Brand: Schneider Electric
Schneider Electric A9C32816 iETL Extension for iTL, 1C/O+1NO
Description
A9C32816: iETL extension that adds a second contact group to an iTL relay
The A9C32816 is a Schneider Electric Acti9 product listed in the datasheet as: extension iETL iTL 16- 2P – 1C/ O+1NO -16A – coil 110VDC – 230 to 240V AC 50/60Hz. The A9C32816 is not a stand-alone relay. It is an extension module that clips on the right side of an iTL impulse relay and follows its state, adding contacts without taking another set of control wires. It gives one changeover and one normally open contact at 16 A. Seven Star LLC supplies the A9C32816 in Oman and the GCC as an independent supplier based in Muscat.
The title reads: iETL iTL 16 (the extension for iTL 16 A), 2P described as 1 C/O + 1 NO, 16 A, coil 110 V DC or 230 to 240 V AC 50/60 Hz. The datasheet lists a rated operational voltage of 415 V AC, impulse duration of 50 ms, a supply inrush of 19 VA and mounting on the right side of the TL.
Technical specifications of the A9C32816
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / A9C32816 |
| Description | extension iETL iTL 16- 2P – 1C/ O+1NO -16A – coil 110VDC – 230 to 240V AC 50/60Hz |
| Range of product | Acti9 |
| Product or component type | Extension for impulse relay |
| Device short name | iETL iTL 16 |
| Relay application | Remote control |
| Poles description | 2P |
| Pole contact composition | 1 C/O + 1 NO |
| [In] rated current | 16 A |
| Network type | AC |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 415 V AC 50/60 Hz |
| Control type | Toggle; Remote control |
| Control signal type | Impulse |
| Switching frequency | 5 switching operations/minute |
| Impulse duration | 50 ms |
| Remote control type | Illuminated push-button 3 mA |
| Local signalling | ON/OFF indication |
| [Uc] control circuit voltage | 230 to 240 V AC 50/60 Hz; 110 V DC |
| Supply inrush power | 19 VA |
| Mounting mode | Fixed, on right side of TL |
| Mounting support | 35 mm symmetrical DIN rail |
| 9 mm pitches | 2 |
| Height | 60 mm |
| Width | 18 mm |
| Depth | 84 mm |
| Electrical durability | AC-21: 200000 cycles; AC-22: 100000 cycles |
| Auxiliary connection terminal | Tunnel type terminals control circuit in 0.5 to 6 mm² |
| Standards | EN 669-1; EN 669-2-2 |
| Product certifications | GOST |
| Quality labels | NF; VDE; CEBEC; KEMA; IMQ |
| Noise level | 60 dB |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Relative humidity | 95 % at 55 °C |
| Ambient air temperature, operation | -20 to 50 °C |
| Ambient air temperature, storage | -40 to 70 °C |
How the A9C32816 works
An impulse relay stores its state mechanically: a short pulse moves the contact and a latch keeps it there with no coil current, and the next pulse moves it back. The iETL does not decide anything on its own; it is mechanically and electrically linked to the iTL beside it, so whatever the base relay does, the extension contacts do as well.
The extension is mechanically and electrically coupled to the main relay. When a pulse operates the iTL, the iETL contacts follow, so the number of switched circuits grows without extra push-button wiring. The datasheet lists a toggle control type and a remote control type of illuminated push-button 3 mA, and the range compatibility entry names the iTL and iTLi.
Control and contact data of the A9C32816
Coil voltage: 230 to 240 V AC 50/60 Hz; 110 V DC. Rated operational voltage: 415 V AC 50/60 Hz. Rated current: 16 A. Control type: Toggle; Remote control. Impulse duration: 50 ms. Switching frequency: 5 switching operations/minute. Remote control type: Illuminated push-button 3 mA. Supply inrush power: 19 VA. Electrical durability: AC-21: 200000 cycles; AC-22: 100000 cycles.
AC-21 and AC-22 are the load categories of IEC 60947: AC-21 refers to resistive loads including moderate overloads and AC-22 to mixed resistive and inductive loads. The higher cycle count for AC-21 shows that purely resistive circuits give the longer contact life.
Range and accessories around the A9C32816
The A9C30815 differs in contacts 1 NO + 1 NC against 1 C/O + 1 NO here. The A9C33811 differs in poles 1P against 2P here; contacts 1 NO against 1 C/O + 1 NO here; coil 230 to 240 V AC 50/60 Hz against 230 to 240 V AC 50/60 Hz here.
The datasheet lists compatible accessories and range members for this reference: Acti9 iTL; Acti9 iTLi. The comparison table lists the impulse relays of this group.
| Reference | Poles / contacts | Coil | Width |
|---|---|---|---|
| A9C30111 | 1P / 1 NO | 24 V AC 50/60 Hz, 12 V DC | 18 mm |
| A9C30115 | 2P / 1 NO + 1 NC | 24 V AC 50/60 Hz, 12 V DC | 18 mm |
| A9C30212 | 2P / 2 NO | 48 V AC 50/60 Hz, 24 V DC | 18 mm |
| A9C30811 | 1P / 1 NO | 230 to 240 V AC 50/60 Hz, 110 V DC | 18 mm |
| A9C30812 | 2P / 2 NO | 230 to 240 V AC 50/60 Hz, 110 V DC | 18 mm |
| A9C30814 | 4P / 4 NO | 230 to 240 V AC 50/60 Hz, 110 V DC | 36 mm |
| A9C30815 | 2P / 1 NO + 1 NC | 230 to 240 V AC 50/60 Hz, 110 V DC | 18 mm |
| A9C32816 (this page) | 2P / 1 C/O + 1 NO | 230 to 240 V AC 50/60 Hz, 110 V DC | 18 mm |
| A9C33811 | 1P / 1 NO | 230 to 240 V AC 50/60 Hz | 18 mm |
Selection checklist for the A9C32816
- Confirm the base relay is a 16 A iTL or iTLi and that the coil voltage matches.
- Leave room on the right side of the base relay for the 18 mm module.
- Check the pulse source: a push-button or a controller output that delivers a pulse of 50 ms to 1 s.
- Check the width of 18 mm (2 pitches) against free space on the rail.
- Check load type against AC-21 and AC-22 data, including inrush of LED or electronic loads.
Installation and maintenance of the A9C32816
Test a new installation by pressing each button station in turn and watching the ON/OFF indicator on the relay. A relay that toggles twice per press usually has an illuminated button leaking current or a bouncing contact; a relay that does not respond usually has a wrong coil voltage or an open neutral. Work with the supply isolated while wiring and record button positions on the board label for later maintenance.
Environmental data from the datasheet: -20 to 50 °C in operation, -40 to 70 °C in storage, relative humidity 95 % at 55 °C.
Where the A9C32816 is used in Oman and the GCC
Use it where a single impulse command must switch more than the pole count of the base relay: for example a stair-light circuit plus an indication contact, or lighting with a related fan. In GCC offices and hotels, it extends existing iTL relays without rewiring buttons.
Because the extension mounts on the right, plan the row so there is a free place on that side. Terminals take up to 6 mm squared, a larger capacity than the 4 mm squared on the iTL base. The extension should be ordered with the base relay’s coil voltage in mind; the datasheet lists 110 V DC and 230 to 240 V AC.
Information to send with an RFQ for the A9C32816
- Full reference (A9C32816) and quantity required
- Supply and control voltage at site, with the frequency
- Existing panel, rail and neighbouring devices it must fit beside
- Delivery location and timing
- Whether it is a spare, a like-for-like replacement or a new installation
- Number of push-button stations and whether they are illuminated
Documents and quotation
A datasheet for the A9C32816 is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it should be read together with the manufacturer’s installation instructions for the final design.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Other Models in the Se Acti9 Itl Range
Seven Star LLC supplies models from the Se Acti9 Itl range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric A9C30111 iTL 1NO 16 A Impulse Relay | Contactors & Overload Relays | View details |
| Schneider Electric A9C30115 iTLi 1NO+1NC 16 A Impulse Relay | Contactors & Overload Relays | View details |
| Schneider Electric A9C30212 iTL 2NO 16 A Impulse Relay | Contactors & Overload Relays | View details |
| Schneider Electric A9C30811 iTL 1NO 16 A Impulse Relay | Contactors & Overload Relays | View details |
| Schneider Electric A9C30812 iTL 2NO 16 A Impulse Relay | Contactors & Overload Relays | View details |
| Schneider Electric A9C30814 iTL 4NO 16 A Impulse Relay | Contactors & Overload Relays | View details |
| Schneider Electric A9C30815 iTLi 1NO+1NC 16 A Impulse Relay | Contactors & Overload Relays | View details |
| Schneider Electric A9C32816 iETL Extension for iTL, 1C/O+1NO | Contactors & Overload Relays | You are viewing this model |
| Schneider Electric A9C33811 iTLc 1NO 16 A Impulse Relay | Contactors & Overload Relays | View details |
Datasheets & Documents
- Datasheet Schneider Electric A9C32816 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric A9C32816 iETL Extension for iTL,
Answers from our engineering team on installation, compatibility and integration.
01What coil or control voltage does the A9C32816 use?
The datasheet lists 230 to 240 V AC 50/60 Hz, 110 V DC. Check this against the real control supply before ordering.
02What are the dimensions of the A9C32816?
The datasheet gives a width of 18 mm; see the table above for height and depth.
03How many contacts does the A9C32816 have and how are they arranged?
The datasheet lists 1 C/O + 1 NO. Check that this arrangement matches your control circuit before ordering.
04How is the A9C32816 mounted?
The datasheet gives: 35 mm symmetrical DIN rail.
05What ambient temperature range is listed for the A9C32816?
The datasheet lists -20 to 50 °C in operation and -40 to 70 °C in storage. In hot Gulf plant rooms the operating upper limit should be compared with the real panel temperature.