand should be confirmed against the driver list for the model before ordering, as the supplier page does not list drivers.

Where the DOP-100 B fits and related models

Delta lists packaging, textile, woodworking, rubber and plastics machinery as typical applications. The same logic applies to simple pumping skids, small process machines and utility equipment in industrial plants, where a small panel replaces push buttons and indicator lamps.

The nearest upgrade in the range is the Standard type, the DOP-300 S series (DOP-3S07S3E2 and DOP-3S10S3E2), which adds dual Ethernet ports, three serial ports, MQTT, OPC UA, EtherNet/IP and the DIACloud service. Select the DOP-100 B when a lean, economical panel is enough, and the DOP-300 S when the project needs network or cloud connectivity.

The DOP-100 B is often used with Delta temperature controllers such as DT3, DTM and DTN, using Modbus over serial communication to display set values and alarms for heating zones.

DOP-100 B selection and ordering checklist

  • Choose 4.3 inch (DOP-103BQ) when space is tight and screens are simple; choose 7 inch (DOP-107BV) for more tags, trends and larger buttons.
  • Check the cut-out: 118.8 x 92.8 mm for DOP-103BQ and 196.9 x 142.9 mm for DOP-107BV, with the depth shown above for the housing.
  • Identify the controller brand and its serial protocol, and confirm the driver is available.
  • Count the serial ports needed; this series has two COM ports on a single D-Sub connector, so a second device may need a splitter or adapter arrangement.
  • Confirm the enclosure environment against the 0 to 50°C operating range.
  • Plan how the project will be downloaded and backed up using the USB ports.

Installation and maintenance of the DOP-100 B

Cut the panel opening to the mounting dimensions, insert the unit from the front and secure it with the mounting clips from behind. To keep the IP65 rating at the front face, the gasket must be seated evenly and the cut-out edges must be clean and flat. Do not mount the panel where it will be exposed to direct sun or radiant heat.

For serial wiring, use shielded cable, keep it away from power conductors, and ground the shield at one end. Label the COM port and baud rate settings in the project documentation, because mismatched communication parameters are the most common cause of a panel showing no data.

Maintenance is limited to cleaning the front, inspecting the gasket for hardening, and keeping a verified copy of the project. A replacement of the same model can be loaded with the stored project.

Applications of the DOP-100 B in Oman and the GCC

In Oman and the GCC the Basic HMI is used on packaging lines, plastic extrusion and moulding machines, small pump and compressor packages, water treatment dosing skids and workshop equipment. The main environmental factors are heat and dust. The IP65 front face helps with dust and washdown splash at the panel surface, but the operating range of 0 to 50°C means the panel should be shaded and kept out of unventilated enclosures in summer.

DOP-100 B model comparison

Item DOP-103BQ DOP-107BV
Item DOP-103BQ DOP-107BV
Screen size 4.3 inch 7 inch
Resolution 480 x 272 800 x 480
External size (mm) 137 x 103 x 37.1 215 x 161 x 35.5
Cut-out (mm) 118.8 x 92.8 196.9 x 142.9
CPU / memory Cortex-A8 800 MHz, 256 MB / 256 MB Cortex-A8 800 MHz, 256 MB / 256 MB

Information to send with a DOP-100 B request

  • Model name (DOP-103BQ or DOP-107BV) and quantity.
  • Controller brand, model and communication protocol.
  • Port type needed and cable length.
  • Cabinet door thickness and available depth.
  • Delivery location in Oman or the GCC.

Documents and quotation

Seven Star LLC is an independent supplier in Muscat and quotes the Delta DOP-100 B to customers in Oman and the GCC. Send us the exact model code, quantity and delivery location and we will confirm availability and lead time.

No datasheet file is attached on this page. Send the part number and we will confirm available documents, including manuals and engineering drawings for the model you need.

Other Models in the Delta Hmi Range

Seven Star LLC supplies models from the Delta Hmi range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Delta DOP-300 S Standard HMI 7 and 10.1 inchHMI DisplaysView details
Delta DOP-100 B Basic HMI 4.3 and 7 inch IP65HMI DisplaysYou are viewing this model
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Delta Electronics is a Taiwanese maker of power and automation products, founded in April 1971 by Bruce Cheng with 15 employees in a small factory in Sinjhuang, Taipei County. Its first products were TV deflection coils and electronic components; it later became a leading maker of switching power supplies and added drives, PLCs and HMIs for industrial automation. Delta is headquartered in Neihu, Taipei, and listed on the Taiwan Stock Exchange.

Seven Star LLC lists the Delta DVP04AD-S2 analog input module and the ESR-48/30D rectifier module, and sources Delta PLC modules and power parts for panel builders and maintenance teams in Oman and the GCC.

Delta company profile

Founded April 1971, Sinjhuang, Taipei County, Taiwan
Founder Bruce C.H. Cheng
First products TV deflection coils and electronic components
Headquarters Neihu District, Taipei, Taiwan
Listing Taiwan Stock Exchange (2308)
Product families DVP and AS series PLCs, C2000 Plus, CP2000, CH2000, MH300 and ME300 AC motor drives, REG2000 regenerative units, DIN Pro and DIN Eco DIN-rail power supplies, HMIs and servo systems

Milestones

  • 1971: Bruce Cheng founds Delta with 15 employees.
  • 1975: Delta is reorganised as a company limited by shares.
  • 2021: Delta marks 50 years.

Delta PLC families and the DVP slim line

Delta's controller program runs from the DVP series through the modular AS series to the AH series. Inside the DVP series, the slim CPUs (among them DVP-SS2, SA2, SX2, SV2 and SE) take slim expansion modules on their right side. The DVP04AD-S2 is one of these: a four-channel analog input module for voltage or current signals, which the CPU reads with FROM and TO instructions.

Delta products we list

Family Examples
AC Drives C2000 Plus High Performance Vector Contr…, CH2000 Heavy Duty Vector Control Drive f…, CP2000 Fan and Pump Vector Control Drive, ME300 Basic Compact AC Motor Drive, MH300 High Performance Compact Vector Co…, MS300 Standard Compact AC Motor Drive, REG2000 Power Regenerative Unit
PLC & I/O Cards AS Series Compact Modular Mid-Range PLC…, DVP Series Programmable Logic Controller…, DVP04AD-S2 DVP-S Series 4-Channel Analog…
Power Modules DIN Eco Series 3-Phase DIN Rail Power Su…, DIN Pro Series Single-Phase DIN Rail Pow…, ESR-48/30D Rectifier Module Power Supply

Ordering Delta parts: what we need

For PLC modules, send the complete type from the side label, including the suffix, and the CPU model it will join. For a rectifier module, send the type, the DC output voltage and current, the AC input, and the model of the power shelf or system it plugs into.

Facts checked against Delta's own 50th anniversary timeline (delta50.deltaww.com), October 2026.

FAQ

Questions about the Delta DOP-100 B Basic HMI 4.3 and 7 inch IP65

Answers from our engineering team on installation, compatibility and integration.

01Which models are in the Delta DOP-100 B series?
The published specification lists the DOP-103BQ (4.3 inch, 480 x 272) and the DOP-107BV (7 inch, 800 x 480). Both use a Cortex-A8 800 MHz CPU.
02What protection rating does the DOP-100 B have?
Delta states an IP65 rating for the Basic HMI. This applies to the front panel when it is correctly mounted with its gasket in a suitable cut-out.
03How many communication ports does the DOP-100 B have?
The panel has two serial COM ports and USB with one slave and one host port. It does not list Ethernet in the specification.
04What are the mounting cut-outs for the DOP-100 B?
The cut-out is 118.8 x 92.8 mm for the DOP-103BQ and 196.9 x 142.9 mm for the DOP-107BV.
05What temperature range applies to the DOP-100 B?
Operating temperature is 0 to 50°C and storage temperature is -20 to 60°C. Use shaded, ventilated enclosures in hot installations.