Brand: Yokogawa
Yokogawa EJA530E-JBH9N-032EN Hastelloy Gauge Pressure
Description
Specification story of EJA530E-JBH9N-032EN
Start from the process, not the catalogue. If the fluid is a mild acid or a hydrogen sulfide bearing condensate, 316L might not last at the diaphragm and process connector. Yokogawa EJA530E-JBH9N-032EN answers that with Hastelloy C-276 throughout the wetted path. The B capsule gives a gauge-pressure span of 0.02 to 2 MPa, the process connection is M20 x 1.5 DIN male, and a corrosion-resistant aluminum housing carries an LCD with a range-setting push button. Output is HART at 4 to 20 mA.
EJA530E-JBH9N-032EN suffix, character by character
| Code position | Meaning |
|---|---|
| -J | 4 to 20 mA DC with HART 5 or HART 7 digital communication (selected at ordering) |
| B | Capsule: span 0.02 to 2 MPa |
| H | Hastelloy C-276 for process connector, diaphragm and other wetted parts |
| 9 | Process connection: M20 x 1.5 DIN 16 288 male |
| 3 | Amplifier housing: cast aluminum alloy with corrosion resistance properties |
| 2 | Electrical: 1/2 NPT female, two electrical connections, no blind plugs |
| E | Integral indicator: digital indicator with range-setting push button |
| N | Mounting bracket: none |
How capsule B behaves
Upper range limit and working pressure are 2 MPa (290 psig). Over-pressure is 4 MPa and burst 30 MPa. Accuracy is plus or minus 0.055 percent of span for spans of 0.2 MPa and up, and the gauge unit is rated for plus or minus 0.1 percent of URL stability over ten years. The range can go to minus 0.1 MPa, and zero can be set fully elevated or suppressed within capsule limits.
Data table for EJA530E-JBH9N-032EN
| Item | Value |
|---|---|
| Wetted parts | Hastelloy C-276: connector, diaphragm and other |
| Process thread | M20 x 1.5 DIN male |
| Housing 3 | Cast aluminum with corrosion resistance properties, copper content 0.03 percent or less, iron 0.15 percent or less |
| Electrical entries | 1/2 NPT female x2 |
| Indicator | Digital, E version with push button |
| Local settings | Loop test, tag, unit, LRV, URV, damping, output mode, display, re-range by applied pressure |
| Output | 4 to 20 mA, HART 5/7 |
| Bracket | None |
| Over-pressure | 4 MPa |
| Marine/NACE | Materials conform to NACE MR0175/ISO 15156 and MR0103 |
Application notes: chemical and sour service
Typical tasks include produced-water treatment, amine regenerator feed, desalination chemical injection and sour condensate lines. The datasheet does not endorse every fluid and warns to check compatibility; confirm with the manufacturer for very aggressive media.
Housing 3 versus 1 and 2
Housing code 3 improves corrosion resistance over standard aluminum with strictly limited copper and iron content, but it cannot be combined with electrical connection codes 0, 5, 7, 9 or A; the EJA530E-JBH9N-032EN electrical code 2 is allowed. The stainless housing 2, by contrast, adds 1.5 kg according to the datasheet.
Installation checkpoints
Tighten the M20 x 1.5 male connector with a suitably sized seal. Mount in a place where drain and vent are accessible. After wiring, use the push button to confirm LRV and URV, using actual pressure from a hand pump. Because the indicator can show up to three of pressure in percent, scaled pressure and measured pressure in rotation, decide at commissioning which values the operator needs, and write the choice on the loop sheet. The 5-digit numeric display, 6-digit unit field and bar graph are visible through the cover glass, so mount the transmitter with the display toward the walkway.
Spare-part tips for EJA530E-JBH9N-032EN
Keep the nameplate image on file. Since the wetted parts are Hastelloy, replacement time from stock may differ; the bracket field is N so plan to supply a bracket separately if needed.
If the chemistry allows, the S wetted code reduces cost and offers DIN thread options without restriction on the D capsule. If you want the same wetted parts but need to read pressure without a handheld, note that this code already carries the E indicator. Different thread, different capsule or an added bracket each make a distinct part number from EJA530E-JBH9N-032EN. Options after the slash include fluoro-rubber O-rings (/HE) that limit the lower ambient temperature to minus 15 degrees C, 316 SST exterior screws (/HC), a wired 316 SST tag plate (/N4) and degreased cleaning for oxygen service (/K1 and related codes). None is included in the base code quoted here.
For a quotation, the nameplate image, tag and process data allow us to confirm that the code matches the loop requirement and to avoid delays from reorders.
Quick answers about EJA530E-JBH9N-032EN
- What material touches the process in EJA530E-JBH9N-032EN? Hastelloy C-276 is used for the process connector, diaphragm and other wetted parts because of the H code.
- What thread does the 9 select? M20 x 1.5 DIN 16 288 male. The datasheet notes that DIN threads are based on the withdrawn DIN 16 288.
- Why is housing 3 combined with electrical 2? Housing 3 is not available with electrical codes 0, 5, 7, 9 or A, and code 2 is a valid choice.
- Does the E indicator allow re-ranging? Yes, E adds a range-setting push button so LRV and URV can be set locally.
- What pressure range does it cover? The B capsule covers a span of 0.02 to 2 MPa with a range from minus 0.1 to 2 MPa gauge.
Documents and quotation
Please state the process medium in your RFQ so wetted-material suitability can be reviewed.
Attach or request the Yokogawa general specification GS 01C31F01-01EN for this family; it is provided as the datasheet PDF with the product listing. Your RFQ should state the part number EJA530E-JBH9N-032EN, quantity, tag numbers, process medium and any hazardous-area approval. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Availability and delivery are confirmed per enquiry.
Spares and Lifecycle Considerations
For critical service, many plants hold one Yokogawa EJA530E-JBH9N-032EN as an operational spare rather than waiting for a failure. When you plan spares, look at how many identical pressure transmitters units are installed, how long a replacement would take to arrive, and the cost of an unplanned stop. Store spare units in their original packaging in a dry, temperature-controlled area and record the part number and serial number in your maintenance system. We can quote single units or a small spares package and confirm the lead time for each item in writing.
Other Models in the EJA530E Range
Seven Star LLC supplies models from the EJA530E range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Yokogawa EJA530E-DAS4N-012NN Gauge Pressure Transmitter | Pressure Transmitters | View details |
| Yokogawa EJA530E-JCS8N-014DL Gauge Pressure, G1/2 Male | Pressure Transmitters | View details |
| Yokogawa EJA530E-JBH9N-032EN Hastelloy Gauge Pressure | Pressure Transmitters | You are viewing this model |
Datasheets & Documents
- Datasheet Yokogawa EJA530E-JBH9N-032EN Hastelloy Gauge Pressure Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.
Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.
Yokogawa at a glance
| Established | 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki |
|---|---|
| Milestones | Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986 |
| Headquarters | Tokyo, Japan |
| Product families | Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers |
Yokogawa products we list
| Family | Models | Typical use |
|---|---|---|
| Pressure and DP transmitters | EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable | Pressure, level and DP flow measurement in process plants |
| Temperature transmitters | YTA610, YTA710 | RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus |
| Flowmeters | ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 | Water and conductive liquids, mass flow of hydrocarbons, steam and gas |
| Analysers | TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover | Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen |
| Controllers and recorders | UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 | Single-loop control, furnace programs and data recording |
| Control and safety systems | CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 | Spares and expansions for CENTUM DCS, safety systems and STARDOM |
| Battery packs | S9129FA, S9185FA, S9548FA | Memory backup batteries for DCS and controller modules |
The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.
Where Yokogawa products are used
In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.
Ordering Yokogawa products: what we need
Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.
Facts checked against Yokogawa's corporate history, October 2026.
Browse Yokogawa products by category: PLC & I/O Cards, Flowmeters, Pressure Instrumentation, Automation Accessories, Temperature Instrumentation.
FAQ
Questions about the Yokogawa EJA530E-JBH9N-032EN Hastelloy Gauge
Answers from our engineering team on installation, compatibility and integration.
01What material touches the process in EJA530E-JBH9N-032EN?
Hastelloy C-276 is used for the process connector, diaphragm and other wetted parts because of the H code.
02What thread does the 9 select?
M20 x 1.5 DIN 16 288 male. The datasheet notes that DIN threads are based on the withdrawn DIN 16 288.
03Why is housing 3 combined with electrical 2?
Housing 3 is not available with electrical codes 0, 5, 7, 9 or A, and code 2 is a valid choice.
04Does the E indicator allow re-ranging?
Yes, E adds a range-setting push button so LRV and URV can be set locally.
05What pressure range does it cover?
The B capsule covers a span of 0.02 to 2 MPa with a range from minus 0.1 to 2 MPa gauge.