Brand:

Yokogawa EJA530E-DAS4N-012NN Gauge Pressure Transmitter

Description

The reference code: Yokogawa EJA530E-DAS4N-012NN

Yokogawa prints one example of a complete model code in the EJA530E datasheet, and it is EJA530E-DAS4N-012NN. That alone explains why the number is requested so often: it is the typical configuration the company itself illustrates. It describes an in-line gauge pressure transmitter with the lowest-pressure A capsule, BRAIN protocol on the 4 to 20 mA loop, 316L stainless wetted parts with a Hastelloy C-276 diaphragm, a 1/2 NPT female process port, an aluminum housing and two 1/2 NPT conduit entries. There is no indicator and no bracket.

Because the D output code uses BRAIN rather than HART, this is a unit for plants whose terminals and host systems already use BRAIN, and for engineers who simply want to keep an existing loop configuration.

Position-by-position reading of EJA530E-DAS4N-012NN

Code position Meaning
-D 4 to 20 mA DC with BRAIN digital communication
A Capsule: span 10 to 200 kPa
S 316L SST process connector, Hastelloy C-276 diaphragm, 316L SST or F316L SST other wetted parts
4 Process connection: 1/2 NPT female
1 Amplifier housing: cast aluminum alloy
2 Electrical: 1/2 NPT female, two electrical connections, no blind plugs
N Integral indicator: none
N Mounting bracket: none

Low-pressure behaviour of the A capsule

The A capsule spans 10 to 200 kPa, with a range limit from minus 100 kPa to 200 kPa since the EJA530E is a gauge unit; the upper range limit and maximum working pressure are both 200 kPa (29 psig), and over-pressure is 4 MPa. Accuracy is plus or minus 0.055 percent of span at spans of 20 kPa or larger, and below that the datasheet applies a term proportional to URL over span. Stability is plus or minus 0.1 percent of URL for 10 years. Because capsule A is the most sensitive, tilting the transmitter 90 degrees can move zero by up to 0.21 kPa, a noticeable fraction of a 10 kPa span.

Electrical and environmental data of EJA530E-DAS4N-012NN

Item Value
Output 4 to 20 mA DC, BRAIN protocol (code D)
Output range 3.6 to 21.6 mA
Failure alarm Up-scale 110 percent (21.6 mA or more) or down-scale minus 5 percent (3.2 mA or less)
Supply 10.5 to 42 V DC, minimum 16.6 V for communication
Loop load 0 to 1290 ohm; 250 to 600 ohm for communication
BRAIN cable length Up to 2 km with CEV polyethylene PVC-sheathed cable
Ambient temperature Minus 40 to 85 degrees C
Process temperature Minus 40 to 120 degrees C
Protection IP66/IP67, Type 4X
Burst pressure 30 MPa (A, B and C capsules)
Weight 1.2 kg without indicator or bracket

Typical duties for EJA530E-DAS4N-012NN

Low-range gauge pressure turns up in boiler furnace purge checks, filter differential supervision where the other side is atmospheric, flare header and blower discharge monitoring, tank blanket pressure on nitrogen padded storage, and HVAC air handling for utility buildings. Under 200 kPa, the 1/2 NPT female thread is easy to connect with tube or pipe fittings.

Why BRAIN instead of HART

The suffix character D selects BRAIN. It is read with a BRAIN terminal or with host systems that support the BRAIN protocol. HART, code J, is the common choice for new multi-vendor systems. If your DCS input card is a plain 4 to 20 mA card and you use a handheld that speaks BRAIN, EJA530E-DAS4N-012NN is the match. Switching between protocols in the field is not possible; the choice is made at manufacture.

Mounting and start-up

Because no bracket is part of EJA530E-DAS4N-012NN, direct mounting on a rigid pipe or an instrument stand is common. Connect with the 1/2 NPT female thread using a suitable sealant, keep the process port from collecting liquid when gas is measured, and close the covers fully after wiring. Apply known low pressure and adjust zero with the external screw, which has 0.01 percent resolution of span.

Avoid blowing air into the port for cleaning, since a single mistaken pulse above 4 MPa is beyond the over-pressure rating. Replace weathered O-rings in the amplifier cover if you see swelling; fluoro-rubber O-rings are an option.

Related variants of EJA530E-DAS4N-012NN

The same housing and electronics are shared by every EJA530E code, so spare covers, indicators and amplifier assemblies follow the family and not the capsule. What changes EJA530E-DAS4N-012NN into a different part number is any one position in the suffix: swapping A for B moves the span window to 0.02 to 2 MPa, changing 4 for 7 turns the port into a male thread, changing D for J swaps BRAIN for HART, and adding D or E in the ninth position adds an indicator. Slash options such as /A lightning protector, /HAC high accuracy of plus or minus 0.04 percent of span, /C2 and /C3 NAMUR output limits, or /D1 psi calibration create further distinct orders, so mention them if your nameplate shows them.

Nameplates also carry a tag and a calibrated range. Send a photo if you can, because the calibrated range tells us whether the unit was supplied with a calibration option.

Quick answers about EJA530E-DAS4N-012NN

  • Why is EJA530E-DAS4N-012NN considered the typical code? Yokogawa lists it as the example model code in the datasheet, with arrow-marked typical selections in each position.
  • Does the D in EJA530E-DAS4N-012NN mean digital or HART? No. D selects 4 to 20 mA with BRAIN digital communication; J would select HART.
  • What is the pressure range of this unit? The A capsule gives a span of 10 to 200 kPa with a range from minus 100 to 200 kPa gauge.
  • What is the over-pressure rating for capsule A? 4 MPa according to the datasheet, with 30 MPa burst pressure for A, B and C capsules.
  • Can I mount EJA530E-DAS4N-012NN without a bracket? Yes. The bracket position is N, so no bracket is supplied and the transmitter is mounted directly or on a separately ordered bracket.

Documents and quotation

The base code is quoted without optional slash codes.

Attach or request the Yokogawa general specification GS 01C31F01-01EN for this family; it is provided as the datasheet PDF with the product listing. Your RFQ should state the part number EJA530E-DAS4N-012NN, quantity, tag numbers, process medium and any hazardous-area approval. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Availability and delivery are confirmed per enquiry.

Datasheets & Documents
  • PDF Datasheet Yokogawa EJA530E-DAS4N-012NN Gauge Pressure Transmitter Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.

Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.

Yokogawa at a glance

Established 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki
Milestones Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986
Headquarters Tokyo, Japan
Product families Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers

Yokogawa products we list

Family Models Typical use
Pressure and DP transmitters EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable Pressure, level and DP flow measurement in process plants
Temperature transmitters YTA610, YTA710 RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus
Flowmeters ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 Water and conductive liquids, mass flow of hydrocarbons, steam and gas
Analysers TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen
Controllers and recorders UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 Single-loop control, furnace programs and data recording
Control and safety systems CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 Spares and expansions for CENTUM DCS, safety systems and STARDOM
Battery packs S9129FA, S9185FA, S9548FA Memory backup batteries for DCS and controller modules

The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.

Where Yokogawa products are used

In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.

Ordering Yokogawa products: what we need

Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.

Facts checked against Yokogawa's corporate history, October 2026.

FAQ

Questions about the Yokogawa EJA530E-DAS4N-012NN Gauge Pressure

Answers from our engineering team on installation, compatibility and integration.

01Why is EJA530E-DAS4N-012NN considered the typical code?
Yokogawa lists it as the example model code in the datasheet, with arrow-marked typical selections in each position.
02Does the D in EJA530E-DAS4N-012NN mean digital or HART?
No. D selects 4 to 20 mA with BRAIN digital communication; J would select HART.
03What is the pressure range of this unit?
The A capsule gives a span of 10 to 200 kPa with a range from minus 100 to 200 kPa gauge.
04What is the over-pressure rating for capsule A?
4 MPa according to the datasheet, with 30 MPa burst pressure for A, B and C capsules.
05Can I mount EJA530E-DAS4N-012NN without a bracket?
Yes. The bracket position is N, so no bracket is supplied and the transmitter is mounted directly or on a separately ordered bracket.