Brand: Yokogawa
Yokogawa EJA530E-JCS8N-014DL Gauge Pressure, G1/2 Male
Description
European threads on EJA530E-JCS8N-014DL
Metric and BSP threads dominate many European-built skids shipped to the Gulf. Yokogawa EJA530E-JCS8N-014DL is built for that world: a G1/2 DIN 16 288 male process connection and M20 female conduit entries (two of them, no blind plugs). On top of the thread choice, it adds a digital indicator and a 316 SST two-inch pipe bracket, so the unit is ready to go onto a pipe stand with a readable display. The C capsule works from 0.1 to 10 MPa gauge pressure, with HART output.
What each character means in EJA530E-JCS8N-014DL
| Code position | Meaning |
|---|---|
| -J | 4 to 20 mA DC with HART 5 or HART 7 digital communication (selected at ordering) |
| C | Capsule: span 0.1 to 10 MPa |
| S | 316L SST process connector, Hastelloy C-276 diaphragm, 316L SST or F316L SST other wetted parts |
| 8 | Process connection: G1/2 DIN 16 288 male |
| 1 | Amplifier housing: cast aluminum alloy |
| 4 | Electrical: M20 female, two electrical connections, no blind plugs |
| D | Integral indicator: digital indicator |
| L | Mounting bracket: 316 SST 2-inch pipe mounting bracket |
The C capsule in numbers
Upper range limit and maximum working pressure are 10 MPa (1450 psig), with 20 MPa over-pressure and 30 MPa burst. The span runs from 0.1 to 10 MPa and the range can reach down to minus 0.1 MPa, handy for pumps with suction lift. Accuracy is plus or minus 0.055 percent of span at spans of 1 MPa and above. Stability is plus or minus 0.1 percent URL over ten years for the EJA530E, against plus or minus 0.2 percent for the absolute EJA510E. Update period is 45 ms and response time 90 ms.
Comparison with a female NPT build
A G1/2 male thread is a parallel pipe thread, it is not interchangeable with 1/2 NPT even though both are described as half inch; the datasheet notes the threads follow the withdrawn DIN 16 288. The datasheet lists four process options: 1/2 NPT female, 1/2 NPT male, G1/2 DIN male and M20 x 1.5 DIN male. For EJA530E-JCS8N-014DL, the choice is the G1/2 one. Because the thread is parallel rather than tapered, sealing is normally made with a gasket or sealing washer, so follow the fitting maker instructions.
Summary of EJA530E-JCS8N-014DL data
| Item | Value |
|---|---|
| Capsule | C, 0.1 to 10 MPa gauge |
| URL = MWP | 10 MPa (1450 psig) |
| Over-pressure | 20 MPa |
| Connection | G1/2 DIN 16 288 male |
| Conduit entries | M20 female x2 |
| Indicator | Digital LCD |
| Bracket | 316 SST, 2-inch pipe |
| Output | 4 to 20 mA HART |
| Ambient range with LCD | Minus 30 to 80 degrees C |
| Housing | Aluminum alloy, IP66/IP67 |
| Weight | 1.2 kg before indicator and bracket; add 1.5 kg only for stainless housing |
Applications for a 10 MPa gauge transmitter
Hydraulic power packs, lube-oil supply headers on turbines, boiler feedwater discharge at moderate pressure, cooling water loop pressure and pneumatic supply on instrument skids. On skids built in Europe or Asia to metric standards, the G1/2 male port plugs directly into the manifold block.
Wiring through M20 glands
M20 entries need glands rated for the approval category of the area. Use cable glands with IP66 or better and torque them, because a loose gland defeats the housing rating. If hazardous-area approval code is added later, the certificate rules for gland type apply. HART communication requires 250 ohm minimum loop resistance and a supply of at least 16.6 V at the terminals.
Spares and handling for EJA530E-JCS8N-014DL
Keep a spare sealing washer for the DIN thread and note that disassembling the amplifier is not recommended in the field. Check the LCD indication against a reference gauge annually.
For EJA530E-JCS8N-014DL the family offers alternatives that change one decision at a time. If your skid uses NPT ports, the 1/2 NPT female code 4 or male code 7 replaces the G1/2 thread. If the pressure never exceeds 2 MPa, the B capsule has a finer minimum span of 0.02 MPa. If power and signal are required in a hazardous area, approval options such as ATEX flameproof KF22, IECEx SF22, FM FF1 and CSA CF1 are listed in the datasheet, and they use electrical codes 2, 4, 7, 9, C or D, which means M20 entry code 4 here is compatible. Intrinsic safety approvals are not applicable to the 1 to 5 V low-power output but are available with J.
Option /HAC reduces the reference error to plus or minus 0.04 percent of span for spans of 1 MPa and above, which matters when the transmitter feeds custody or efficiency calculations.
Quick answers about EJA530E-JCS8N-014DL
- Is the G1/2 thread on EJA530E-JCS8N-014DL tapered? No. G1/2 DIN 16 288 is a parallel thread, not a tapered 1/2 NPT thread, so it is sealed with a washer or gasket.
- What do the 014 in the suffix mean? The first digit after the hyphen is always 0, 1 is cast aluminum housing and 4 is M20 female conduit entries without blind plugs.
- Does EJA530E-JCS8N-014DL include a bracket? Yes. L is a 316 SST two-inch pipe bracket.
- What is the range of the C capsule? 0.1 to 10 MPa span with a lower range limit of minus 0.1 MPa gauge.
- Can this model show pressure locally? Yes. Indicator code D provides a five-digit LCD with a bar graph. It cannot re-range by push button unless code E is used.
Documents and quotation
If your skid uses a different thread than G1/2, mention it so we can offer the right code.
Attach or request the Yokogawa general specification GS 01C31F01-01EN for this family; it is provided as the datasheet PDF with the product listing. Your RFQ should state the part number EJA530E-JCS8N-014DL, quantity, tag numbers, process medium and any hazardous-area approval. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Availability and delivery are confirmed per enquiry.
Other Models in the EJA530E Range
Seven Star LLC supplies models from the EJA530E range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Yokogawa EJA530E-DAS4N-012NN Gauge Pressure Transmitter | Pressure Transmitters | View details |
| Yokogawa EJA530E-JCS8N-014DL Gauge Pressure, G1/2 Male | Pressure Transmitters | You are viewing this model |
Datasheets & Documents
- Datasheet Yokogawa EJA530E-JCS8N-014DL Gauge Pressure, G1/2 Male Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.
Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.
Yokogawa at a glance
| Established | 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki |
|---|---|
| Milestones | Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986 |
| Headquarters | Tokyo, Japan |
| Product families | Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers |
Yokogawa products we list
| Family | Models | Typical use |
|---|---|---|
| Pressure and DP transmitters | EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable | Pressure, level and DP flow measurement in process plants |
| Temperature transmitters | YTA610, YTA710 | RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus |
| Flowmeters | ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 | Water and conductive liquids, mass flow of hydrocarbons, steam and gas |
| Analysers | TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover | Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen |
| Controllers and recorders | UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 | Single-loop control, furnace programs and data recording |
| Control and safety systems | CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 | Spares and expansions for CENTUM DCS, safety systems and STARDOM |
| Battery packs | S9129FA, S9185FA, S9548FA | Memory backup batteries for DCS and controller modules |
The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.
Where Yokogawa products are used
In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.
Ordering Yokogawa products: what we need
Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.
Facts checked against Yokogawa's corporate history, October 2026.
Browse Yokogawa products by category: PLC & I/O Cards, Flowmeters, Pressure Instrumentation, Automation Accessories, Temperature Instrumentation.
FAQ
Questions about the Yokogawa EJA530E-JCS8N-014DL Gauge Pressure, G1/2
Answers from our engineering team on installation, compatibility and integration.
01Is the G1/2 thread on EJA530E-JCS8N-014DL tapered?
No. G1/2 DIN 16 288 is a parallel thread, not a tapered 1/2 NPT thread, so it is sealed with a washer or gasket.
02What do the 014 in the suffix mean?
The first digit after the hyphen is always 0, 1 is cast aluminum housing and 4 is M20 female conduit entries without blind plugs.
03Does EJA530E-JCS8N-014DL include a bracket?
Yes. L is a 316 SST two-inch pipe bracket.
04What is the range of the C capsule?
0.1 to 10 MPa span with a lower range limit of minus 0.1 MPa gauge.
05Can this model show pressure locally?
Yes. Indicator code D provides a five-digit LCD with a bar graph. It cannot re-range by push button unless code E is used.