Brand:

ABB S203-C100 S200 MCB 100 A Curve C, three pole

Description

S203-C100 100 A curve C three-pole breaker decoded

The ABB S203-C100 is a three-pole miniature circuit breaker with a 100 A rated current and C characteristic from the System pro M compact S200 family. The 80 A and 100 A ratings extend the range to higher currents while keeping the one-module-per-pole width of 17.5 mm. The ABB order code is 2CDS253001R0824 and the EAN is 4016779916288.

Reading the type name: S203 gives the pole count (3), C the tripping characteristic, and 100 the rated current in amperes. The C characteristic trips between 5 and 10 times In; this makes the S203-C100 well suited to general distribution, lighting and mixed motor-and-socket circuits.

S203-C100 technical specifications

Parameter Specification
Manufacturer / part number ABB / S203-C100
Order code 2CDS253001R0824
EAN 4016779916288
Series System pro M compact S200, 80 A to 100 A range
Poles 3
Tripping characteristic C
Rated current In 100 A
Standards IEC/EN 60898-1, IEC/EN 60947-2
Rated operational voltage Un (IEC/EN 60898-1) 400 V AC
Rated frequency 50/60 Hz
Rated short-circuit capacity Icn 6 kA
Icu / Ics (IEC/EN 60947-2) 6 kA / 6 kA
Rated insulation voltage Ui 440 V AC
Rated impulse withstand voltage Uimp 4 kV (1.2/50 µs)
Thermal release 1.13 × In non-tripping, 1.45 × In tripping within 2 h
Magnetic release 500 to 1000 A (5 to 10 × In)
Terminals Failsafe bi-directional cage clamp, up to 50 mm² solid, stranded and flexible, 3.0 Nm
Pole dimensions (H × D × W) 88.8 × 69 × 17.5 mm per pole
Weight (pack of 1: per piece) 0.384 kg
Ambient / storage temperature −25 to +55 °C / −40 to +70 °C
Endurance 10,000 electrical / 20,000 mechanical operations
Protection degree IP20, IP40 in an enclosure with cover
Mounting 35 mm DIN rail by fast clip, any position, any supply

How the S203-C100 trips

A bimetal element opens the contacts on sustained overload: up to 1.13 times In the breaker must hold for at least two hours, and at 1.45 times In it must open within two hours. A magnetic element covers short circuits and acts between 500 to 1000 A (5 to 10 × In) on AC without intentional delay.

The thermal element is calibrated for a 30 °C reference temperature (55 °C under IEC/EN 60947-2 reference conditions). In warmer cabinets the usable current drops by roughly 6 % for every 10 K of temperature rise, so a 100 A rating inside a hot enclosure behaves like a smaller breaker.

Derating the 100 A three-pole in a hot panel

Derating matters most at this rating. With the cabinet at 40 °C the allowable current falls by about 6 %, at 50 °C by about 12 %, and when several breakers sit side by side with load on all poles the grouping correction factor reduces the limit further. Spacing the breakers or using a ventilated enclosure helps. For the S203-C100, check the manufacturer derating table for the exact figures before finalising the cable and breaker size.

Where the S203-C100 fits and related parts

The S203-C100 works with the S2C accessory family: the auxiliary contact S2C-H6R, the signal and auxiliary contact S2C-S/H6R, the shunt trip S2C-A, the undervoltage release S2C-UA and the overvoltage release S2C-OVP. Alongside the breakers of the same range (S201, S202, S203 and S204, curves B and C, 80 A and 100 A) there are NA versions with a neutral pole. On the same rail you will often see S201-C80 or S203-C100 next to the S203-C100, depending on the pole count of each feeder.

S203-C100 and sibling order codes

Type Order code Packing unit Weight per piece
S201-C100 2CDS251001R0824 10 0.128 kg
S202-C100 2CDS252001R0824 5 0.256 kg
S203-B100 2CDS253001R0825 1 0.384 kg
S203-B80 2CDS253001R0805 1 0.384 kg
S203-C100 2CDS253001R0824 1 0.384 kg
S203-C80 2CDS253001R0804 1 0.384 kg

Selection checklist for the S203-C100

  • Rated current 100 A against load, cable cross-section (terminals take up to 50 mm²) and cabinet temperature
  • Curve C against the inrush of the connected load
  • 3 pole(s) against the system: three-phase three-wire feeders at 400 V
  • Prospective short-circuit current at the board, which must not exceed 6 kA
  • Accessories: auxiliary contact, trips, motor operating device

Installing the S203-C100

Snap the breaker on to a 35 mm DIN rail with the fast clip. Strip the conductor, insert it into the cage clamp with the screw loose, and tighten to 3.0 Nm with a Pozidriv 2 driver. The toggle is sealable and shows the contact position in red for ON and green for OFF. Supply can be fed from either side. After commissioning, retighten the terminals once the load has cycled, because large conductors at 80 A and 100 A can settle.

Using the S203-C100 in Oman and the GCC

For electrical rooms with high ambient temperature, the 55 °C rating and cyclic damp-heat test are useful. The S203-C100 100 A C breaker is used as a sub-distribution feeder in buildings, workshops, pump houses and utility rooms in oil and gas, power, desalination and petrochemical sites, wherever a compact 6 kA breaker at this rating is enough. Where the prospective fault level is higher, a step up to the S800 range should be considered.

Information to send with an RFQ for the S203-C100

  • Full type name S203-C100 and order code 2CDS253001R0824
  • Quantity and any accessories
  • System voltage and prospective short-circuit current
  • Load type and ambient temperature in the panel
  • Delivery location in Oman or the GCC

Storage, handling and spares for the ABB S203-C100

Keep ABB S203-C100 units in their original packaging until they are mounted. Store them indoors in a dry, dust-free room, away from direct sun and condensation. Panel shops in Oman and the GCC often hold stock in warehouses that get very hot in summer, so check that storage temperature stays within the limits given in the manufacturer datasheet.

  • Check the label and order code on every unit against the drawing before it goes into the panel.
  • Use the correct tool and tightening torque for the terminals, as given in the instructions supplied with the product.
  • Keep a small number of spare units for each rating used on site, so that a failed or damaged part can be replaced without waiting for a new shipment.
  • Record the order code in the panel documentation and the as-built drawings, so that maintenance teams can reorder the same part later.

When you plan spares for a project, group the ABB S203-C100 with the other parts of the same panel in one RFQ. This keeps delivery dates aligned and makes it easier to confirm stock for the whole bill of materials at once.

Documents and quotation

The official ABB data sheet for the System pro M compact S 200 80A-100A miniature circuit breakers (2CDC002180D0203, English) is attached on this page as a PDF and covers the ABB S203-C100 order number. It lists the 80 A and 100 A ratings in B and C characteristic, the rated breaking capacity to IEC/EN 60898-1 and IEC/EN 60947-2, the tripping curves, the terminal capacity, the dimensions and the compatible accessories. Check the rated current, the number of poles and the short-circuit level at your installation point before ordering, then send us the quantity and the delivery location for a quotation.

Seven Star LLC supplies ABB low-voltage protection in Oman and the GCC from Muscat.

Other Models in the Abb S200 80 100a C Range

Seven Star LLC supplies models from the Abb S200 80 100a C range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
ABB S201-C80 S200 MCB 80 A Curve C, single poleCircuit BreakersView details
ABB S201-C100 S200 MCB 100 A Curve C, single poleCircuit BreakersView details
ABB S203-C80 S200 MCB 80 A Curve C, three poleCircuit BreakersView details
ABB S203-C100 S200 MCB 100 A Curve C, three poleCircuit BreakersYou are viewing this model
ABB S204-C80 S200 MCB 80 A Curve C, four poleCircuit BreakersView details
ABB S204-C100 S200 MCB 100 A Curve C, four poleCircuit BreakersView details
Datasheets & Documents
  • PDF Datasheet ABB S 200 80A-100A Miniature Circuit Breaker Data Sheet 2CDC002180D0203 (PDF) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

FAQ

Questions about the ABB S203-C100 S200 MCB 100 A Curve C, three pole

Answers from our engineering team on installation, compatibility and integration.

01What is the ABB S203-C100?
It is a three-pole S200 miniature circuit breaker rated 100 A with C characteristic, approved to IEC/EN 60898-1 and IEC/EN 60947-2, with a breaking capacity of 6 kA.
02What is the magnetic trip range of the S203-C100?
The instantaneous release operates between 500 to 1000 A (5 to 10 x In) on AC; the thermal release holds 1.13 times In and trips at 1.45 times In.
03How wide is the S203-C100?
Each pole is 17.5 mm wide, so the S203-C100 occupies 52.5 mm of rail. Height is 88.8 mm and depth 69 mm.
04Which conductor size does the S203-C100 accept?
The failsafe bi-directional cage clamp accepts up to 50 mm2 solid, stranded or flexible conductors, tightened to 3.0 Nm with a Pozidriv 2 driver.
05Does ambient temperature affect the S203-C100?
Yes. The breaker is calibrated at 30 deg C and the allowable current falls by about 6 percent for each 10 K rise; it is rated for operation from minus 25 to plus 55 deg C.