Schneider Electric C40H32D400 ComPacT NSX400H 3P ML 2.3 400A

Description

C40H32D400: ComPacT NSX400H 3P breaker with MicroLogic 2.3

The C40H32D400 is a ComPacT NSX400H three-pole (3D, all three poles protected) circuit breaker, fixed mounting, rated 400 A, supplied complete with a MicroLogic 2.3 trip unit. The datasheet gives the H 70 kA 415 V AC breaking code and a rated operational voltage of 690 V AC 50/60 Hz. Seven Star LLC supplies the C40H32D400 in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference: across the references in this group the datasheet titles show that the leading characters follow the frame size, the letter H matches the H performance level (70 kA at 415 V AC), and the trip unit and rating are named in the title as MicroLogic 2.3 at 400 A. The datasheets do not publish a full decoding table, so confirm any other option with the ordering documents.

Site conditions and use of the C40H32D400 in Oman and the GCC

Distribution feeders: the datasheet lists the application as distribution, which suits incomers and outgoing feeders in low-voltage boards.

The datasheet lists -25 to 70 °C for operation, relative humidity of 0 to 95 %, protection IP40 conforming to IEC 60529 and IK07 conforming to IEC 62262, pollution degree 3 conforming to IEC 60664-1, and altitude 0 to 2000 m without derating, 2000 m to 5000 m with derating. In Oman the practical limits are the temperature inside the switchboard in summer and the dust and salt-laden humidity on the coast.

Typical places are substations, desalination and water plants, oil and gas facilities, and industrial or commercial buildings. A panel builder should check derating at the board temperature, not only the datasheet rating at the reference temperature.

Trip unit and settings of the C40H32D400

The trip unit is the MicroLogic 2.3, an electronic unit whose datasheet protection code is LSoI: long-time overload protection, short-time protection with a fixed delay, and instantaneous protection. The long-time pick-up Ir has nine settings between 160 to 400 A. The delay is fixed and is listed as 400 s at 1.5 x Ir; 16 s at 6 x Ir; 11 s at 7.2 x Ir.

Short-time pick-up Isd is adjustable in nine steps over 1.5 to 10 x Ir with a fixed delay. The instantaneous threshold is fixed at 4800 A, so it does not move when Ir is changed. Thermal memory is 20 minutes before and after tripping before and after tripping, which matters on feeders that restart soon after a trip.

The trip unit is part of this reference, so no separate trip unit order is needed.

C40H32D400 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / C40H32D400
Range / device ComPacT / NSX400H
Application Distribution
Poles / protected poles 3P / 3D
Rated current [In] 400 A at 40 °C
Rated operational voltage [Ue] 690 V AC 50/60 Hz
Insulation / impulse [Ui / Uimp] 800 V AC 50/60 Hz / 8 kV
Isolation suitability Yes conforming to EN/IEC 60947-2
Utilisation category Category A
Breaking capacity code H 70 kA 415 V AC
Ultimate breaking capacity [Icu] 100 kA at 220/240 V AC; 70 kA at 380/415 V AC; 65 kA at 440 V AC; 50 kA at 500 V AC; 35 kA at 525 V AC; 20 kA at 660/690 V AC; 85 kA at 240 V AC conforming to UL 60947-4-1; 65 kA at 480 V AC conforming to UL 60947-4-1; 20 kA at 600 V AC conforming to UL 60947-4-1
Service breaking capacity [Ics] 100 kA at 220/240 V AC; 70 kA at 380/415 V AC; 65 kA at 440 V AC; 50 kA at 500 V AC; 11 kA at 525 V AC; 10 kA at 660/690 V AC
Trip unit MicroLogic 2.3, electronic, functions LSoI
Long-time pick-up [Ir] 160 to 400 A
Long-time delay [tr] 400 s at 1.5 x Ir; 16 s at 6 x Ir; 11 s at 7.2 x Ir
Short-time pick-up [Isd] 1.5 to 10 x Ir
Instantaneous pick-up [Ii] 4800 A
Earth-leakage / ZSI Without / Without
Mechanical durability 15000 cycles
Electrical durability 12000 cycles at 440 V In/2; 6000 cycles at 440 V In; 6000 cycles at 690 V In/2; 3000 cycles at 690 V In
Power dissipation per pole 19.2 W
Mounting / connections Fixed, Backplate; Front top, Front bottom; pitch 45 mm
Dimensions W x H x D 140 mm x 255 mm x 110 mm
Net weight 6.05 kg
Standards EN/IEC 60947-2
Protection degree IP40 conforming to IEC 60529; IK07 conforming to IEC 62262
Operating temperature -25 to 70 °C

Breaking capacity of the C40H32D400 at the voltages that matter

The breaking capacity code on the datasheet reads H 70 kA 415 V AC. The H code carries 70 kA Icu at 380/415 V AC, the highest figure in this group of datasheets. At 660/690 V AC the Icu is 20 kA, and the service capacity Ics at 380/415 V AC is 70 kA.

Insulation voltage is 800 V AC 50/60 Hz and the impulse withstand is 8 kV.

ComPacT NSX400 and NSX630 references around the C40H32D400

The table lists the references of the same frame size covered by this set of datasheets, so you can see where the C40H32D400 sits among the frames, pole counts and trip units. Similar references differ in frame performance level, pole count or trip unit, not in appearance alone.

Part number Frame Poles Trip unit Rating Icu at 380/415 V
C4036E400 Trip unit 3P MicroLogic 6.3 E 400 A –
C40F3 NSX400F 3P none (basic frame) 400 A 36 kA
C40F31M320 NSX400F 3P MicroLogic 1.3 M 320 A 36 kA
C40F32D400 NSX400F 3P MicroLogic 2.3 400 A 36 kA
C40F4 NSX400F 4P none (basic frame) 400 A 36 kA
C40F42D400 NSX400F 4P MicroLogic 2.3 400 A 36 kA
C40H32D400 NSX400H 3P MicroLogic 2.3 400 A 70 kA
C40H4 NSX400H 4P none (basic frame) 400 A 70 kA
C40H42D400 NSX400H 4P MicroLogic 2.3 400 A 70 kA
C40N3 NSX400N 3P none (basic frame) 400 A 50 kA
C40N31M320 NSX400N 3P MicroLogic 1.3 M 320 A 50 kA
C40N32D400 NSX400N 3P MicroLogic 2.3 400 A 50 kA
C40N32M320 NSX400N 3P MicroLogic 2.3 M 320 A 50 kA
C40N42D400 NSX400N 4P MicroLogic 2.3 400 A 50 kA

Selection and RFQ checklist for the C40H32D400

  • Rating: 400 A with MicroLogic 2.3, and the load current at the actual board temperature.
  • Poles: 3P, and whether the neutral must be switched.
  • Fault level: 70 kA Icu at 380/415 V AC against the prospective current.
  • Space: 140 mm x 255 mm x 110 mm and 6.05 kg.
  • Accessories such as auxiliary contacts, handles and terminal shields are separate references.

For the quotation please send the part number C40H32D400, quantity, system voltage and frequency, prospective fault current, delivery place and required date.

Size, weight and mounting of the C40H32D400

The C40H32D400 is a fixed-mounted breaker for a backplate, with front connections at top and bottom on a 45 mm pitch. The body is 140 mm wide, 255 mm high and 110 mm deep and weighs 6.05 kg.

This is a three-pole version without a neutral pole. For networks with a switched neutral, the four-pole references in the same frame are the alternative.

Power dissipation is 19.2 W per pole, a number to carry into the heat calculation of the enclosure.

Documents and quotation

The manufacturer datasheet for the C40H32D400 is attached on this page. It lists the ratings and dimensions summarised above, so compare it with your single-line diagram and short-circuit study before you order.

Send us the part number, quantity and a few lines about the installation and we will reply with availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not part of the manufacturer’s own sales network.

Datasheets & Documents
  • PDF Datasheet Schneider Electric C40H32D400 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric C40H32D400 ComPacT NSX400H 3P ML

Answers from our engineering team on installation, compatibility and integration.

01What trip unit does the C40H32D400 include?
The datasheet lists MicroLogic 2.3, an electronic trip unit with the function code LSoI. The long-time pick-up is 160 to 400 A.
02What is the breaking capacity of the C40H32D400?
It is 70 kA Icu at 380/415 V AC and 20 kA at 660/690 V AC according to the datasheet, with the code H 70 kA 415 V AC.
03Is the C40H32D400 a three-pole or four-pole breaker?
The datasheet lists 3P with protected poles 3D.
04What are the size and weight of the C40H32D400?
The datasheet gives 140 mm wide, 255 mm high and 110 mm deep, with a net weight of 6.05 kg.
05How is the C40H32D400 mounted and connected?
It is fixed, on a backplate, with front connections at top and bottom and a connection pitch of 45 mm.