Brand:

Yokogawa UT35A-000-10-00 Single-Loop Digital Indicating Controller

Description

Yokogawa UT35A-000-10-00 overview

The Yokogawa UT35A-000-10-00 is the general-purpose single-loop model in the Yokogawa UTAdvanced digital indicating controller family. It uses the same 96 x 96 mm case, 65 mm panel depth, 14-segment color LCD and navigation-key operation as the UT55A, but its control mode is single-loop control with a fixed 200 ms control period, which makes it the cost-conscious choice for simple temperature, pressure or level loops.

In the order code Yokogawa UT35A-000-10-00 the -0 selects the standard control type, the next 0 and 0 select no additional contact I/O block and no open network, -1 is an English guide display, 0 is a white case and -00 is the fixed code. The manufacturer’s general specification also covers the 48 x 96 mm UT32A in the same document, so the UT35A is easy to confuse with its narrow sibling when searching for a replacement.

This page describes the UT35A-000-10-00 as published in the manufacturer’s general specification GS 05P01D31, written in our own words for buyers who need to identify the exact part. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. We supply against the part number you provide and do not substitute without your written agreement.

Key features of the UT35A-000-10-00

  • 14-segment active color LCD with 21.5 mm PV character height and a guide display for parameter names.
  • Universal input and retransmission output (or 15 V DC loop power supply) as standard, with two contact inputs and three contact outputs in the basic form.
  • Single-loop control with PID, ON/OFF and heating/cooling control types, auto-tuning, and the Super overshoot-suppressing function.
  • Ladder sequence function as standard, with up to 300 program steps in this model.
  • Four alarm settings and up to eight alarm output points depending on the model code.
  • Open-network choices through the Type 3 code, including RS-485, Ethernet with serial gateway, CC-Link, PROFIBUS-DP and DeviceNet, each with Modbus master function where stated.
  • Front panel protection to IP66 and NEMA 4 (hose-down test only) except side-by-side mounting.

UT35A-000-10-00 technical specifications

Item Specification
Model UT35A, digital indicating controller, panel mounting
Order code UT35A-000-10-00 (Type 1 -0, Type 2 0, Type 3 0, language -1, case color 0, fixed code -00)
Case size 96 mm x 96 mm x 65 mm deep from the panel surface
Panel cutout 92 mm x 92 mm (plus 0.8 mm / minus 0 tolerance)
Weight 0.5 kg or less
Control mode Single-loop control
Control period 200 ms
Display 5-digit 14-segment color LCD, PV character height 21.5 mm
Universal input 1 point: thermocouple, RTD, DC voltage, DC current; type K accuracy 0.1 percent of range plus 1 digit for 0 degC or more
Inputs and outputs (code x0x) 1 analog input, 1 analog output, 2 contact inputs, 3 contact outputs
Ladder capacity Up to 300 steps; up to 7 digital inputs and 8 digital outputs for the ladder
Alarms 4 alarm settings; up to 8 alarm output points depending on model code
Power supply 100 to 240 V AC, 50/60 Hz; 24 V AC/DC with option /DC
Power consumption 18 VA
Ambient temperature -10 to 50 degC (side-by-side mounting -10 to 40 degC)
Front protection IP66, NEMA 4 (hose-down test only)

The values above are taken from the manufacturer’s general specification for the UT35A and UT32A digital indicating controllers. Treat the document as the controlling reference and confirm every figure against the latest revision before final design, because the manufacturer may change specifications without notice.

Typical applications in oil and gas, utilities, water and manufacturing

Controllers of this class suit oil and gas package skids, gas-fired heaters and reboilers, glycol and amine units, desalination and water-treatment heating and dosing loops, packaging and food lines, laboratory furnaces and ovens, and pump-house or compressor utilities across Oman and the GCC. Small loops do not justify a DCS point, yet they must hold a setpoint, raise an alarm and share data with a PLC or SCADA system.

A buyer who already has the UT35A-000-10-00 installed usually wants the same suffix code again, which keeps panel cutouts, terminal layouts, spare stocks and documentation unchanged. That is the main reason this exact part number is searched for rather than a generic description.

Selection and compatibility notes for the UT35A-000-10-00

  • Type 1: -0 standard, -1 position proportional, -2 heating/cooling. Type 2 adds contact inputs and outputs (0 none, 1 two extra DIs and DOs, 2 five extra DIs and DOs).
  • Type 3 selects the open network (0 none, 1 RS-485, 2 Ethernet, 3 CC-Link, 4 PROFIBUS-DP, 5 DeviceNet).
  • Options include /LP (24 V DC loop supply), /HA (heater break alarm), /DC (24 V AC/DC supply), /CT (coating), /CV (terminal cover), /MDL (DIN rail type) and /RSP (non-isolated remote input).
  • If cascade control or multiple analog inputs are needed, the UT55A is the better fit; for a program (ramp/soak) profile, the UP35A is the related model.

Parameter and ladder data can be prepared on a PC with the LL50A parameter setting software, which is sold separately.

Installation and commissioning

Mount the controller from the front of the panel using the supplied upper and lower brackets in a cutout of the size listed above, within the panel thickness range in the general specification. Keep the mounting angle within 30 degrees above horizontal with no downward tilt. Wire signals and power to the M3 screw terminals with square washers, keep sensor wiring away from power cables, and observe the allowable wiring resistance for RTD inputs. Allow a warm-up time of 30 minutes before judging accuracy, set the input type and range, configure alarms and the control mode, and run auto-tuning once the process is stable.

Before energising a UT35A-000-10-00 in a hazardous or critical service, confirm that the selected variant, enclosure rating and any approvals you require are covered by the order string and by your site rules.

Maintenance and spare parts

The controller has no moving parts and stores parameters in nonvolatile memory. Routine care means checking terminals for tightness, keeping the front panel and vents clean, verifying input accuracy against a calibrator at intervals set by your quality system, and exercising alarm and relay outputs. Keep a record of parameters, ladder programs and the order string so that a replacement unit can be configured quickly. Note that relay contacts have a finite life under heavy loads, so heavily switched outputs may be better driven through an external relay or solid-state device.

Related products and ordering notes

The UT35A-000-10-00 belongs to the UT35A and UT32A digital indicating controllers group. Related family members, modules, software and accessories are listed in the same general specification, and we can quote them together with the UT35A-000-10-00 when you need a complete panel or loop. Because many Yokogawa instruments are specified by long suffix strings, always quote the complete order code, the option codes, the quantity and the destination. If your installed unit is an older revision, send a nameplate photograph or the exact code printed on it so that compatibility can be checked before any quotation is issued.

Frequently asked questions about the UT35A-000-10-00

  • Is the UT35A-000-10-00 a single-loop controller only? Yes. According to the general specification its control mode is single-loop control with a 200 ms control period; cascade and other multi-loop modes belong to the UT55A.
  • What does the -000 part of UT35A-000-10-00 select? The first 0 after the dash is the standard control type (Type 1 -0), the second is Type 2 0 (no additional contact I/O) and the third is Type 3 0 (no open network).
  • How many ladder steps are available? The general specification states a maximum program capacity of 300 steps for the UT35A and UT32A, depending on parameters, commands used and control period.
  • Can I get Ethernet or PROFIBUS-DP? Yes, but through a different Type 3 code (2 for Ethernet, 4 for PROFIBUS-DP) so the order string would no longer be UT35A-000-10-00.
  • What do you need for an RFQ? Please send the full order string UT35A-000-10-00 and any option codes, the quantity and the project location in Oman or the GCC with your RFQ.

Documents and quotation

The manufacturer’s datasheet for the UT35A-000-10-00 is available on this page for download and lists the model and suffix codes, specifications and dimensions in full. To request a quotation, send the RFQ with the part number UT35A-000-10-00, the quantity, any option codes and the delivery destination in Oman or the GCC. Our team will confirm availability, lead time and commercial terms for the UT35A-000-10-00 by return.

Datasheets & Documents
  • PDF Datasheet Yokogawa UT35A-000-10-00 Single-Loop Digital Indicating Controller Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.

Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.

Yokogawa at a glance

Established 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki
Milestones Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986
Headquarters Tokyo, Japan
Product families Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers

Yokogawa products we list

Family Models Typical use
Pressure and DP transmitters EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable Pressure, level and DP flow measurement in process plants
Temperature transmitters YTA610, YTA710 RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus
Flowmeters ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 Water and conductive liquids, mass flow of hydrocarbons, steam and gas
Analysers TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen
Controllers and recorders UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 Single-loop control, furnace programs and data recording
Control and safety systems CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 Spares and expansions for CENTUM DCS, safety systems and STARDOM
Battery packs S9129FA, S9185FA, S9548FA Memory backup batteries for DCS and controller modules

The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.

Where Yokogawa products are used

In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.

Ordering Yokogawa products: what we need

Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.

Facts checked against Yokogawa's corporate history, October 2026.

FAQ

Questions about the Yokogawa UT35A-000-10-00 Single-Loop Digital

Answers from our engineering team on installation, compatibility and integration.

01Is the UT35A-000-10-00 a single-loop controller only?
Yes. According to the general specification its control mode is single-loop control with a 200 ms control period; cascade and other multi-loop modes belong to the UT55A.
02What does the -000 part of UT35A-000-10-00 select?
The first 0 after the dash is the standard control type (Type 1 -0), the second is Type 2 0 (no additional contact I/O) and the third is Type 3 0 (no open network).
03How many ladder steps are available?
The general specification states a maximum program capacity of 300 steps for the UT35A and UT32A, depending on parameters, commands used and control period.
04Can I get Ethernet or PROFIBUS-DP?
Yes, but through a different Type 3 code (2 for Ethernet, 4 for PROFIBUS-DP) so the order string would no longer be UT35A-000-10-00.
05What do you need for an RFQ?
Please send the full order string UT35A-000-10-00 and any option codes, the quantity and the project location in Oman or the GCC with your RFQ.