Brand:

Yokogawa UT55A-000-10-00 Digital Indicating Controller

Description

Yokogawa UT55A-000-10-00 overview

The Yokogawa UT55A-000-10-00 is a 96 x 96 mm panel-mounting digital indicating controller from the Yokogawa UTAdvanced range. The order code is read from the suffix tables in the manufacturer’s general specification: UT55A is the model, the first suffix block (-0) selects the standard single-output control type, the next two digits (0 and 0) select no additional function block and no open-network option, -1 selects an English guide display, 0 selects the white (light gray) case, and -00 is the fixed code for a standard code model.

The controller combines a large 14-segment color LCD, navigation keys, a built-in ladder sequence function and a rich set of PID control modes in a case only 65 mm deep behind the panel. Buyers search for the exact string Yokogawa UT55A-000-10-00 because replacement or like-for-like extension of an existing loop usually requires the same suffix code, and because the neighbouring codes (for example Type 2 and Type 3 variants) are not interchangeable in wiring.

This page describes the UT55A-000-10-00 as published in the manufacturer’s general specification GS 05P01C31, written in our own words for buyers who need to identify the exact part. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. We supply against the part number you provide and do not substitute without your written agreement.

Key features of the UT55A-000-10-00

  • 14-segment active color LCD with a five-digit PV display and a separate five-digit data display; the PV color can change with alarm state, and a guide display shows parameter names in English, German, French or Spanish.
  • Universal input for thermocouple, resistance temperature detector, DC voltage and DC current, with burnout handling selectable as upscale, downscale or off.
  • Eight control modes including single-loop, cascade, backup, PV switching, PV auto-selector and PV-hold control, with PID, ON/OFF, heating/cooling, sample PI, batch PID and feedforward control types available according to the mode.
  • Eight sets of target setpoints, alarm setpoints and PID parameters, plus auto-tuning, the Super overshoot-suppressing function and the Super 2 hunting-suppressing function.
  • Ladder sequence function as standard, with up to 500 program steps, for simple interlocks and sequencing without an external relay panel.
  • Retransmission output or a 15 V DC loop power supply, three contact inputs and three contact outputs are included in the basic configuration.
  • Front panel protection to IP66 and NEMA 4 (hose-down test only), except for side-by-side close mounting.

UT55A-000-10-00 technical specifications

Item Specification
Model UT55A, digital indicating controller, panel mounting
Order code UT55A-000-10-00 (Type 1 -0, Type 2 0, Type 3 0, language -1, case color 0, fixed code -00)
Case size 96 mm wide x 96 mm high x 65 mm deep from the panel surface
Panel cutout 92 mm x 92 mm (plus 0.8 mm / minus 0 tolerance)
Weight 0.5 kg or less
Display 5-digit 14-segment color LCD PV display, character height 21.5 mm
Universal input 1 point: thermocouple, RTD (3-wire), DC voltage, DC current
Typical accuracy Type K thermocouple: 0.1 percent of instrument range plus 1 digit for 0 degC or more; Pt100: 0.1 percent of range plus 1 digit
Control period 50 ms, 100 ms or 200 ms selectable
Alarms 8 alarm settings per loop; up to 18 alarm output points depending on model code
Contact I/O (basic) 3 contact inputs and 3 contact outputs
Relay contact rating 1c-contact 3 A at 250 V AC or 3 A at 30 V DC (resistance load)
Analog output 4 to 20 mA DC or 0 to 20 mA DC, load 600 ohm or less, accuracy 0.1 percent of span
Loop power supply 15 V DC, 14.5 to 18.0 V DC, about 21 mA maximum (shared with retransmission output)
Power supply 100 to 240 V AC (+10 percent / -15 percent), 50/60 Hz; 24 V AC/DC with option /DC
Power consumption 18 VA
Ambient temperature -10 to 50 degC (side-by-side mounting -10 to 40 degC)
Ambient humidity 20 to 90 percent RH, no condensation
Front protection IP66, NEMA 4 (hose-down test only)
Case material Polycarbonate resin, flame retardancy UL94 V-0
Communication (by Type 3 code) RS-485, Ethernet with gateway, CC-Link, PROFIBUS-DP or DeviceNet, each with Modbus master function where stated

The values above are taken from the manufacturer’s general specification for the UT55A and UT52A digital indicating controllers. Treat the document as the controlling reference and confirm every figure against the latest revision before final design, because the manufacturer may change specifications without notice.

Typical applications in oil and gas, utilities, water and manufacturing

Controllers of this class suit oil and gas package skids, gas-fired heaters and reboilers, glycol and amine units, desalination and water-treatment heating and dosing loops, packaging and food lines, laboratory furnaces and ovens, and pump-house or compressor utilities across Oman and the GCC. Small loops do not justify a DCS point, yet they must hold a setpoint, raise an alarm and share data with a PLC or SCADA system.

A buyer who already has the UT55A-000-10-00 installed usually wants the same suffix code again, which keeps panel cutouts, terminal layouts, spare stocks and documentation unchanged. That is the main reason this exact part number is searched for rather than a generic description.

Selection and compatibility notes for the UT55A-000-10-00

  • Type 1 selects the control type: -0 standard, -1 position proportional, -2 heating/cooling. This page covers -0.
  • Type 2 adds remote auxiliary analog inputs, extra contact inputs and outputs, and RS-485; Type 3 adds a network interface. The code 0 and 0 used here means no extension block and no open network.
  • Options such as /DR (additional direct input), /LP (24 V DC loop power supply), /HA (heater break alarm), /DC (24 V AC/DC power) and /MDL (DIN rail mounting without display and keys) change the order string and must be stated at enquiry.
  • The UT52A is the 48 x 96 mm sibling of this model; panel cutouts differ (92 x 92 mm against 45 x 92 mm), so confirm the existing cutout before ordering.

Terminal covers for the UT55A (model UTAP001) and the LL50A parameter setting software (sold separately) are listed in the same specification as separate order items.

Installation and commissioning

Mount the controller from the front of the panel using the supplied upper and lower brackets in a cutout of the size listed above, within the panel thickness range in the general specification. Keep the mounting angle within 30 degrees above horizontal with no downward tilt. Wire signals and power to the M3 screw terminals with square washers, keep sensor wiring away from power cables, and observe the allowable wiring resistance for RTD inputs. Allow a warm-up time of 30 minutes before judging accuracy, set the input type and range, configure alarms and the control mode, and run auto-tuning once the process is stable.

Before energising a UT55A-000-10-00 in a hazardous or critical service, confirm that the selected variant, enclosure rating and any approvals you require are covered by the order string and by your site rules.

Maintenance and spare parts

The controller has no moving parts and stores parameters in nonvolatile memory. Routine care means checking terminals for tightness, keeping the front panel and vents clean, verifying input accuracy against a calibrator at intervals set by your quality system, and exercising alarm and relay outputs. Keep a record of parameters, ladder programs and the order string so that a replacement unit can be configured quickly. Note that relay contacts have a finite life under heavy loads, so heavily switched outputs may be better driven through an external relay or solid-state device.

Related products and ordering notes

The UT55A-000-10-00 belongs to the UT55A and UT52A digital indicating controllers group. Related family members, modules, software and accessories are listed in the same general specification, and we can quote them together with the UT55A-000-10-00 when you need a complete panel or loop. Because many Yokogawa instruments are specified by long suffix strings, always quote the complete order code, the option codes, the quantity and the destination. If your installed unit is an older revision, send a nameplate photograph or the exact code printed on it so that compatibility can be checked before any quotation is issued.

Frequently asked questions about the UT55A-000-10-00

  • What does each part of the UT55A-000-10-00 code mean? UT55A is the model. Type 1 is -0 (standard type), Type 2 is 0 and Type 3 is 0 (no extension block, no open network), -1 is an English guide display, 0 is a white case and -00 is the fixed standard code.
  • Does the UT55A-000-10-00 have a ladder function? Yes. A ladder sequence function with up to 500 steps is included as standard according to the general specification; programming uses the separately sold LL50A parameter setting software.
  • What power supply does it need? The standard supply is 100 to 240 V AC at 50/60 Hz. A 24 V AC/DC supply is available only by adding option code /DC, so it is a different order string.
  • Can it be mounted on a DIN rail? Not in the form described here. The DIN rail version carries option code /MDL and omits the display and keys; it is described in a separate general specification.
  • What information should I send with an RFQ? Send the full order string UT55A-000-10-00 including any option codes, the quantity and the delivery location in Oman or the GCC so that we can confirm availability.

Documents and quotation

The manufacturer’s datasheet for the UT55A-000-10-00 is available on this page for download and lists the model and suffix codes, specifications and dimensions in full. To request a quotation, send the RFQ with the part number UT55A-000-10-00, the quantity, any option codes and the delivery destination in Oman or the GCC. Our team will confirm availability, lead time and commercial terms for the UT55A-000-10-00 by return.

Other Models in the UT55A And UT52A Digital Indicating Controllers Range

Seven Star LLC supplies models from the UT55A And UT52A Digital Indicating Controllers range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Yokogawa UT55A-000-10-00 Digital Indicating ControllerControllers & Data AcquisitionYou are viewing this model
Yokogawa UT52A-000-10-00 48 x 96 mm Digital Indicating ControllerControllers & Data AcquisitionView details
Datasheets & Documents
  • PDF Datasheet Yokogawa UT55A-000-10-00 Digital Indicating Controller Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.

Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.

Yokogawa at a glance

Established 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki
Milestones Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986
Headquarters Tokyo, Japan
Product families Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers

Yokogawa products we list

Family Models Typical use
Pressure and DP transmitters EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable Pressure, level and DP flow measurement in process plants
Temperature transmitters YTA610, YTA710 RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus
Flowmeters ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 Water and conductive liquids, mass flow of hydrocarbons, steam and gas
Analysers TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen
Controllers and recorders UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 Single-loop control, furnace programs and data recording
Control and safety systems CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 Spares and expansions for CENTUM DCS, safety systems and STARDOM
Battery packs S9129FA, S9185FA, S9548FA Memory backup batteries for DCS and controller modules

The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.

Where Yokogawa products are used

In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.

Ordering Yokogawa products: what we need

Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.

Facts checked against Yokogawa's corporate history, October 2026.

FAQ

Questions about the Yokogawa UT55A-000-10-00 Digital Indicating

Answers from our engineering team on installation, compatibility and integration.

01What does each part of the UT55A-000-10-00 code mean?
UT55A is the model. Type 1 is -0 (standard type), Type 2 is 0 and Type 3 is 0 (no extension block, no open network), -1 is an English guide display, 0 is a white case and -00 is the fixed standard code.
02Does the UT55A-000-10-00 have a ladder function?
Yes. A ladder sequence function with up to 500 steps is included as standard according to the general specification; programming uses the separately sold LL50A parameter setting software.
03What power supply does it need?
The standard supply is 100 to 240 V AC at 50/60 Hz. A 24 V AC/DC supply is available only by adding option code /DC, so it is a different order string.
04Can it be mounted on a DIN rail?
Not in the form described here. The DIN rail version carries option code /MDL and omits the display and keys; it is described in a separate general specification.
05What information should I send with an RFQ?
Send the full order string UT55A-000-10-00 including any option codes, the quantity and the delivery location in Oman or the GCC so that we can confirm availability.