Schneider Electric CCT15369 Acti9 IC2000 Outdoor Twilight Switch

Description

CCT15369 Acti9 IC2000 outdoor twilight switch, 2 to 2000 lux

The CCT15369 is the outdoor version of the Schneider Electric Acti9 IC2000 twilight switch. The DIN-rail module is 18 mm wide with a normally-open dry contact, and the provided sensor is an outdoor twilight sensor rated IP55. Brightness threshold is adjustable across 2–2000 lux. Seven Star LLC supplies the CCT15369 in Oman and the GCC as an independent supplier based in Muscat.

It is the natural pairing for street, facade and car-park lighting because the sensor can be placed outside while the module sits in the board. The weight difference to the indoor CCT15285 (111 g against 87.5 g) reflects the heavier sensor housing.

CCT15369 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / CCT15369
Range / product name Acti9
Product type Twilight switch
Short name IC2000
Provided equipment twilight sensor outdoor
Light intensity adjustment 2–2000 lux
Channels 1
Control type By brightness detection
Rated operational voltage 230 V AC +10 % -15 % at 50/60 Hz
Maximum switching current 10 A – 250 V AC pf = 0.6; 16 A – 250 V AC pf = 1
Minimum switching current 10 mA 230 V AC; 100 mA 24 V AC/DC
Contacts 1 NO
Time delay 20 s on; 80 s off
Standby power 0.5 W stand by
Mounting TH35 DIN rail conforming to EN 60715
Terminals 1 × 2.5 mm² screw terminals solid or flexible with sleeve; 2 × 0.5–2.5 mm² screw terminals solid or flexible
Dimensions 85.5 mm x 18 mm x 67 mm (H x W x D)
Net weight 111 g
Insulation class Class II
Overvoltage category Class 3
Standard EN 60669-2-1
Operating temperature -30–55 °C
Storage / transport temperature -30–70 °C
Relative humidity 90 %, non-condensing
Protection IP20; IP55 (sensor)
Warranty 18 months

How the CCT15369 switches

The module switches by brightness detection with a delay of 20 s on and 80 s off, which filters out short light changes. Contact rating is 10 A – 250 V AC pf = 0.6 and 16 A – 250 V AC pf = 1; the minimum is 10 mA 230 V AC and 100 mA 24 V AC/DC. Insulation class is Class II and overvoltage category Class 3.

Operating range of the module is -30–55 °C. The datasheet gives IP20 for the module and IP55 for the sensor, so the sensor can be mounted outside but the module cannot.

CCT15369 against the other twilight products in this range

Datasheet comparison of the twilight modules and the separate cell:

Part number Type Sensor / equipment Contact Lux range Weight
CCT15285 Twilight switch twilight sensor indoor 1 NO 2–2000 lux 87.5 g
CCT15369 (this page) Twilight switch twilight sensor outdoor 1 NO 2–2000 lux 111 g
CCT15483 Programmable twilight switch with time switch function twilight sensor outdoor C/O 2–2000 lux 150 g
CCT15263 Wall mounted cell n/a n/a 2–2000 lux 40.5 g

Setting the threshold on the CCT15369

The threshold is a dial between 2 and 2000 lux. Set it at dusk with the real lamps off: turn the dial until the output just switches at the brightness at which you want the lights on, then confirm the time delay stops flicker. Always keep the sensor out of the light of the lamps it controls.

The delay of tens of seconds is a feature, not a fault: after the dial setting the output will change a short moment later.

Loads and ratings for the CCT15369

Lamp-load limits from the datasheet:

  • incandescent lamp: 2600 W
  • halogen lamp: 2600 W
  • non-corrected fluorescent tube: 2300 VA
  • serial-compensated fluorescent tube: 2300 VA
  • parallel compensated fluorescent lamp: 730 VA (80 µF)
  • compact fluorescent lamp: 170 W
  • < 2 W LED lamp: 30 W
  • ≥ 2 W LED lamp: 200 W

For heavier or inductive loads, drive a contactor and let the twilight module switch only its coil.

Selection checklist for the CCT15369

  • Where is the light measured: indoors, outdoors, or at a remote wall position?
  • Is brightness alone enough, or is a time schedule also needed?
  • Does the supply and load match the module rating on the datasheet?
  • Is the cable length enough between sensor and module?
  • Does the mounting position avoid direct light from the controlled lamps?

Reading the lux scale: a low threshold makes the output respond only in near darkness, while a setting toward the 2000 lux end responds in bright daylight. Pick the threshold from the brightness at which lights are really needed on site, not from the datasheet range alone.

Installation and commissioning of the CCT15369

Install this unit according to its role: clip the module onto the rail, mount the outdoor sensor where it sees open sky and wire its sensor terminals.

Test on site at dusk, check that the output is stable through the delay, and record the final dial position in the board schedule so that a replacement can be set the same way.

If the lights flicker around dusk, the usual causes are a sensor that sees its own lamp, a threshold set too close to the switching brightness or a contaminated sensor window. Move or shield the sensor first, then adjust the dial, and only then look at the module.

Where the CCT15369 fits in Oman and the GCC

Twilight control suits external lighting for compounds, roads, car parks and facades, and daylight-linked lighting in atria and corridors. Strong sun, dust and sand on a sensor window and high board temperatures are the main local issues: place sensors where they can be cleaned, shade boards and compare the datasheet limits with real conditions.

Lighting circuits in the region often share one supply with signage and security equipment, so record in the board which outputs follow the twilight signal and which do not. A written setting for the dial, the lux threshold chosen and the date of commissioning saves time at the next maintenance visit.

Documents and quotation

The official Schneider Electric datasheet of this unit is attached on this page for download, so every figure above can be checked against the source.

To request a quotation, send us the part number CCT15369, the quantity and the delivery location through the RFQ form. Seven Star LLC replies with availability and lead time.

Other Models in the Se Ic Twilight Range

Seven Star LLC supplies models from the Se Ic Twilight range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric CCT15263 Acti9 Outdoor Light Sensor CellAutomation AccessoriesView details
Schneider Electric CCT15285 Acti9 IC2000 Indoor Twilight SwitchAutomation AccessoriesView details
Schneider Electric CCT15369 Acti9 IC2000 Outdoor Twilight SwitchAutomation AccessoriesYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric CCT15369 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric CCT15369 Acti9 IC2000 Outdoor

Answers from our engineering team on installation, compatibility and integration.

01What is the CCT15369?
A Schneider Electric Acti9 twilight switch supplied with a twilight sensor outdoor. Brightness adjustment is 2…2000 lux.
02What contact does the CCT15369 have?
The datasheet lists 1 NO with 10 A - 250 V AC pf = 0.6; 16 A - 250 V AC pf = 1.
03What supply does the CCT15369 use?
230 V AC +10 % -15 % at 50/60 Hz; standby consumption 0.5 W stand by.
04Does the CCT15369 have a switching delay?
Yes. The datasheet gives 20 s on; 80 s off, which avoids rapid toggling when brightness changes briefly.
05What operating temperature applies to the CCT15369?
-30…55 °C in operation and -30…70 °C in storage and transport.