Schneider Electric A9N18346 C120N 2P 100 A B-Curve MCB

Description

A9N18346: C120N 2P 100 A B-curve Acti9 circuit breaker

The A9N18346 is a Schneider Electric Acti9 C120 miniature circuit-breaker in the C120N performance class: two-pole, 100 A, with B curve. It is a thermal-magnetic device on a 35 mm DIN rail, 54 mm wide, and the datasheet marks it suitable for isolation. Seven Star LLC supplies the A9N18346 in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference from the product title: C120N names the breaking-capacity version (standard within the C120 family), 2P the number of protected poles, 100 A the rated current at 30 °C and B the trip curve. The C120 is the large-frame member of the Acti9 modular range, used where a 63 A to 125 A feeder is needed in a modular panel rather than a moulded-case device. A9N18346 follows that pattern.

Technical specifications of the A9N18346

Parameter Specification
Manufacturer / part number Schneider Electric / A9N18346
Range / product Acti9 C120 (device short name C120N)
Type Miniature circuit-breaker, thermal-magnetic, distribution application
Poles 2P, 2 protected pole(s)
Rated current [In] 100 A at 30 °C
Curve / magnetic trip B curve, 3–5 × In
Network type AC and DC
Rated operational voltage / test voltages 400 V AC 50/60 Hz; 440 V AC 50/60 Hz; ≤ 250 V DC; 220–240 V AC 50/60 Hz; 380–415 V AC 50/60 Hz
Rated insulation voltage / impulse 500 V AC / 6 kV
Isolation Suitable for isolation (IEC 60947-2)
Limitation class 3
Mechanical / electrical endurance 20000 cycles / 5000 cycles
Dimensions (H × W × D) 81 × 54 × 73 mm (6 modules of 9 mm)
Net weight 0.41 kg
Terminals Tunnel type; 1–50 mm² rigid, 1.5–35 mm² flexible
Stripping length / torque 15 mm / 3.5 N.m
Earth-leakage protection Separate block
Locking Handle sealable in OFF or ON position
Ingress protection IP20 (IEC 60529)
Pollution degree / overvoltage category 3 / IV
Tropicalisation Class 2 (IEC 60068-1)
Operating temperature -25–70 °C
Storage temperature -40–85 °C
Humidity / altitude 95 % at 55 °C / 2000 m
Standards EN/IEC 60898-1, EN/IEC 60947-2
Certification listed EAC

Installation, torque and routine checks

Strip 15 mm of insulation, fit the conductor into the tunnel terminal and tighten to 3.5 N.m; under-torqued terminals on a 100 A circuit are a common source of hot spots. The handle can be sealed in either position to deter tampering, but the datasheet does not list a padlock accessory for this reference, so use a panel-door lock where lockout is required. Clip the unit onto the 35 mm rail and fit it so the ON/OFF indication is visible.

After energising, run a thermographic scan under load during the first season, then include the breaker in the yearly panel inspection: re-torque, clean dust, and operate the handle to keep the mechanism free. Electrical endurance is listed as 5000 cycles, so a 100 A device on a frequently switched circuit may reach this sooner than a feeder that rarely operates.

Related C120 references to compare with the A9N18346

These neighbouring references appear in the same Schneider Electric range; the table compares the points that most often change a selection.

Part number Class Poles Rating Curve Width
A9N18362 C120N 2P 100 A C 54 mm
A9N18361 C120N 2P 80 A C 54 mm
A9N18363 C120N 2P 125 A C 54 mm
A9N18358 C120N 1P 100 A C 27 mm
A9N18367 C120N 3P 100 A C 81 mm
A9N18357 C120N 1P 80 A C 27 mm

Moving between the N and H class changes breaking capacity, and moving between pole counts changes width and DC voltage capability; rating and curve only change the thermal and magnetic settings.

Breaking capacity of the A9N18346 on AC and DC

The C120N version quotes the following breaking values in the datasheet. Icn is the household-and-similar capacity (EN/IEC 60898-1) and Icu the ultimate capacity (EN/IEC 60947-2).

Network voltage Type Rating Standard
400 V AC 50/60 Hz Icn 10000 A EN/IEC 60898-1
440 V AC 50/60 Hz Icu 6 kA EN/IEC 60947-2
≤ 250 V DC Icu 10 kA EN/IEC 60947-2
220–240 V AC 50/60 Hz Icu 20 kA EN/IEC 60947-2
380–415 V AC 50/60 Hz Icu 10 kA EN/IEC 60947-2

The N version gives 20 kA at 220–240 V AC and 10 kA at 380–415 V AC for the multi-pole types listed here, adequate for most building and utility distribution but not for boards next to a large transformer. On DC, two poles are quoted at up to 250 V DC; for a higher DC voltage confirm the pole wiring arrangement against the manufacturer’s DC diagrams, and a polarity check should be part of commissioning.

Frame size and pole layout of the A9N18346

A two-pole C120 occupies 6 modules of 9 mm, which is 54 mm of rail and 0.41 kg of mass. Neutral position is listed as left. The earth-leakage option is a separate add-on block, and the breaker is compatible with comb busbars and distribution blocks. Two poles suit single-phase feeders with a switched neutral, or DC circuits where both polarities must be interrupted.

Because a C120 is deeper and wider than the small iC60 range, count the busbar and enclosure space early. Dimensions of 81 × 54 × 73 mm are listed, which fits standard modular enclosures with a 35 mm rail.

Selection checklist and RFQ details for the A9N18346

Use these points before you confirm the part number.

  • Pole count: 2P must match phases, neutral and any DC polarity to be interrupted.
  • Rating and curve: 100 A, B curve, with enclosure derating applied.
  • Fault level at the board against the Icu table above (C120N class).
  • Space: 54 mm of rail, and whether an add-on block (shunt trip, auxiliary, earth-leakage) must be fitted alongside.
  • Conductor: the terminals accept 1–50 mm² rigid or 1.5–35 mm² flexible.
  • Discrimination with upstream and downstream devices, using the manufacturer’s tables.

When you send the enquiry, include:

  • Part number A9N18346 and required quantity.
  • Board fault level and supply voltage, AC or DC.
  • Required add-on blocks, such as shunt trip or earth-leakage.
  • Delivery location and required date.
  • The project specification if a certificate or test report is requested.

Trip curve and rating logic

The thermal element protects the cable against sustained overload; the magnetic element releases on short circuit. For A9N18346 the datasheet gives 3–5 × In as the magnetic tripping limit with a B characteristic. A B-curve release in this size is uncommon, so confirm that your upstream device and fault-level study actually call for it, rather than the C curve used for most distribution feeders.

The 100 A figure is defined at 30 °C. Panels in Oman often run well above that, so apply the manufacturer’s derating tables for the real enclosure temperature and for adjacent hot devices; a 100 A rating sits mid-range in the C120 family and is common for sub-main feeders to a distribution board.

Where the A9N18346 is used in Oman and the GCC

Typical homes for a two-pole 100 A B-curve device are main and sub-main feeders in commercial buildings, workshop and utility boards, pump-house and desalination distribution panels, and camp or accommodation supplies in oil and gas. The listed operating range of -25–70 °C and 95 % humidity at 55 °C cover the heat and condensation of the Gulf coast, but ventilation of the enclosure and sand-proof gland plates remain the installer’s job. For DC auxiliary and battery circuits the C120N 2P breaker can also be applied within the voltage limit stated above.

Documents and quotation

The manufacturer’s product datasheet for the A9N18346 is attached on this page for reference; it is the document to use when you verify ratings, dimensions and approvals against your own design. It lists the rated values for this exact reference.

To receive a quotation, send the part number A9N18346 with quantity and delivery location in Oman or the GCC. Seven Star LLC replies with availability and lead time as an independent supplier based in Muscat.

Datasheets & Documents
  • PDF Datasheet Schneider Electric A9N18346 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9N18346 C120N 2P 100 A B-Curve

Answers from our engineering team on installation, compatibility and integration.

01What does the A9N18346 protect against?
The A9N18346 is a thermal-magnetic breaker: the thermal element handles sustained overload and the magnetic element releases on short circuit. The B curve has a magnetic tripping limit of 3-5 x In.
02What breaking capacity does the A9N18346 have?
As a C120N unit it is listed at 20 kA Icu at 220-240 V AC and 10 kA Icu at 380-415 V AC to EN/IEC 60947-2. The table on this page shows every voltage and standard in the datasheet.
03Can the A9N18346 be used on DC circuits?
The datasheet lists network type AC and DC and quotes DC breaking capacity up to 250 V DC for 2P configuration. Check polarity and series wiring against the manufacturer's DC diagrams.
04How wide is the A9N18346 and what rail does it need?
It is 54 mm wide (6 modules of 9 mm), 81 mm high and 73 mm deep, and clips onto a 35 mm DIN rail.
05What terminals and torque apply to the A9N18346?
Tunnel terminals accept 1-50 mm2 rigid or 1.5-35 mm2 flexible conductors, with 15 mm stripping length and 3.5 N.m tightening torque.