Brand: Schneider Electric
Schneider Electric A9N26948 Acti9 MX + OF shunt trip release
Description
A9N26948: Acti9 MX + OF shunt trip release with a changeover (C/O) contact, 12–24 V
The A9N26948 is a Schneider Electric Acti9 MX + OF shunt trip release with a changeover (C/O) contact, an 18 mm side-mounted module that trips a compatible Acti9 breaker remotely when its coil is energised. Its control voltage is 12–24 V AC 50/60 Hz and 12–24 V DC. Seven Star LLC supplies the A9N26948 in Oman and the GCC as an independent supplier based in Muscat.
This unit is an accessory, not a breaker: it only works when mounted on a compatible Acti9 device, and it makes remote opening possible for emergency stop circuits, fire-alarm shutdown, process interlocks and monitored feeders. The OF part of the name is an additional C/O signalling contact, so the same module both trips the breaker and reports its state.
Technical specifications of the A9N26948
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / A9N26948 |
| Range / product | Acti9 MX + OF |
| Type | Shunt trip release with OC contact |
| Control circuit voltage [Uc] | 12–24 V AC 50/60 Hz and 12–24 V DC |
| Signal contacts | 1 C/O |
| Mounting | Fixed, 35 mm symmetrical DIN rail |
| Width | 18 mm (2 modules of 9 mm) |
| Dimensions (H × W × D) | 82.5 × 18 × 73.5 mm |
| Net weight | 65 g |
| Colour | White |
| Local signalling | Action indicator |
| Comb busbar compatibility | Top: yes |
| Terminals | Clamp terminal – 1 cable(s) 2.5 mm² – flexible |
| Stripping length / torque | 9 mm / 1 N.m |
| Standard | EN/IEC 60947-2 |
| Tropicalisation | Class 2 |
| Humidity | 95 % at 55 °C |
| Operating temperature | -25–50 °C |
| Storage temperature | -40–85 °C |
| Approvals listed | ASTA LCIE KEMA ASEFA |
Breaker compatibility of the A9N26948
The datasheet lists these Acti9 ranges as compatible: iDPN, C120, C40, C60H-DC, C60NA-DC, C60PV-DC, DPN Vigi, DT40, DT60, ID C40, IDc, ITG40, ID, DPN. The C120 range is among them, which includes the A9N18346 and similar C120 breakers, but always check the exact breaker reference and its mounting side before you order. The module is fixed-mounted, takes the comb busbar at the top and mounts on the side of the breaker so that the pair occupies the breaker width plus 18 mm of rail.
Compatibility lists in a datasheet name the breaker families, not every pole count or rating, so confirm with the breaker datasheet that the shunt trip can be added on the chosen frame.
MX references to compare with the A9N26948
Related references in the same accessory family:
| Part number | Version | Control voltage | Signal contact |
|---|---|---|---|
| A9N26476 | MX | 110–415 V AC 50/60 Hz and 110–130 V DC | No contact |
| A9N26946 | MX + OF | 110–415 V AC 50/60 Hz and 110–130 V DC | 1 C/O |
Wiring, testing and maintenance of the A9N26948
Connect the control wires to the bottom terminals: the datasheet lists one 2.5 mm² flexible conductor, with 9 mm stripping and 1 N.m torque. Make sure the supply type matches the coil: an AC coil must not be driven from a DC rail, and the polarity convention of DC control circuits should be checked against the wiring diagram supplied with the product.
After commissioning, test the trip by applying the control voltage once and confirming that the breaker opens and the indicator shows; repeat at each annual maintenance round. Check also that the C/O contact changes state and the PLC or alarm reads it. A shunt trip that never operates gives no feedback until it is needed, so a periodic test is the only way to know it works. Keep the coil circuit fuse or breaker rated per the manufacturer’s data.
Selection checklist and RFQ details for the A9N26948
Check these before ordering.
- Control voltage: 12–24 V AC 50/60 Hz and 12–24 V DC must match the signal supply.
- Auxiliary contact: required, with 1 C/O.
- Breaker: the exact reference must be listed as compatible.
- Mounting: one 18 mm slot to the side of the breaker.
- Signal source: relay, PLC output, push button or fire panel.
With your enquiry, send:
- Part number A9N26948 and quantity.
- The breaker reference it will be fitted to.
- Control supply type and voltage.
- Delivery location and date.
Where the A9N26948 is used in Oman and the GCC
Shunt trips are used in emergency stop and fire-alarm shutdown schemes of buildings and industrial plants, for remote isolation of feeders to pumps and chillers, and for load shedding on generator-backed boards. The OF version is also useful where a BMS or SCADA needs to know that the feeder was tripped by command and not by a fault. The temperature range of -25–50 °C suits indoor panels; on rooftop or plant-room boards in the Gulf the heat near the top of an enclosure can exceed that range, so mount the module away from heat sources.
What the A9N26948 does inside a breaker assembly
A shunt trip is a coil that sits beside a circuit breaker and, when energised by a command signal, releases the breaker mechanism. It does not protect the circuit by itself and it does not close the breaker again; the breaker handle must be reset manually afterwards. For this unit the coil is specified for 12–24 V AC 50/60 Hz and 12–24 V DC, so it follows the supply of the control circuit that triggers it. Because the control voltage is only 12–24 V, the trip can come directly from low-voltage PLC outputs, battery systems or SELV supplies without an interposing relay.
The C/O contact changes state when the module trips, so it can be wired to an alarm or a PLC input; the datasheet gives no contact rating for this low-voltage version, so use it only on low-energy signal circuits and confirm the rating with the manufacturer.
Documents and quotation
The manufacturer’s product datasheet for the A9N26948 is attached on this page for reference; it is the document to use when you verify ratings, dimensions and approvals against your own design. It lists the control voltage and compatibility for this exact reference.
To receive a quotation, send the part number A9N26948 with quantity and delivery location in Oman or the GCC. Seven Star LLC replies with availability and lead time as an independent supplier based in Muscat.
Other Models in the Schneider Mx Range
Seven Star LLC supplies models from the Schneider Mx range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric A9N26476 Acti9 MX shunt trip release | Automation Accessories | View details |
| Schneider Electric A9N26946 Acti9 MX + OF shunt trip release | Automation Accessories | View details |
| Schneider Electric A9N26948 Acti9 MX + OF shunt trip release | Automation Accessories | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric A9N26948 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric A9N26948 Acti9 MX + OF shunt
Answers from our engineering team on installation, compatibility and integration.
01What does the A9N26948 do?
It is a shunt trip release: when its coil is energised with 12-24 V AC 50/60 Hz and 12-24 V DC it opens a compatible Acti9 breaker remotely. The breaker must be reset by hand.
02What control voltage does the A9N26948 need?
The datasheet lists 12-24 V AC 50/60 Hz and 12-24 V DC control circuit voltage for this reference.
03Does the A9N26948 have an auxiliary contact?
Yes, it has one C/O signalling contact. Check that this arrangement matches your control circuit before ordering.
04Which breakers can the A9N26948 be fitted to?
The datasheet lists Acti9 iDPN, C120, C40, C60H-DC, C60NA-DC, C60PV-DC, DPN Vigi, DT40, DT60, ID C40, IDc, ITG40 and ID ranges. Confirm the exact breaker reference.
05How wide is the A9N26948?
It is 18 mm wide (2 modules of 9 mm), 82.5 mm high and 73.5 mm deep, mounted on a 35 mm DIN rail.