Schneider Electric A9F53104 Acti9 iC60H 1P 4A B MCB
Description
A9F53104: Acti9 iC60H 1P 4 A B-curve breaker
The A9F53104 is an Acti9 iC60H miniature circuit breaker from Schneider Electric: 1P, rated 4 A, thermal-magnetic trip unit and B tripping curve. It has a single protected pole, used for one phase conductor in a single-phase final circuit. Seven Star LLC supplies the A9F53104 in Oman and the GCC as an independent supplier based in Muscat.
The reading of the reference follows the product title and datasheet fields, not a published ordering key: A9F53104 belongs to the iC60H range with 1 pole, a 4 A rating and curve code B. The datasheet was generated on 8 Nov 2026, and the figures below follow it.
Trip characteristics of the A9F53104
A thermal-magnetic breaker combines two mechanisms. The thermal element follows sustained overload and responds slowly, so a brief surge does not cause a nuisance trip. The magnetic element reacts to short-circuit current almost at once. On this unit the datasheet gives the magnetic tripping limit as 4 × In ± 20 %, which for a 4 A rating works out to roughly 12.8 A to 19.2 A, centred on 16 A. Inside that band the instantaneous element is expected to operate; below it, only the thermal element acts.
Curve B is the sensitive choice. With a magnetic limit of only 4 × In, the breaker reacts to modest fault currents, which makes it useful on long cable runs, at the far end of radial feeders and in systems where the earth-fault loop impedance is high and the available fault current is small. The trade-off is inrush: lamp transformers, small motors and power-supply banks may trip a B breaker at switch-on. The limitation class is 3 under EN/IEC 60898-1, which means the breaker restricts the let-through energy of a fault well below the prospective level.
Technical specifications of the A9F53104
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / A9F53104 |
| Range / product name | Acti9 / Disbo iC60 |
| Device short name | iC60H |
| Product type | Miniature circuit-breaker |
| Poles / protected poles | 1P / 1 |
| Rated current [In] | 4 A |
| Network type | AC/DC |
| Network frequency | 50/60 Hz |
| Trip unit | Thermal-magnetic |
| Curve code | B |
| Magnetic tripping limit | 4 x In ± 20 % |
| Icu at 12–60 V AC | 70 kA |
| Icu at 100–133 V AC | 70 kA |
| Icu at 220–240 V AC | 70 kA |
| Icu at 12–60 V DC | 20 kA |
| Icu at 60–72 V DC | 15 kA |
| Icn (EN/IEC 60898-1) | 10000 A at 240 V AC |
| Rated insulation voltage [Ui] | 500 V AC 50/60 Hz |
| Rated impulse withstand [Uimp] | 6 kV |
| Limitation class | 3 (EN/IEC 60898-1) |
| Dimensions (height, width, depth) | 85 × 18 × 78.5 mm |
| 9 mm pitches | 2 |
| Net weight | 0.125 kg |
| Mounting | Clip-on, DIN rail |
| Terminals | Single terminal, top or bottom: 25 mm² rigid, 16 mm² flexible |
| Operating temperature | -35–70 °C |
| Protection degree | IP20 (IEC 60529) |
| Mechanical / electrical durability | 20000 / 10000 cycles |
| Warranty | 18 months |
How the A9F53104 compares with related references
The table sets the A9F53104 beside nearby references from the same Acti9 iC60 family, each taken from its own datasheet. Width follows the number of poles at 9 mm per module, so the 1P version here is 18 mm wide. The Icu column shows the highest AC figure listed for each reference.
| Reference | Range and curve | Poles | Rated current | Width | Top AC Icu | Lifecycle |
|---|---|---|---|---|---|---|
| A9F53116 | iC60H B | 1P | 16 A | 18 mm | 42 kA | No notice |
| A9F53120 | iC60H B | 1P | 20 A | 18 mm | 42 kA | No notice |
| A9F53132 | iC60H B | 1P | 32 A | 18 mm | 42 kA | No notice |
| A9F53202 | iC60H B | 2P | 2 A | 36 mm | 70 kA | No notice |
| A9F53206 | iC60H B | 2P | 6 A | 36 mm | 42 kA | No notice |
Where the A9F53104 fits in Oman and the GCC
Breakers of this class are used in single-phase lighting and socket circuits in villas, offices, site cabins and utility rooms. This unit is typically selected for very small loads such as signalling, control-transformer primaries and instrument supplies, where a larger breaker would not protect the cable or load closely. Gulf installations bring their own concerns: high board temperatures in direct sun, dust ingress through cable entries, and humidity in coastal areas. The datasheet allows operation to 70 °C and 95 % humidity at 55 °C, but a board that runs hot also reduces the margin before the thermal element trips, so ventilation and derating deserve attention.
Curve B suits long villa and warehouse circuits where cable length limits the fault current.
Breaking capacity and DC use of the A9F53104
Breaking capacity is the largest fault current the device can interrupt. Icu is the ultimate capacity; Ics is the service capacity after which the breaker is still expected to remain usable, shown here as a percentage of Icu. The iC60H is the higher-capacity tier of the iC60 range. For this reference the datasheet lists 70 kA at 220–240 V AC and up to 70 kA at the lowest AC band, with Ics given as 100 % of Icu or more on the AC rows. The figures fall as the rated current rises, so read the row for the exact reference.
| Voltage | Icu | Ics |
|---|---|---|
| 12–60 V AC | 70 kA | 70 kA (100 %) |
| 100–133 V AC | 70 kA | 70 kA (100 %) |
| 220–240 V AC | 70 kA | 70 kA (100 %) |
| 12–60 V DC | 20 kA | 20 kA (100 %) |
| 60–72 V DC | 15 kA | 15 kA (100 %) |
Under EN/IEC 60898-1 the datasheet also lists 10000 A Icn at 240 V AC. The network type is AC/DC, and the DC ratings are limited to the voltage bands in the table (12–60 V DC and 60–72 V DC). On a DC system the pole count matters, so check how many poles must be in series for the system voltage rather than reusing an AC arrangement.
Selection checklist for the A9F53104
- Circuit: 4 A suits very small loads such as signalling, control-transformer primaries and instrument supplies, where a larger breaker would not protect the cable or load closely; confirm the cable rating and the load starting current.
- Poles: 1P is for one phase conductor in a single-phase circuit, with the neutral solid or switched elsewhere; make sure the system earthing matches.
- Fault level: available short-circuit current at the board must stay below 70 kA at the highest AC rating listed.
- Trip: B curve, magnetic trip around 16 A (± 20 %); compare with the expected fault current at the far end of the cable.
- Status: no discontinuation notice is shown on the datasheet date.
Connections, mounting and dimensions of the A9F53104
The A9F53104 clips onto a DIN rail and occupies 2 modules of 9 mm, a width of 18 mm, with a height of 85 mm and a depth of 78.5 mm. Net weight is 0.125 kg. A toggle operates it, a contact position indicator and a trip indicator show the state, and the lever can be padlocked, which helps with lock-out procedures.
Each pole has a single terminal at the top and at the bottom accepting up to 25 mm² rigid or 16 mm² flexible conductor. The datasheet specifies a wire stripping length of 14 mm and a tightening torque of 2 N.m, so use a calibrated screwdriver and a conductor cross-section suited to the 4 A rating and the installation method. The datasheet lists compatible Vigi iC60 and Quick Vigi iC60 add-on residual current devices, and earth-leakage protection is a separate block, not built into this breaker.
The operating range is −35 to 70 °C and humidity is rated at 95 % at 55 °C. The enclosure protection is IP20, so the breaker belongs inside a closed board.
Information to send with an RFQ for the A9F53104
- Exact reference A9F53104 and quantity.
- System voltage, number of phases and whether the circuit is AC or DC.
- Available fault level at the board and the cable size to be protected.
- Any matching add-on residual current block, auxiliary or accessory needed in the same order.
- Delivery location in Oman or the GCC and project timeline.
Documents and quotation
The manufacturer datasheet for the A9F53104 is attached on this page. It holds the specification summarised here; check the date and lifecycle notice against your project.
Send us the reference A9F53104, quantity and delivery location and Seven Star LLC will reply to your request. We supply as an independent supplier based in Muscat.
Datasheets & Documents
- Datasheet Schneider Electric A9F53104 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric A9F53104 Acti9 iC60H 1P 4A B MCB
Answers from our engineering team on installation, compatibility and integration.
01What is the rating of the A9F53104?
The datasheet lists a 1P Acti9 iC60H miniature circuit breaker with 4 A rated current, B curve and a thermal-magnetic trip unit for 50/60 Hz AC/DC networks.
02What is the breaking capacity of the A9F53104?
Icu is 70 kA at 220–240 V AC and 70 kA at 12–60 V AC under EN/IEC 60947-2; the datasheet lists DC ratings as well.
03At what current does the A9F53104 trip magnetically?
The magnetic tripping limit is 4 × In ± 20 %, which for 4 A is about 12.8 to 19.2 A. Overloads below this are handled by the thermal element.
04What terminals and mounting does the A9F53104 use?
Single terminals top and bottom accept 25 mm² rigid or 16 mm² flexible conductors; the breaker is 18 mm wide, occupies 2 modules and clips onto a DIN rail.
05Is the A9F53104 still available?
The datasheet shows no discontinuation notice on its date of 8 Nov 2026. Availability can change, so confirm stock when you enquire.