Brand: JUMO
JUMO hydroTRANS S30 Duct Humidity and Temperature Transmitter
Description
Duct-mounted humidity and temperature transmitter for ventilation systems
The JUMO hydroTRANS S30 (type 907043) is the duct version of the hydroTRANS family. It is meant for mounting in weather-proofed ventilation ducts to monitor the outside air that enters a building or a production process. It reports relative humidity and temperature, with an optional CO2 module for demand-controlled ventilation.
Outputs are a configurable 4 to 20 mA / 0 to 10 V combination or RS485 Modbus RTU. A USB micro-B port is used for configuration through the setup program. The data sheet lists railway applications according to DIN EN 50155 among the areas of use, and extra code 950 applies for railway use (not with CO2).
The same multisensor design as the other hydroTRANS devices gives a typical accuracy of 2.0 % RH and 0.2 °C, with a maximum of 2.5 % RH and 0.4 °C after the 60-hour stabilization period, and a one-second sampling rate for humidity and temperature.
Technical specifications
| Parameter | Specification |
|---|---|
| Type | 907043; extension 11 (RH-T) or 12 (RH-T-CO2); duct version |
| Humidity / temperature | 0 to 100 % RH and -40 to +80 °C; with CO2 module 0 to 95 % RH and -10 to +60 °C; same accuracy class as the S20 series |
| CO2 (option) | 400 to 10000 ppm, +/-(50 ppm + 5 % of measured value) |
| Outputs | Analog 4 to 20 mA / 0 to 10 V (0.1 %); or RS485 Modbus RTU, 9600 to 115200 baud, address 1 to 254 |
| Supply | DC 24 V, SELV/PELV; max. 2.4 W; overvoltage category II; protection class III |
| Connection | Spring-cage terminals, 0.2 to 1.5 mm2; M16 x 1.5 cable fitting for 4.5 to 10 mm cable |
| Display (option) | Integrated TFT display, extra code 994 |
| Environment | -40 to +80 °C; with CO2 module -10 to +60 °C; with display -20 to +60 °C; storage -40 to +80 °C |
| Protection | Housing IP65 |
| Housing / weight | Polycarbonate; approx. 260 g |
| Stock versions | 907043/11-0-15-009/000; 907043/11-0-15-530/000; 907043/12-0-17-009/000; 907043/12-0-17-530/000 |
| Accessories | USB cable A to micro-B (00616250); plastic sinter filter 18 mm (00754581); plastic membrane filter 18 mm (30048149); setup program (00775170) |
Order code and filters
The order code is 907043/ extension (11 or 12) – version 0 – measuring range (15 or 17) – output (009 or 530) / extra codes. Extra codes are 062 DNV (not with CO2), 775 DAkkS calibration service, 950 railway application (not with CO2), 951 and 952 DAkkS calibration with fixed points, and 994 integrated display. The example in the data sheet is 907043/12-0-17-009/994.
Four stock versions with order codes are listed with part numbers, covering RH-T and RH-T-CO2 variants with analog or RS485 output. Choose the plastic sinter filter for dusty duct air and the membrane filter where droplets may reach the probe.
Calculated values are provided as well: dew point, frost point, wet-bulb temperature, absolute humidity, mixing ratio, partial water vapor pressure and specific enthalpy, which lets an air-handling controller work directly from enthalpy or dew point rather than relative humidity alone.
Four stock versions are listed in the data sheet, covering the analog and RS485 outputs with and without CO2, so a common duct application can usually be served without a special build. Ask us to confirm availability for the version you need.
Duct installation and typical uses
Mount it in the duct so that the measuring point sits in the moving air, away from heating coils and cold surfaces so the reading represents the mixed air. Typical places are fresh-air intakes, air-handling units, cleanrooms, greenhouse air ducts and storage ventilation.
Where CO2 is ordered, remember that the CO2 version limits temperature to -10 to +60 °C. A display raises the lower ambient limit to -20 °C, so choose the display only where the housing area stays within range. The data sheet also warns that the CO2 module is sensitive to vibration, which matters on fan-mounted ducts.
Electrical details to plan for: DC 24 V with a tolerance of -33 % to +33 %, a maximum 2.4 W, a limited-energy circuit per DIN EN IEC 61010-1:2020, and spring-cage terminals. On the RS485 version, set the device address between 1 and 254 and use the default 38400 baud unless the network needs another rate.
For projects that need documented performance, DAkkS calibration at 20, 50 and 80 percent RH at 23 degrees Celsius can be ordered with extra code 951, and extra code 952 covers two points at 33 and 73 percent RH. Specify the test points in plain text for the service calibration code 775. Spare filters are listed under accessories.
Filters protect the sensor: the data sheet lists an 18 mm plastic sinter filter (part 00754581) and an 18 mm plastic membrane filter (30048149). Choose the sinter filter for dusty air and the membrane type where moisture or splashes can reach the probe.
Mount the duct unit so the probe sits in the middle of the air stream, away from heating coils and humidifier nozzles that would disturb the reading. The housing is IP65, and the cable fitting M16 x 1.5 takes cables of 4.5 to 10 mm.
Documents and quotation
For engineering details, open the attached PDF (JUMO hydroTRANS S30 data sheet 907043 V5.00 (EN, 2026-06-01)). When you are ready to buy, submit the order code and project requirements through the request form, and our team will confirm what can be supplied and when. Browse the category Temperature Instrumentation for alternatives.
Datasheets & Documents
- Datasheet JUMO hydroTRANS S30 data sheet 907043 V5.00 (EN, 2026-06-01) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
JUMO is the German maker of temperature sensors, process controllers, pressure transmitters and liquid analysis instruments. Moritz Kurt Juchheim founded it in Fulda in 1948 as M. K. Juchheim KG, making glass thermometers with six employees. The name JUMO comes from the founder's name. It is still a family company headquartered in Fulda, and the parent company has been called JUMO GmbH & Co. KG since 2003.
Seven Star LLC is an independent supplier in Muscat. We list JUMO RTD and thermocouple probes, thermowells, transmitters, controllers, recorders and water analysis instruments, and supply them to process plants, OEMs, HVAC contractors and water utilities in Oman and the GCC by type number.
JUMO company profile
| Established | 1948, Fulda, Germany, by Moritz Kurt Juchheim |
|---|---|
| First products | Glass and contact thermometers; platinum glass sensors from 1966 |
| Ownership | Family-owned; renamed JUMO GmbH & Co. KG in 2003 |
| Product families | RTD and thermocouple probes, thermowells, temperature and pressure transmitters, controllers and thermostats, safety temperature limiters, paperless recorders, liquid analysis and flow and level instruments |
Milestones
- 1948: Moritz Kurt Juchheim founds M. K. Juchheim KG in Fulda, making glass thermometers with six employees.
- 1966: Platinum glass temperature sensors are added.
- 2003: The parent company is renamed JUMO GmbH & Co. KG.
JUMO products we list
| Family | Models | Typical use |
|---|---|---|
| RTD and thermocouple probes | 902020, 902030, 902050, 902120, 902006 2xPt100, PROCESStemp, mineral-insulated RTD, 901020 thermocouple, 901210, 902810 hygienic, 902550 surface, 902520 HVAC, MarineTemp | Temperature measurement in pipes, vessels, machines, HVAC and food plants |
| Thermowells and inserts | 909710 thermowells, 909740 measuring inserts | Protecting sensors and replacing them without opening the process |
| Temperature transmitters | dTRANS T01, T03, T04, T05, T06 SIL, T07 HART, T09, T1000 IO-Link, DELOS T switch | Converting sensor signals to 4-20 mA, HART or IO-Link |
| Pressure and level | dTRANS p20, p30, p31 hygienic, p33 Ex, p02 DELTA, MIDAS S05, MIDAS DP10, DELOS S02, MAERA S25, NESOS R20 | Pressure in process, hydraulic and OEM systems; tank and well level |
| Controllers, limiters and recorders | DICON touch, IMAGO 500, dTRON 316, iTRON, cTRON, diraTRON 104, eTRON T, safetyM STB/STW, safetyM TB/TW, LOGOSCREEN 601, mTRON T | Furnace, oven and process control, over-temperature protection and recording |
| Liquid analysis and flow | AQUIS touch S, AQUIS touch P, AQUIS 500 pH, AQUIS 500 CR, dTRANS pH 02, pH electrode, digiLine DO, ecoLine NTU, flowTRANS MAG H20, flowTRANS US W01 | pH, conductivity, oxygen and turbidity in water treatment; liquid flow |
Choosing a temperature sensor starts with the range and accuracy. A Pt100 RTD is accurate and stable from about -200 to 600 °C and is the usual choice in process plants. A thermocouple (type K or J, for example) covers much higher temperatures and responds faster but is less accurate. The wiring also matters: a 3-wire or 4-wire Pt100 connection cancels the resistance of the cable, while a 2-wire connection adds an error that grows with cable length. That is why a head-mounted transmitter is often fitted close to the sensor.
Where JUMO products are used
In Oman and the GCC, JUMO sensors and controllers are used in oil and gas and chemical plants, food and beverage production, plastics and metal heat treatment, HVAC and district cooling, water and wastewater treatment, swimming pools and marine applications.
Ordering JUMO products: what we need
Send the JUMO type number and the full order code from the label (for example 902020/10-...). For probes, add the sensor type (Pt100, Pt1000, type K or J), the number of wires, the insertion length and diameter, and the process connection. For controllers, add the input, outputs and supply voltage.
Facts checked against JUMO's company history, October 2026.
Browse JUMO products by category: Temperature Instrumentation, Pressure Instrumentation, Liquid Analysis Sensors, Controllers & Data Acquisition, Level Transmitter.
Related products
Frequently Asked Questions
Yes. The S30 is for weather-proofed ventilation ducts; the S20 is the wall version.
4 to 20 mA / 0 to 10 V combination output or RS485 Modbus RTU.
Yes, as RH-T-CO2 versions (basic type extension 12).
Yes, DAkkS calibration options are listed as extra codes 775, 951 and 952.
Approximately 260 g.

Reviews
There are no reviews yet.